Добавил:
Опубликованный материал нарушает ваши авторские права? Сообщите нам.
Вуз: Предмет: Файл:

reading / British practice / Vol D - 1990 (ocr) ELECTRICAL SYSTEM & EQUIPMENT

.pdf
Скачиваний:
3
Добавлен:
17.07.2023
Размер:
30.18 Mб
Скачать

Special design features

GENERATOR Yrs

DISTRIBUTION BOARD

E2T:

-

A . P A

:

RELA , - T Ar, '

I I I I

qELA,

 

1

 

 

 

 

 

 

 

55

riCA SA l L A '

r.1 E.TIAwA

s, lEON. AN

 

 

 

 

 

 

 

!.:EGA.VATT

TARIFF

 

 

 

5

 

ND.EATIDNS

 

 

SRNCYPONPSINC.

 

 

 

METERING

 

L.7.AE

.1 - ac,. •

 

LO5C CONTROL 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

_i _ _ — ,,

/

 

 

-&'

EJ65

 

 

I

 

 

 

 

 

OPP: DELTA BURDEN

 

 

 

IF RECL, PED

---

I

 

 

---—.

 

 

 

-0- - - - - - - - - - - - - - - - E E5.

--

ET.

E '

 

Ail T OMA, 'DC vOLTAGE

OVEFIFLLAING PROTECTION

 

LOW FORwAn.

REGULATOR CHANNEL A

MO.TNTED ON RELAY °ANEL

 

POWER RELAY

POLE SLIPPING PROTECTION

 

 

J..1 TECiF.AL

 

ANL) VOLTAGE

O

FiLfYiNG CONTROL

OVER UNDER FREOUENCY

 

SUPPLY

PROTECTION S. VOLTAGE

 

AND FUSE PAIL DEL, CE

 

SUPERVISION RELA',

 

 

ELIPFA_Y SLIPER'i!SIGN RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I ' 24 '

 

 

 

I2 Li" L., 2 A

'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

I

 

I

 

I

 

 

 

I

 

 

 

 

AuTC3:,9ATIC +TC,

 

1:DVERFLUXING

PROTECDO- N

 

 

 

 

 

 

 

 

 

LTAGE

I

VOUNTED ON RELAY PANEL

 

LOLA FORWARD

 

 

 

 

PEGLILATCP CHANNEL

LOSS OF EXCITATION

 

 

 

 

 

 

Pov..ER RELAY

 

 

 

 

 

 

.t:TE;RRAL

, pc:01N.:C 'NON DIRECTIONAL

 

SUPPO'

 

 

 

 

:ERF,WONG CONTROL

I CVEPCLiPPENT PROTECTION

 

 

 

 

 

SUPERV I SION RELAY

 

 

 

 

AND TL.rSE DE

EP

 

 

 

VOLTAGE SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51;P•TRyisirrN 4

R",

 

 

 

 

 

FIG. 3:78 (cont'd) Generator VT connection arrangement

283

Transformers

Chapter 3

 

 

Flo. 3.79 Generator voltage transformer

(except in certain specific circumstances, which will be dealt with later).

The amount by which the transformation ratio departs from the ideal value is:

Phase angle error

0

Flu. 3.80 Phasor diagram for current transformer

(N 2 p4 1 )2 z Load

0

PRIMARY SUPPLY

VOLTS

[(Ka — Kn)/K,J 100%

(3.9)

where K T, is the turns ratio of the ideal transformer, given by N2/N1 and K a is the effective turns ratio given by 11/12.

It should be noted that this differs from the definition of current ratio errorgiven by BS3938: 1973[19J which is:

[(K0I2 — Ii)/II] 100 07o

(3.10)

i.e., the current which is assumed to be flowing in the primary on the basis of the measured current in the secondary (I2), minus the current actually flowing (1 ) divided by I. This becomes

[(Kn Ka)/K a ] 100%

(3.11)

MIMI is not the same as Equation (3.9) but, since the difference between K n and K a is usually small compared with both K, and K a , for practical purposes this will appear the same. The term 'current ratio error' is often abbreviated to simply 'ratio error'.

The phase angle error is the angle between the phasors representing the primary current and the secondary current reversed. This is conventionally taken as

FlG. 3.81 Conventional equivalent circuit for transformer

positive when the secondary current phasor reversed leads the primary current phasor.

Since there is a wide band of primary currents within which the transformer will operate below saturation then, provided the secondary current remains within that determined by the rated burden, it is possible for the current transformer designer to make some correction for the ratio error. For example, if it were required to design a CT having the ratio 1000: I, and over the operating range the ratio error varied in magnitude between 0.2% and 0.5% then, by using 998 turns on the secondary for a single primary turn, the actual error over the operating range would be minimised. From this, it will be seen that the larger the number of primary turns, the greater the accuracy with which compensation can be carried out. Such compensation does not, of course, affect the phase-angle error.

It will be evident from the above that reduction of the current and phase angle errors can be obtained for any given operating condition by reducing the exciting

284

Special design features

ri.• ••••

ampere-turns in relation to the secondary winding ampere-turns. This can be achieved by shortening the flux.path and increasing the cross-sectional area of the core. Hence, ideally, a ring construction having the smallest practical diameter and greatest practical cross-

section should be used.

A significant reduction in errors can be achieved by increasing the number of turns on primary and secondary windings. The reason for this is that, assuming no change in burden, the secondary EMF necessary to circulate the required secondary current remains constant. However, if this is induced into an increased number of turns, the volts/turn are reduced, the flux density is reduced and hence the exciting current, which is the source of the error, will be reduced. It can be shown that provided operation is within the linear part of the magnetisation curve, the error is approximately inversely proportional to (turns) 2 . This is an approximate relationship since, as with power transformers, no parameter can be changed in isolation from all others. Increasing the number of turns inevitably increases the resistance of the secondary winding, thus needing an increased EMF to circulate the required current. This can be offset by increasing the conductor cross-section but since this itself increases the length of mean turn, only partial benefit results.

The above also emphasises the benefits to be gained by minimising secondary burdens so that, although the impedance of relays or other equipment cannot be changed, leads can be made as large as practicable, thereby minimising voltage drops.

At this point it is appropriate to identify and examine the different requirements of current transformers for measurement and protection purposes.

BS3938: 1973 defines the accuracy classes of measurement current transformers in much the same way as does BS3941 for voltage transformers. Classes 0.1, 0.2, 0.5, 1, 3 and 5 have permitted current errors of ±0.1, ±0.2, ±0.5, ±1, ±3 and ±5% respectively at 120 070 of rated current. (Permitted errors are also quoted for intermediate currents. The full range is shown in Tables 3.3 and 3.4.) The performance during fault

or transient conditions is not of interest for most measurement applications; in fact it might be advantageous if the CT saturates under these conditions, since this limits the overvoltage applied to the connected equipment.

For protective current transformers, the performance under fault conditions is critical and for these the concept of composite error is introduced in BS3938. This is defined as:

100

(3.12)

p

where the symbols and suffixes have the same meanings as defined above except that i, and i p are instantaneous values. T is the period of one cycle of the supply.

As can be seen, this expression has the form of an RMS quantity and takes into account the harmonic content and phase shift of the secondary current. Composite error is defined at the rated accuracy limit primary current which may be several times the rated primary current. The ratio of accuracy limit current to the rated current is known as the accuracy limit factor. Protective CT classes are defined in accordance with their permitted composite errors and BS3938 lists Classes 5P and 10P having composite errors of 5 and 1007o respectively. The corresponding permitted current errors at rated current are ± 1% and +3%.

For protective CTs, a high degree of absolute accuracy is not important, provided that a reasonable degree of accuracy is obtained at the required overcurrent level. For this reason, turns compensation is not generally applied to such transformers.

The above remarks are mainly applicable to protective CTs used for overcurrent protection. For most other protection applications, the most important feature is the maximum useful EMF which can be obtained from the CT under system fault conditions. In this context BS3938 defines the knee point EMF of

TABLE 3.3

Limits of error for current transformers accuracy for Classes 0.1 to 1

 

± percentage current (ratio)

 

± phase displacement at percentage of rated curren

 

 

 

 

shown below

 

 

 

error at percentage of rated

 

 

 

 

 

 

 

 

 

 

 

 

current shown below

 

 

 

 

 

 

Class

 

minutes

 

 

centiradians

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 up to

20 up to

100 up to

10 up to

20 up to

100 up to

10 up to

20 up to

100 up to

 

but not

but not

120

but not

but not

120

but not

but not

120

 

incl. 20

incl. 100

 

incl 20

incl 100

 

incl

incl 100

 

 

 

 

 

 

 

 

 

 

 

0.1

0.25

0.2

0.1

10

8

5

0.3

0.24

0.15

0.2

0.5

0.35

0.2

20

15

10

0.6

0.45

0.3

0,5

1.0

0.75

0.5

60

45

30

1.8

1,35

0.9

 

2.0

1.5

1.0

120

90

60

3,6

2.7

1.8

 

 

 

 

 

 

 

 

 

 

285

Transformers

Chapter 3

 

 

TABLE 3.4

Limas of error for current transformers accuracy for Classes 3 and 5

 

± percentage current (ratio)

Class

error at perc ntage of rated

 

current sh own below

 

 

 

 

50

100

 

 

 

3

3

3

5

5

5

 

 

 

the CT as 'That sinusoidal EMF of rated frequency applied to the secondary terminals ... which, when increased by 10 6/o, causes the exciting current to increase by 50 07o'. CTs specified in terms of knee point FMF (as well, of course, as rated primary current and turns ratio) are designated Class X Protective Current Transformers by BS3938 and are permitted a turns ratio error of +0.25 07o.

2.7.4 Current transformer construction

Current transformers for measurement and protection purposes are required throughout a power station auxiliary system. Most frequently it is convenient to locate these within switchgear, for which the barprimary arrangement is the most suitable in terms of strength and simplicity.

Current transformers used on generator voltage busbar systems are also, in effect, bar-primary devices with features developed specifically to meet the requirements of the system. Figure 3.69 shows current transformers at the neutral end of a 660 MW generator. It is necessary to wind the secondary turns on the very large diameter toroidal core in order to provide the air clearance required to meet the 70 kV power frequency, 170 kV impulse-withstand insulation levels of the generator busbars. For a 660 MW machine, the rated busbar current is 20 000 A so that, if the final secondary current is to be 5 A, a ratio of 20 000: 5 is required. With a bar-primary, 4000 secondary turns would thus be needed and some manufacturers consider it more economic to carry out this transformation in t wo stages. Main CTs installed at the generator busbars having a ratio of, say, 20 000: 20 are used in conjunction with additional interposing transformers of ratio 20 5. The interposing transformers are pre-

ferably located as close as possible to the generator busbars to minimise the length of leads required to carry 20 A.

3

References

[ 1 1

British Standards Institution: BS171: Specification for power

 

transformers: 1970

121

Blume L. F., Boyajian A., Carnifli G., Lennox T. C., Mined

 

S. and Montsinger V. M.: Transformer Engineering: John

 

Wiley and Sons

( 3 1

British Standards Institution: BS1432: Specification for copper

 

for electrical purposes. Strip with drawn or rolled edges: 1970

Montsinger V. M.: Loading transformers by temperature: Trans. AIEE Vol 49 pp 776: 1930

BS Code of Practice CP1010: Loading guide for oil-immersed transformers: 1975

Shroff D. H. and Stannett A. W.: A review of paper aging in power transformers: Proc. 1EE, Vol 132, Part C, No.6: November 1985

Franklin A. C. and Franklin D. P.: The 3 and P Transformer Book, 11th Edition: Butterworths: 1983

British Standards Institution: BS5750: Quality systems:

Part 1: Specification for design, manufacture and installation: 1979

Part 2: Specification for manufacture and installation: 1979 Part 3: Specification for final inspection and test: 1979 Part 4: Guide to the use of BS5750, Part 1: 1981

Part 5: Guide to the use of BS5750, Part 2: 1981 Part 6: Guide to the use of BS5750, Part 3: 1981

19J International Electrotechnical Commission: Publication 76, Power Transformers

[10]British Electricity Boards Specification: BEBS-T2: Specification for transformers and reactors: 1966

111] The Electricity Council: Document IT: Guide on impulse testing power transformers and reactors

[12]British Standards Institution: BSI48: Specification for unused mineral insulating oils for transformers and switchgear

1984

[131 Wilson A. C. M.: Insulating liquids and their uses, manufacture and properties: Peter Peregrinus Ltd

1141 The Electricity Council: Recommendation G.5/3: Limits for harmonics in the UK electricity supply system: September 1976

[15]Corbyn D. B.: This business of harmonics: Electronics and Power, Vol 18 pp 219-223: 1972

[16]The Electricity Council: Report ACE15: Harmonic distortion caused by converter equipment

[17]British Standards Institution: BS3941: Specification for voltage transformers: 1975 (1982)

[18]Wright A.: Current transformers, their transient and steady state performance: Chapman and Hall Ltd

[19]British Standards Institution: BS3938: Specification for current transformers: 1973 (1982)

286

CHAPTER 4

Generator main connections

1Introduction

1.1Evokition

2Principles of isolated phase busbar operation and forces encountered

2.1Principles

2.2Forces

2.3Voltage rise

3Designing an IPB system

4Forced cooling

4.1Forced air cooling

4.2Liquid cooling

4.3Water cooling

5System description

5.1Line end

5.2Neutral end

5.3Tee-offs

5.4Delta connections

5.5Excitation busbars

5.6Earth bar

6Setting out the specification

7Component parts of an IPB system

7.1Conductor and enclosures

7,2 Equipment enclosures

7.3 Insulators

7.3.1 Post insulators

7,3.2 Foot insulators (including enclosure supports)

7.3.3Disc bushings

7.3.4Wall seals

7.3.5Bellows

7.4Conductor and enclosure expansion joints 7 5 Flexible connectors

7.5.1Flexible laminae connectors

7.5.2Braided flexible connectors

7.6Painting

7.7Conditioned air

7.8Voltage transformers

7.9Current transformers

7.10Environmental conditions

7.11Portable earth access covers

7.12Viewing ports

7.13Connection of the conductor to plant

7.14Joints in the conductor

7.15On-load temperature measurement 7,16 VT cubicles

7.17Access platforms

7.18Structural steelwork

7.19Neutral earthing equipment

7.20Site installation

7.21Quality assurance

8 Testing

8.1 Tests on component parts

8.1.1Insulators and bushings

8.1.2Busbar material

8.1.3Transformers

8.1.4Loading resistors

8.1.5Capacitors

8.1.6Switchgear and earthing switches

8.1.7Compressed air system

8.2Tests on representative sections of IPB

8.3Test levels

8.4Tests at site

9 Experience of testing

10 Generator voltage switchgear

11Earthing

12Earthing for maintenance purposes

12.1Primary earth

12.2Portable drain earths

13Protection

14Interlocking

15Future trends

15 References

1 Introduction

The principal function of the Main Connections Busbar System is to connect the generator to its associated

generator transformer and, incidentally, to provide a convenient means of connecting the Unit electrical

system to the Unit transformer, via a tee-off. It is present day practice, for reasons explained later, to use an aluminium tube for each phase conductor (or

busbar), which is surrounded by a concentric enclosure of the same material and similar conducting crosssectional area; each is effectively isolated from its neighbour, hence the term isolated phase busbar (IPB). British practice (1988) uses dry conditioned air at a pressure slightly above atmospheric as the insulating medium between the conductor and enclosure.

The conductor is supported at the centre of the enclosure by insulators; these are equispaced and rigidly

287

Generator main connections

Chapter 4

 

 

fixed around the circumference of the enclosure but allow limited radial movement of the conductor. The rating of the main connections installation is established on the basis of temperature rise above a specified ambient at maximum commercial load and its ability to withstand both three-phase short-circuit and earth fault conditions anywhere on the generator voltage system without damage. These requirements introduce some complication in the system design in order to achieve high integrity. Isolated phase busbars have evolved over a number of years, having originally been pioneered in the USA and further developed in France before their introduction in the UK in the mid-1960s. They represent 3-4% of the total cost of the connected generator and transformers. A typical installation is shown in Fig 4.1.

1.1Evolution

There has been extensive development of generator connection designs since their introduction because of larger generating sets and the consequential increase in load and fault currents. Clearly a cable connection to the machine is simplest, but both current and temperature limit their use to about 120 MW (assuming a generator terminal voltage of approximately 23 kV). Consequently, for larger machines, three bare copper conductors (one/phase) were introduced, supported by single insulators at regular intervals and enclosed within a common duct or enclosure (Fig 4.2 (a)). Aluminium gradually replaced copper for the conduc-

tor, primarily on economic grounds, once aluminium welding techniques had improved. The duct or enclosure only excluded gross pollution and prevented physical contact, giving no protection against phase- to-phase faults or the electromagnetic forces between conductors. Strong magnetic fields from this arrangement could cause overheating of external steelwork adjacent to the busbars, increasing system losses.

As currents increased, phase barriers made of either a metallic or insulating material were introduced to li mit the consequences of phase-to-phase flashover (Fig 4.2 (b)). Further improvement was achieved by the use of phase segregation, using a continuous metallic fabricated-aluminium enclosure and barrier, the barrier being integral with the enclosure (Fig 4.2 (c)).

Whilst phase segregation offered an improved design compared with the original common enclosure, it still had a number of weaknesses. Phase-to-phase faults were still possible because adjacent phase conductors share a common barrier. Complicated circulating currents in the enclosure produced forces between conductor and enclosure because no attempt had been made to isolate the busbars magnetically, and the assembly generally became large and exacting to construct. Such designs were used for generators up to 500 MW before new designs were introduced to deal with the shortcomings of phase segregation. These are insulated by enclosing each phase in its own conducting metal tube separate from its neighbours; hence the name isolated phase busbars'. In an installation of this type, eddy currents are induced in the enclosure, or sheath, due

 

 

 

 

ifFItiglio

\

),--,,

EXCITER

liklir

 

 

 

CONNECTIONS

EARTH

 

 

 

 

r-

 

 

 

 

SWITCH

 

 

 

i

,

 

NEUTRAL

\

 

 

 

CONNECTIONS

 

 

\

GENERATOR

 

 

t-,

 

 

CONNECTIONS

 

 

 

 

,A... .-..:a.

 

 

 

 

 

,...-

 

 

 

 

\

I1 i,

 

 

 

UNIT

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

EARTHING

 

 

 

 

VT

TRANSFORMER

 

 

 

 

 

 

 

 

 

CUBICAL

 

 

 

EXCITER

ISOLATED

 

 

 

PHASE

 

 

 

FIELD

 

 

 

ASSEMBLY

 

 

 

SW/TCH

 

 

 

EXCITER

 

 

ni

 

 

 

 

NEUTRAL RECTIFIER

 

 

EARTHING

 

 

 

MODULE

 

 

FIG. 4.1 Generator main connections — general arrangement of a typical installation

288

Principles of isolated phase busbar operation and forces encountered

OUCT OR

ENCLOSURE

CONDUCTOR

SUPPORT

INSULATOR

z1NTERPHASE BARRIERS

,r. ETALLIC OR INSULATING,

^+E., -& ea , egalea DS

Darr.er$

CONTINUOUS METALLIC FABRICATED ENCLOSURE aNCUJOING BARRIERS

Ph3se seg•egated sus C; \

INSULATING FEET

FIG. 4.2 Segregated and non-segregated busbars

to the conductor current, and this to some extent shields I he forces between the conductors by modifying the field around the conductor. There are, however, still

substantial magnetic fields outside the enclosure, which produce forces between phases. These are reduced con-

siderably if the extreme ends of each phase enclosure are bonded together, thereby allowing a balanced cur-

rent flow in the enclosures of all three phases. This system is known as an 'electrically - continuous IPB with

short-circuit' (see Fig 4.3). Each phase enclosure is made electrically continuous throughout its length and all three are connected together at both ends of the run. This distinguishes it from other systems, namely the insulated type (where the enclosure is not continuous hut includes non-conducting sections) or the continuous

[ Me with saturable impedance, where the continuous phase enclosures are connected together at the ends of

the run through small saturable reactors which limit the induced longitudinal currents to a design value. The last-named appears attractive because the reactor limits the enclosure circulating currents during normal opera- ti on, thereby reducing the enclosure losses, and during

fault conditions the reactor saturates, reducing its impedance to circulating currents and allowing greater enclosure current to flow. As will be explained later, this enclosure current reduces the forces between conductors during fault conditions. However, in practice, the reactors tended to burn out, so now only the elec- trically-continuous 1PB with short-circuit is considered in the UK and elsewhere. These, by virtue of the enclosure circulating currents, limit forces between phase conductors to approximately 10 07o of those that would exist without the enclosure.

The enclosure system is earthed at one point only and is insulated from earth along its length by supporting it on insulated foot mountings, thereby giving control over the path followed by any fault current in the enclosure. Clearly the main connections have now become a system in their own right and to control the circulating currents, as described, the enclosures must be isolated from all items of plant to which the conductors are connected. Enclosures are therefore connected to auxiliary plant via rubber bellows which maintain the physical protection of the conductor but isolate the enclosures electrically from the plant. The bonding or short-circuiting of the enclosures is done as close to the end of their run as possible. The external magnetic fields produced by the conductor currents can link with conducting loops in the adjacent steelwork, producing circulating currents and heat. This is a problem to be considered by the designer since excessive heat, in addition to being an unnecessary system loss, can cause unacceptable expansion and can be a hazard to personnel if the steelwork is touched.

Machines of 660 MW are now used extensively in the UK and an IPB installation of the type described provides an adequate main connections design which can be naturally cooled and is of manageable size. This probably represents the limit of naturally cooled designs and any significant increase in machine rating will mean that forced-cooled designs will have to be considered. The components of one phase of such a system are shown diagrammatically in Fig 4.4.

2 Principles of isolated phase busbar operation and forces encountered

2.1Principles

Consider, using simple analysis, how the magnetic fields may be reduced. When a conductor carries an alternating current, it produces an external concentric alternating magnetic field, the direction of which is determined by application of the 'corkscrew' rule. If another conductor runs parallel to it, then an EMF is induced in it, given by e = — (c1(1)/dt), where cl) is that proportion of the flux linking the two conductors. The negative sign indicates that it tries to oppose the force which created it.

289

Generator main connections

Chapter 4

 

 

FG. 4.3 Phase isolated busbar — continuous sheath

For a length of isolated phase busbar, the voltage Se induced in an elemental section of non-continuous sheath (say, SA and SB in Fig 4.5 (a)) due to the current flowing in its associated conductor will be the same magnitude for all elements on the circumference of the sheath at any point along its length. It follows, therefore, that one phase in isolation can have no current flow in the sheath, since the voltages at all points are equal.

If next, the condition in Fig 4.5 (b) is considered, the voltage e induced in an elemental section of noncontinuous sheath due to the current flowing in an adjacent conductor will be of different magnitude for each position around the periphery (say, SC and SD), since each element cuts a different proportion of flux from that conductor. Therefore, unequal voltages are available to cause current to flow in the sheath as shown in Fig 4.6 (a). This sheath current, which for the elemental circuit shown in Fig 4.6 (a) can be considered as a simple `go' and 'return' circuit, will set up an electromagnetic field whose direction can be determined by application of the corkscrew rule. This will give rise to a reduction of field within the enclosure but a reinforcement of the field outside as shown in Fig 4.6 (b). Thus the, e is a reduction of forces between the conductors and an increase in forces exerted on the enclosure. The enclosure will therefore need substantial supports.

The currents circulating in each sheath caused by the proximity effects of adjacent conductor systems are termed 'eddy currents'. Formulae for determining these currents and their associated losses have been proposed by H. B. Dwight in 1923 and F. W. Carter

in 1927. In the paper by Carter [I], the eddy current was determined by considering the fixed distribution of conductor currents but taking into account the magnetic field set up by the induced eddy current in the sheath itself. This first order eddy current was then determined for neighbouring sheaths and these were used as a fixed distribution to obtain second and further subsidiary eddy currents in the original sheath. The process may be repeated to any degree of approximation to obtain a total eddy current. In Dr Carter's day, the problem did not merit meticulous calculation and the treatment was therefore simplified by considering only the first order eddy current to produce results in a convenient form for hand calculation. Working independently, Dr Dwight tackled a number of proximity effect problems and in 1923 published a first order eddy current solution [2] for sheath eddy loss which is identical to the Carter solution. Later, in 1964, the analysis was extended to determine the subsidiary eddy currents for the particular case of a single-phase circuit and also a three-phase flat grouping.

Since the non-continuous type of IPB is not used by the CEGB, the theory is not developed here, but the reader may deduce the necessary formulae from papers [1 and 2].

Now consider the continuous type of IPB. If the sheaths of all three phases are electrically connected at each end of the IPB run, an external path is provided which allows the sheath currents to flow in the manner shown in Fig 4.3. The phase conductors and the enclosures are comparable to the primary and secondary turns of a short-circuited transformer. The

290

TRANSFORMER END

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GENERATOR END

 

 

 

 

 

 

 

 

 

 

 

 

 

ENCLOSURE EXPANSION

 

 

 

 

 

 

 

 

 

JOINT FOUR SETS OF

 

 

 

 

 

 

 

 

 

 

FIVE FLEXIBLE

 

NEOPRENE

 

 

 

 

 

 

 

 

BRIDGING STRAPS

 

BELLOWS

 

ENCLOSURE

 

INSULATOR

 

 

-

 

 

 

 

MAIN

CONDUCTOR

 

 

 

11"v""....a----...din7_

1

 

GENERATOR

EXPANSION JOINT

 

 

 

 

MAIN

TERMINAL

CONDUCTOR STALK

 

III!

 

 

...1

000

Str.

"1".1

 

Jr.

INSULATED BELLOWS

FOOT

SUPPORTING

STEELWORK

DISC BUSHING

CONDUCTOR

TERMINAL PALMS

(EIGHT OFF)

TRANSFORMER

BUSHING

NOTE THIS IS A DIAGRAMMATIC COMPOSITE TO ILLUSTRATE THE MAIN SYSTEM COMPONENTS IT IS NOT A

TYPICAL ARRANGEMENT AND IS

NOT DRAWN TO SCALE

TERMINAL

CANDELABRA CONNECTIONS (ONLY 3 SHOWN)

Fici. 4.4 Phase isolated busbar — main components

encountered forces and operation busbar phase isolated of Principles

Generator main connections

Chapter 4

 

 

 

B O.,

Al nil

 

;a) induced voltages in an enclosure due to its own conductor

 

•D •

 

.c

0

 

 

 

 

a

magnetic field produced by the primary conductor induces a current of opposite direction in the secondary turn. The magnitude of the circulating sheath current is almost equal to the conductor current, depending on the resistance and reactance of the enclosure circuit, and is in antiphase to the conductor current. The sheath current usually amounts to about 90% of the conductor current.

The circulating sheath current creates its own surrounding magnetic field which must be in antiphase to that produced by the conductor, thus the magnetic field still exists within the enclosure but is cancelled outside it (see Fig 4.6 (c)). Since the enclosure has resistance, the resultant external magnetic field around each conductor is about 10% of that which would occur if there was no metallic sheath.

Since the external magnetic field has been reduced, it follows that the forces between conductors are also reduced by a similar proportion, as will be the forces between enclosures that exist due to the current flowing in them.

CD However, end effects occur where the conductor is connected to its associated piece of plant and is, for practical reasons, unshielded. Therefore magnetic fields at these points are much stronger and forces greater. For further analysis, the reader is referred to a paper by Skeats and Swerdlow [3].

2.2 Forces

(b)Induced voltages in an enclosure due to an adjacent conductor

Fin. 4.5 Induced voltages in an enclosure

The forces caused by short-circuit and earth fault currents are very complex. Neglecting decrements, a totally-offset short-circuit current can be represented

ENCLOSURE

EDDY

CURRENTS

(a} Enclosure eddy currents in a phase isolated buster • dscontinuous sheath

FIG. 4.6 Radial current flows due to current in an adjacent conductor

292

Соседние файлы в папке British practice