29.8. SUMMARY OF PID CONTROL TERMS

2301

29.8Summary of PID control terms

PID control can be a confusing concept to understand. Here, a brief summary of each term within PID (P. I, and D) is presented for your learning benefit.

29.8.1Proportional control mode (P)

Proportional – sometimes called gain or sensitivity – is a control action reproducing changes in input as changes in output. Proportional controller action responds to present changes in input by generating immediate and commensurate changes in output. When you think of “proportional action” (P), think prompt: this control action works immediately (never too soon or too late) to match changes in the input signal.

Mathematically defined, proportional action is the ratio of output change to input change. This may be expressed as a quotient of di erences, or as a derivative (a rate of change, using calculus notation):

Gain value = ΔOutputΔInput

Gain value = dOutput = dm dInput de

For example, if the PV input of a proportional-only process controller with a gain of 2 suddenly changes (“steps”) by 5 percent, and the output will immediately jump by 10 percent (ΔOutput = Gain × ΔInput). The direction of this output jump in relation to the direction of the input jump depends on whether the controller is configured for direct or reverse action.

A legacy term used to express this same concept is proportional band : the mathematical reciprocal of gain. “Proportional band” is defined as the amount of input change necessary to evoke fullscale (100%) output change in a proportional controller. Incidentally, it is always expressed as a percentage, never as fraction or as a per unit value:

Proportional Band value = ΔOutputΔInput

Proportional Band value = dInput = de dOutput dm

Using the same example of a proportional controller exhibiting an output “step” of 10% in response to a PV “step” of 5%, the proportional band would be 50%: the reciprocal of its gain ( 12 = 50%). Another way of saying this is that a 50% input “step” would be required to change the output of this controller by a full 100%, since its gain is set to a value of 2.

Integral value (repeats per minute) =

2302

CHAPTER 29. CLOSED-LOOP CONTROL

29.8.2Integral control mode (I)

Integral – sometimes called reset or floating control – is a control action causing the output signal to change over time at a rate proportional to the amount of error (the di erence between PV and SP values). Integral controller action responds to error accumulated over time, ramping the output signal are far as it needs to go to completely eliminate error. If proportional (P) action tells the output how far to move when an error appears, integral (I) action tells the output how fast to move when an error appears. If proportional (P) action acts on the present, integral (I) action acts on the past. Thus, how far the output signal gets driven by integral action depends on the history of the error over time: how much error existed, and for how long. When you think of “integral action” (I), think impatience: this control action drives the output further and further the longer PV fails to match SP.

Mathematically defined, integral action is the ratio of output velocity to input error:

Integral value (repeats per minute) = Output velocity

Input error

dm dt

e

An alternate way to express integral action is to use the reciprocal unit of “minutes per repeat.” If we define integral action in these terms, the defining equations must be reciprocated:

Input error

Integral time constant (minutes per repeat) = τi = Output velocity

e

Integral time constant (minutes per repeat) = τi = dm

dt

For example, if an error of 5% appears between PV and SP on an integral-only process controller with an integral value of 3 repeats per minute (i.e. an integral time constant of 0.333 minutes per repeat), the output will begin ramping at a rate of 15% per minute ( dmdt = Integral value × e, or

dm = e ). In most PI and PID controllers, integral response is also multiplied by proportional gain,

dt τi

so the same conditions applied to a PI controller that happened to also have a gain of 2 would result in an output ramping rate of 30% per minute ( dmdt = Gain value × Integral value × e, or dmdt

= Gain value × e ). The direction of this ramping in relation to the direction (sign) of the error

τi

depends on whether the controller is configured for direct or reverse action.