6.5.4ADIO Alarms Detail

6.5.4.1View Details

This menu item enables the user to select an ADIO device (i.e., Cordex Smart Peripheral) that is connected to the CXC and view the alarms with respect to: Cell Deviation, Current, Voltage, Temperature, and Comms.

6.5.5Alarm Hysteresis

6.5.5.1Voltage

Voltage Hysteresis applies only to Voltage Alarms (6.5.3.5). This value is the voltage range where the alarm can clear or activate. For example, if the low voltage alarm activates at 43.00V, having a voltage hysteresis of 0.50V means it will clear when the voltage reaches 43.50V.

6.5.5.2Time

Time Hysteresis is the amount of time in seconds that the condition has to be true before the alarm is enunciated. In the example above, if the value of time hysteresis is 5 seconds, the voltage must be below 43.00V for at least 5 seconds before the alarm is activated. Similarly, to clear the alarm, the voltage must be above 43.50V for 5 seconds.

This feature is used only for the following:

Current, Voltage, Battery, and Temperature alarms

HVSD and CEMF controls.

6.5.6Alarm Tone

This feature is found under the Global Alarm Configuration menu (submenu of Alarms) and the tone is enabled by default. The Supervisor may enable/disable the Audible Alarm Buzzer (tone). Enabling the Loud Buzzer option increases the pitch and volume of the buzzer.

Figure 45–Global Alarm Configuration LCD and web interface

0350046-J0 Rev C

Page 59 of 127