6.4.5.3Remote BT Mode

This feature will force a transition to BT mode when a user-defined condition (custom alarm) is true.

Enable

This menu item enables the Supervisor to control the CXC’s Remote BT feature.

Remote BT (Custom 1-20)

This menu item enables the Supervisor to assign the Custom Alarm (see 6.5.3 Configure Alarms) number between 1 and 20.

NOTE: This feature is exclusive for the Cordex series of rectifiers. If Remote BT is active and a rectifier other than the Cordex series is added to the system then Remote BT will be aborted.

6.4.5.4Battery Properties (See 6.4.8)

The “Battery Properties” button at the bottom of the Battery Test window is a link to the Battery Properties window.

The return path (the menu structure) will remain intact; i.e., the user will return through the window where the Battery Properties button was tapped.

6.4.6Battery Current Termination (BCT) Equalize

Refer to Section 3.7.3 for feature overview.

Since the BC Threshold is in amps, it has to be set with caution since the battery current input has limited accuracy. If it is too low, the threshold may never be reached. The threshold should be at least twice as large as the jitter on the battery current input. If this limitation forces the threshold to be set higher than desired, the BCT Duration can be increased slightly to compensate.

6.4.6.1Enable

This menu item enables the Supervisor to control the CXC’s BCT Equalize feature.

6.4.6.2Duration

This menu item enables the Supervisor to program the duration of the BCT Equalize in hours.

6.4.6.3BC Threshold

This menu item enables the Supervisor to program the threshold (in amps) for the battery charging current that will trigger the BCT Equalize.

6.4.6.4Battery Properties (See 6.4.8)

The “Battery Properties” button at the bottom of the BCT Equalize window is a link to the Battery Properties window.

The return path (the menu structure) will remain intact; i.e., the user will return through the window where the Battery Properties button was tapped.