4.3.4Battery Discharge Test or Battery Test (BT) Mode

The battery discharge test is used to update the status of the lead acid battery capacity. BT can be set to run automatically or can be initiated manually (via Mode Selection button).

4.3.4.1Definitions

End/Terminal Voltage — The voltage at which the test will end or terminate. Timeout — The maximum time the test will be permitted to run before it is aborted. Period in Days — The time between each Auto-BT.

Battery On Discharge (BOD) Alarm — This alarm will indicate that the battery is discharging.

4.3.4.2Manual Activation

The user can manually activate the test by tapping the BT mode selection button (Figure 7).

4.3.4.3Auto-BT Feature

This feature will enable the CXC to start a test automatically on a periodic basis. The Supervisor may enable or disable the feature in (BATTERIES) BATTERY TEST\AUTO-BT menu, see 6.4.5.2.

4.3.4.4Tips on Using the BT Mode

Use Charge Current Control (6.4.3) to limit the battery recharge current to the battery manufacturer’s specified maximum value.

The resultant battery capacity estimate will be more accurate if the test is started when the battery is fully charged. If a recent discharge has occurred within the last 96 hours, when a mode change to BT is selected, a dialog box will prompt the user to confirm the mode change.

During a test, the runtime hours will be accessible through the Analog Signals display or Mode Status screen. The runtime hours will reflect the time remaining in the test.

The runtime will be displayed after the start of an outage and when a BOD condition is detected; i.e., battery is sourcing current and voltage is below open circuit.

When a test is started by the remote BT feature, the battery log will show “Remote BT” in the Event Type column.

The BT depth of discharge (DOD) can be accessed via the Analog Signals Display; provides an additional indication of test progress.

BT information is available via the CXC’s battery log web page when a test is in progress. In addition, the new battery capacity estimate can be accessed via the Analog Signals display at any time before, during or after the test.

0350046-J0 Rev C

Page 19 of 127

Refer to the back of this manual for Factory Service and Technical Support contact information

4.3.4.5BT Initiation

When the test begins, an entry will be made in the event log. If enabled, an alarm will provide a warning to indicate that a Battery Test is in progress.

The test will continue, depending on the type of rectifier in use, in accordance with the following algorithms (as applied to lead acid batteries):

Algorithm 1 — For rectifiers that support Battery Test (BT) mode:

1.A command is sent to put the rectifiers into BT mode.

2.BT mode runs for the period set as Timeout or until BT End Voltage is reached.

Algorithm 2 — For (Pathfinder) rectifiers that do not support BT mode:

1.Rectifiers are commanded to go to nominal voltage.

2.The rectifiers are periodically scanned to be sure that they do not begin sourcing current. When 3% DOD is reached and the rectifiers are still not sourcing current, the rectifiers are turned off.

3.The rectifier float setting is reset to the setting stored in the system controller.

4.When the system voltage reaches the end (termination) voltage or a timeout occurs, the system controller will command the rectifiers to turn ON and enter FL mode.

4.3.4.6Activity During BT Mode

Temp Comp and Power Save features are suspended during a battery test. When the battery is discharging, a BOD alarm will be active.

During a test, the mode symbol in the upper left corner of the GUI will be similar to the FL mode symbol except that the letters “FL” will be replaced with “BT.”

Runtime estimate begins at 3% DOD.

Capacity estimate also begins at 3% DOD, but will not be stored unless DOD > 20%; the point at which reasonable accuracy can be assured.

4.3.4.7AC Failure During BT Mode

If the AC fails during a battery test, the test will be aborted. This will place the rectifiers into a state that will enable them to resume providing power to the load when AC returns. If the Runtime is being displayed, it will continue to update.

4.3.4.8Addition of Rectifiers During BT Mode

If rectifiers are added to the system when a battery test is active, they will be placed into the same state as the other rectifiers. They will be:

Placed into BT mode (for rectifiers that support BT mode), or

Placed into remote shutdown, or

Set to the same voltage as the other rectifiers.

4.3.4.9Conditions to Watch for During BT Mode

If the voltage drops below 47V before or when 3% DOD is reached, the test is aborted and the battery capacity is set to 0% (resulting in a Battery Capacity Low alarm). This provides an indication that the battery is very weak2. The battery capacity must be manually reset to 100%, or to the percentage of expected battery capacity before the next battery test is started, in order for the battery monitor to again attempt to compute the battery capacity.

If rectifiers are seen to be sourcing current during the test and the battery ceases to be discharging, the test is aborted.

4.3.4.10Canceling BT Mode

BT mode can be cancelled by changing mode to FL or EQ.

2 In some cases, incorrect battery parameters can cause this condition to occur with a good battery.