Добавил:
Опубликованный материал нарушает ваши авторские права? Сообщите нам.
Вуз: Предмет: Файл:

reading / British practice / Vol D - 1990 (ocr) ELECTRICAL SYSTEM & EQUIPMENT

.pdf
Скачиваний:
9
Добавлен:
17.07.2023
Размер:
30.18 Mб
Скачать

Low voltage switchgear, controlgear and fusegear

FIG. 5.47 3.3 kV fused units of Whipp and Bourne manufacture, generally as depicted in Fig 5.46 but

Shown withdrawn and tilted for inspection/maintenance. The left hand unit features a vacuum switching device and that on the right an air-break interrupter.

Utilisation category

— AC4.

Mechanical endurance — 1 million no-load operating cycles.

• Substantially non-inductive loads switched on for long periods

Rated duty — uninterrupted. Utilisation category — AC1 Mechanical endurance — 0.3 million no-load operating cycles.

Additionally, contactors shall be capable of making tt nd carrying the specified prospective short-circuit current of the system, as limited in magnitude and duration by the associated circuit short-circuit protective device, i.e., fuselinks.

The co-ordination between the contactor and the circuit short-circuit protective device, in accordance

oith 13S4941: Part 1: Appendix C, is basically as follows:

Type b co-ordination for equipment utilising overload devices to BS4941: Part 1.

Type c co-ordination for equipment utilising overload relays to BS142.

Type b co-ordination accepts that the characteristics of any overload relay may be altered per-

manently. Type c co-ordination requires that no damage (including permanent alteration of the characteristics of any overload relay) shall occur.

However, light burning of contacts, and risk of their welding — the latter provided that no flashover occurs — is accepted.

6.2 Design and construction

6.2.1 General

This section describes the design and construction of the switchgear, controlgear and fusegear found on the 415 V and lower voltage systems. The requirements outlined are those for equipment concerned directly with the control of operational plant. They are not necessarily applied in non-operational plant areas, e.g., offices, welfare blocks, stores, etc. Henceforth in the text, the switchgear, controlgear and fusegear will be

referred to simply as

the switchgear,

In AC applications,

the switchgear is classified into

two duty classes commensurate with the severity of

the system conditions. These duty classes are:

Duty Class I For use in systems where the power factor of short-circuit current is extremely low, e.g., where the switchgear is connected in relatively close proximity to the source of generation. Duty Class 1 is the normal requirement.

Duty Class 2 For use in 'distribution' systems in which the power factor of short-circuit is not likely to be lower than 0.3.

Mostly the switchgear is arranged in multi-circuit switchboard formations accommodated in purpose built switchrooms. However, it is expedient in certain instances to locate items, such as small motor starters and distribution fuseboards, local to the plant involved.

Except in the case of distribution fuseboards, although there is now a tendency towards grouping starters into small multi-motor control centre formations, the requirement 'local to plant' is largely for single-circuit units — floor standing or wall mounted.

Main switchboards, i.e., unit and station auxiliaries switchboards, usually comprise a combination of circuit-breakers, fused motor starters and fused distribution gear. The incoming supply circuits of such switchboards are almost always circuit-breakers. In many cases the supply to the switchboard is derived from a 3.3 kV/415 V transformer housed in the switchboard — the high voltage feed being by cable connected directly to the transformer HV terminals. The switchgear includes all protective and interposing relays, main and any necessary interposing current trans- . formers, transducers, instruments, control, selector and test switches.

393

Switchgear and controlgear

Chapter 5

 

ItG, 5.48 3.3 kV switchboard of Reyrolle manufacture. The three left hand units are 'fused equipments Class Sl4A' and the three right hand units are 'air circuit-breakers Class SA'.

(see also colour photograph between pp 496 and 497)

The general assembly of the switchgear complies with BS5486: Low voltage switchgear and controlgear assemblies: Part 1, Specification for type-tested and partially type-tested assemblies (general requirements): thich is identical with IEC Publication 439-1: 1985.

However, for power station service it is necessary to augment and interpret the British Standard as outlined below. Representative switchboard formations are shown in Figs 5.49 to 5.51. Typical examples of the individual cubicle arrangements, air circuit-breakers

394

Low voltage switchgear, controlgear and fusegear

395

Switchgear and controlgear

Chapter 5

 

 

 

 

 

 

 

 

 

= =

=

=

= =

=

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:4>

 

 

 

 

L_J

 

 

 

 

 

 

 

 

 

 

LI

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

"

 

 

 

 

 

 

 

 

 

 

 

 

 

. 21

 

 

 

 

 

 

 

 

 

7r=j

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.9.]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

j

(

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

71I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.yj

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

_

B RCNNN

Lon•NCE

D GAM/

 

GENERAL

EOPMPS5

FOPuTTPSS

 

SE RtLE E A A

.EATER BAT

HEATER BAT

 

COW.ESSOR

COARVOLU

CONTROLS

 

ALA OATER 2

NSTRUNENTATION INSTRUMENTATION

 

 

COMPRESSOR AT4COmPARESSOR

 

 

 

A4RORYER

 

Lc,' GREEN

JWYIIE

YELLOW

 

SPARE

FOALIMPTA

SPARE

 

APED.

NEATER OAT

IEGUIRRECT

 

 

CONTROL .1

 

 

 

lrysTROVENTAILON

 

 

 

AIR COmP , ESSCR 2

 

 

 

 

c

 

TE L LON,'

0 AL ACA

V RED

 

socTe,c,eR

TO TULIPS A

GENERAL

 

HIll CGORRSSSOR lEATER BAT

SERLICES

 

STAGE

CONTROL A

AIR COMPRESSOR

 

 

INST.LIMENTATION

AF FERCOOLER

 

 

Alp COYPRESSOR PAN 2

COOLING FAN 1

wHITE

0 YELLOW

0 BROWN

SOOT BLOWER

4155

LISA AUX

AIR COMPRESSOR

CHIMNEY

BOIL ERHOUSE

PAOTOR HEATER I

SERVICES

BOARD,CHIAINEr

 

BOARD

PLANT BOARD 2

 

SECTION 2

FEEDER

BLPTC

0 RED

 

SOOTBLOwER

raTvOC

 

AIR C OM PRE S SOB

CONTROL

 

MOTOR HEATER 2

BATTERY

 

 

CUBICLE

 

0 BLUE

ORANGE

 

SOOT BL ENTER

FLOODLIGHT

 

AIR COMPRESSOR

TOWER II

 

MOTOR HEATER 3

 

 

RED

9ROWN

ORANGE

scrovaLCNE

FOR'JJMTAA

GENERAL

ALA COMPRESSOR

SEATER BAY

SERVICE AIR

2NC STAGE

CONTROL I.

COMPRESSOR

-IA.% °VW' 5

,NSTRUmENTATON INTERCOOLER

 

ARA COMPRESSOR &ONAOER

 

7.001I52 FA'22 FAN

A

vimiTE

GREEN

 

SPARE

CHIMNEY

I UN—EOUIPPED

WASH CRAIN

 

PUMP

 

BLACK

 

MISCALL

 

ANECTUS

 

TRACE

 

HEATING

 

SECTION 2

 

V BLUE

 

249VAC

 

CUBICLE

 

HEATERS

 

I TV AC. DC

 

TEAT SUPPLIES

A YELLOW

0 RED

0 WHITE

IL SLUE

LIST CHIMNEy

SOOTEILOWER

SOOTTILOwER

SOOTBLO.ER

PLANT BOARD

AIR Comp R ESSOR

AIR COMPRESSOR

AIR COMPRESSOR

I NTERCONNECTOR

SF STAGE LAB

ST STAGE LUB

COOL NO WATER

 

OIL ROAR A

OIL PUMPS

PUMP 5

 

E3 ORANGE

C. BLACK

VSROwN

 

SERVICES

SOCRIILOWR

SPARE

 

DISTRIBUTION

AIR COMPRESSOR IUN—ECUIPPED

 

&NAPO 2

COOLING

 

 

 

WATER PUMP A

 

FIG. 5.50 Typical 415 V switchboard of Electric Construction Co manufacture

and starter equipment that comprise the switchboard formations are illustrated in Figs 5.52 to 5.54.

Basically, switchgear arranged in switchboards is of Form 4 to BS5486. The 'Form' of construction determines the degree of separation by barriers and partitions (within the switchgear structure) of the major components. 'Form 4' specifies the separation of bus- bars from the functional units, and separation of all functional units, including their outgoing terminals, one from the other. Essentially, the whole of the busbar system up to the point of connection to the short-circuit protective devices of each circuit must be capable of withstanding a short-circuit at any point other than in the immediate vicinity of the short-circuit. There

of course, be damage from arcing at the point of short-circuit. Also, the whole switchboard assembly must withstand any external fault. In the event of an internal arcing fault on any functional unit, the damage

must, as far as possible, be confined to that unit, so that the busbars and all other functional units remain fit for service. In addition to the basic requirements of BS5486, specialised equipment and components, e.g., circuit-breakers, contactors, fuse-switches, etc., must comply with the appropriate British Standard.

Withdrawable and removable parts (see Definitions in BS5486) of the same manufacture, type, rating and duty must be interchangeable. Withdrawable and removable parts of the same manufacture, type and rating, but of different circuit duty must be interchangeable, subject to any necessary modification to auxiliary circuits, protective devices, etc.

Handling equipment, e.g., lifting devices, is provided for withdrawable and removable parts exceeding 25 kg gross weight.

The use of hygroscopic or flammable materials is avoided as far as practicable. Terminals in which a

396

co

FIG. 5.51 Typical 415 V swifchboarcl of Flo:fro-Mechanical l`vialinfacitiring Co mantilaotfie

(see also colour photograph heiwceu pp 496 and 497)

 

fusegear and controlgear switchgear,voltage Low

CUBICLE VENT

TOP APERTURE COVER

CONTROL FUSES

AND LINKS

 

 

 

 

 

 

 

 

 

 

 

 

VOLTMETER

 

 

 

 

 

SWITCH

 

 

Q

 

 

 

 

 

 

v I

 

 

 

 

 

e —

 

—LOCKING

 

 

 

 

HASP

 

 

 

 

 

 

 

 

 

 

 

NEUTRAL BUSBAR

 

----

 

 

 

 

 

 

 

 

 

 

 

 

LOCAL CONTROL

 

 

 

 

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOCAL REMOTE

 

 

SELECTOR SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P V.C.GA$BAEFLE

 

 

 

 

ARC CHUTES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOOR HANDLE

 

 

 

 

CLOSING MECH.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR CIRCUIT

 

 

 

 

 

BREAKER

 

 

 

SHUTTER LOCKING

 

 

 

 

 

 

 

 

 

 

 

270V D.C. MONITOR

 

 

 

LAY — TYPE VAA11

 

 

 

 

 

 

 

 

 

 

 

 

AUTO TRIP FLAG

I

 

 

 

 

INDICATION

 

 

 

RELAY — TYPE VA F

 

 

 

 

 

 

 

il

HEATER INDICATION

ftva LAMP (BLUE)

- HEATER SWITCH

HEATER LINK

HEATER FUSE

TRIP SUPERVISORY

RELAY — TYPE VAX 31

SHUTTER LOCKING

LEVERS

SHUTTER

FRONT VIEW

FIG. 5.52 GEC type N.1180 415

PARALLELING

CONNECTIONS

iNTERTRIP RECEIVE — RELAY —TYPE VAJY13

RESTRICTIVE EARTH

FAULT

RELAY — TYPE CAG 14

BUCHHOLZ

RELAY—TYPE VAAll

BUSBARS

NEUTRAL LINK

NEUTRAL/EARTH

CONNECTION AND

NEUTRAL CABLE RISERS

BUSBAR CHAMBER

BARRIER

CABLE SIDE CONNECTIONS

CABLE SIDE NEUTRAL

CONNECTIONS

MASTER TRIP

RELAY —TYPE VAJY11

STANDBY EARTH FAULT

RELAY — TYPE COG 14

MAIN CABLE GLAND PLATES

(BOTTOM ENTRY)

EARTH CONNECTIONS

SIDE VIEW

REAR VIEW

V air cireidl-bri,iaker cubicle, used iypically :is switchboard incoming, interconticciing and bosbar-sectioning equipmeni

f

JeabloJluop pue .leaEqi!Aiss

Low voltage switchgear, controlgear and fusegear

ARC CHUTES

POSITION INDICATOR

OPERATION COUNTER

ARCING CONTACTS

MOVING CONTACTS

FIXED CONTACTS

ISOLATING

CONTACTS

SLIDE RAIL

AUXILIARY SWITCHES

REAK ER RACKING MECH

COVER PLATE

MANUAL TRIP BUTTON

LOCKING FLAP

LOCKING BOLT

MANUAL CLOSING MECH

COVER PLATE

VENTILATION GRILL

H

FRONT PLATE

FIG. 5.53 DEC type M80 circuit-breaker shown withdrawn from cubicle

399

Switchgear and controlgear

Ch

 

 

VIEW INSIDE TOP

COMPARTMENT

D ROPP E R

COMPARTMENT

FUSE SWITCH

L--71

AUML;ARY SWITD•1

CONTACTOR

ANINIE7ER CT 40/1

OVERLOAD RELAY

I NTERPOSING RELAYS

TEST SWITCH

TRANSFORMER 415/110V

Flu. 5.54 Typical interior of a motor control unit fitted to the type of switchboard illustrated in Fig 5.50

screw compresses a bare wire conductor directly are not permitted. Whilst, in general, no diversity factor is allowed for Duty Class 1 equipment, the provisions of BS5486: Part 1 in this respect are accepted for Duty Class 2.

As for switchgear at the other voltages, the temperature rise of terminals for external cabling must not, when carrying rated operational current continuously, exceed 50 ° C, or the limits specified in the appropriate

apparatus specification, whichever is the lower. All main conductors and incoming/outgoing terminals must be identified with their phase/polarity colours, presently in accordance with BS158. The colours at the various points of identification must be of durable material and a minimum of 300 mm 2 in area. Because in the course of time the adhesive may fail; thus allowing 'unwinding' and introducing the risk of fault, identification by taping is not accepted.

400

 

 

 

 

 

 

 

 

 

 

Low voltage switchgear, controlgear and fusegear

 

 

 

 

 

 

 

 

 

 

 

0,2

 

 

closures

 

In the case of outdoor equipment, any fixings which

 

 

 

 

of necessity pierce the Walls of the enclosure for

 

 

 

 

 

 

 

1 ti,..lo‘tires. unless specified or approved otherwise, are

 

the attachment of external fittings must begas-

 

ii:ctal. ventilated naturally, and provide a degree of

 

 

 

ketted. Exceptions to this rule are the fixings of

 

 

 

 

Oil to 13S5400 as follows:

 

 

 

 

 

 

labels. These may penetrate the walls of the enclo-

 

 

,I mpinent for

indoor use — Code IP31.

 

sure provided that they do not exceed 5 mm dia-

 

 

meter and are effectively sealed. Fixings for the

 

,luirineni for outdoor use — Code IP44, or of

 

attachment of outdoor enclosures to supporting

 

 

 

 

 

 

'first' and 'second' numeral as necessary.

 

structures must not pierce the walls of the enclosure.

 

 

.2!Icr

 

 

 

 

 

ichgear featuring withdrawable parts, the spe-

To protect persons against electric shock, the provi-

,

 

 

dciirce of protection must obtain whether the

sions of protection by barriers or enclosures, protec-

 

 

 

 

 

 

the connected or disconnected posi-

tion by insulation of live parts and protection by using

. „„ T ment is in

 

 

 

.i nd must be independent of the fitting of closing

protective circuits, specified in BS5486: Part 1, are

 

 

 

' or other sealing arrangements at the point of

followed.

 

 

 

 

if external

cabling. Unless the specified degree

 

Particular requirements with respect to doors and

 

rrotectiOn provi cled by the enclosure is maintained

covers are:

 

 

 

or c \ample, shutters or shrouding, temporary

Hinged doors shall open not less than 90 0 but, in so

 

 

 

 

are supplied for use when withdrawable or re-

 

doing, the movement must be limited to prevent

-

 

,, He

parts are removed. Such covers have captive

 

 

 

damage to equipment mounted on the doors, and

 

 

iries and padlocking facilities.

 

 

 

 

also damage, or the application of tension, to wiring

 

\,.liiicionallv, all enclosures must provide:

 

 

 

connecting equipment on doors to that in the static

 

 

 

 

 

 

 

 

 

 

\,L cqu aie support of withdrawable parts during with-

 

part of the enclosure.

 

 

,h

- ,ok al, and when left in the disconnected position.

• All indications must be clearly visible when doors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

po,iti‘e restraint of a withdrawable part at the limit

 

are closed, and the equipment available for service.

 

 

 

 

 

 

the means adopted must require deli-

 

Additionally, to assist in the prevention of unau-

 

 

rite

manual manipulation before it •is possible to

 

thorised interference with the intended functioning

 

Ji ,engage the withdrawable part from the enclosure.

 

of the equipment, provision is made for padlocking

\.ces to main and auxiliary contacts from the front

 

all doors closed.

 

 

 

 

 

of

he

equipment. Access to fuses in control and

• Doors and covers which give access to parts live at

 

Luixiliarv circuitry, relays, instruments, etc., is nor-

 

main circuit voltage are secured by fastenings, e.g.,

 

talk from the front of the equipment in the case

 

screws and nuts, the release of which necessitates

 

ol L'ontactor controlgear, but usually from the rear

 

the use of tools. Fastenings intended primarily for

 

, , t) circuit-breaker

equipment.

 

operation by coins are not acceptable in this context.

I or

work in safety on the de-energised side of any

As far as is practicable, bus wiring is segregated from

 

.11,111) circuit isolating device with adjacent main

 

 

 

 

 

live. This is a most essential requirement

all other wiring and run in ducting, conduit, etc.,

 

 

 

 

Ls rarely possible, other than during planned

preferably metallic. Largely from considerations of

 

, htitLlov. n , in the

more important switchboards to

mechanical security, the minimum permissible cross-

 

mak,: dead circuits

other than those requiring par-

sectional area of bus wiring is 2.5 mm 2 .

 

:1L.o

 

 

auenticm

Iso, any main circuit parts which

 

To facilitate efficient operation of the switchgear,

 

 

remain fix

lieu access has been gained to the

the following dimensional limits above operating floor

 

:merior of an cii,loure, other than through doors

level are observed wherever possible:

 

 

 

, ki ■

cr-, secured by fastenings necessitating the

 

 

 

 

 

 

 

 

tools, must

be further enclosed to prevent

Overall height

2600 mm (max)

 

LLdeIttaI touching by persons. The aim in such cases

Operating handles — (highest

2000 mm (max), 450 mm (min)

 

 

lo achieve a degree of protection of not less than

 

I 1);() (co 13S5490), Where it is physically impossible

 

and lowest positions reached

 

 

 

by an operator's hand),

 

 

:0 meet this requirement in respect of the contact

 

protective relays, instruments

 

 

.. Tries

of the larger sizes of fuse-switch and fuse

 

and mechanical indicators

 

 

 

 

 

 

t he openings must be as small as practicable

Doors and panel handles/locks

2000 mm (max), 300 mm (min)

 

Li.,inutaciuring tolerances will allow; additionally,

 

 

 

 

 

 

tna ■

be deemed necessary to fit 'obstacles' to

 

 

 

 

 

 

 

 

To promote a movement of air through the switchgear

 

 

slruct access

by

hands/fingers.

f or

a

cce ss to main circuit fuselinks only when they

that is sufficient to prevent condensation when it is

out of service, heaters of the metalclad black heat

 

 

 

 

 

,ire dead.

 

 

 

 

 

pattern are provided within the enclosures.

401

Switchgear and controlgear

Ch

 

 

6.2.3 Cabling arrangements

Wherever practicable, external cabling is arranged to enter equipment from below. To allow some freedom of choice as to the type of cabling used in a particular circumstance, main circuit terminals must be suitable for the reception of conductors of either copper or aluminium, and arranged to minimise the bending of t he cores.

The main circuit terminals of each functional unit in a switchboard are enclosed separately in an air insulated compartment or barriered section/subsection of earthed metal or approved insulation material. Such a compartment may also accommodate current transformers for instrument and protection purposes.

Terminals for the connection of external control and auxiliary circuits are grouped and positioned relative to the main circuit with which they are associated. Whilst not necessarily so in the past, it is in most cases now policy to enclose each group separately, and thus reduce the risk of work or a fault on one group jeopardising another.

Ali terminal arrangements must, with cables connected, ensure achievement of the clearances and creepage distances shown in Tables 5.1 and 5.2.

TABLE 5.1

Indoor equipment

 

Minimum clearance

 

Minimum creepage, mm

hquipmeni

in air between

 

 

 

 

CTI less

CTI 200

phases and from

 

 

 

 

phase to earth, mm

 

than 200

or greater

 

 

 

 

 

Duty Class

19

 

25

19

Duly Class 2

19

 

19

19

 

 

 

 

 

 

TABLE 5.2

 

 

 

Outdoor equipment

 

 

 

 

 

Equipment

Minimum

 

Minimum creepage, mm

 

 

 

Duty Clases

clearance

 

CTI less

CTI 200

1 and 2

in air, mm

 

 

than 200

or greater

 

 

 

 

 

 

 

 

Idetv,een phases

25

 

38

25

Phase to earth

25

 

25

25

 

 

 

 

 

The physical disposition of main circuit cabling relative to auxiliary cabling at the point of entry into the equipment enclosure is arranged to minimise the risk of fault or fire on the former affecting the proper function of the latter. For this reason, where the design of equipment necessitates the installation of lengths of both main and auxiliary incoming/outgoing cabling within the enclosure, the former is segregated from the latter by earthed metal or other mechanically robust

fire-resistant material. Cable armour alone is not cepted as satisfying this requirement.

Terminal boxes and gland plates for single-core L. bles rated in excess of 400 A are required to be designe, specifically to minimise the production of inducet., currents.

Gland plates are supplied on the basis of one plat per cable gland, and must be detachable to facilitate drilling to suit by the cable contractor.

Insulation must be so mounted and the method of attachment of connections thereto such as to minimise the likelihood of mechanical overstressing during normal tightening of the mounting and connection fixings. Particular care is taken to ensure that expansion and contraction of components shall have no damaging effect, having especial regard to the temperatures likely to be attained under fault conditions. Additionally, the configuration of the surfaces of insulation must be designed to minimise the accumulation of airborne pollutants.

6.2.4 Electrical clearances and creepage distances

As a general rule, the electrical clearances and creepage distances shown in Tables 5.1 and 5.2 are observed as minima. However, some relaxation is permitted specifically in the following areas:

Contactors and associated overload protective devices may have clearances and creepage distances not less than those specified in BS5424: Part 1: Appendix B.

Circuit disconnectors (isolating devices), fuse-switches, switched and other disconnectors may have clearances not less than 12.5 mm.

The relaxed dimensions may be maintained on connections to the terminals of these components for a distance not exceeding 40 mm.

The clearances shown must be maintained irrespective of any insulation applied, unless such insulation is capable of withstanding the full power frequency high voltage test.

6.2.5 Busbar systems

The busbar circuit of a switchboard comprises the complete conductor system up to its points of connection to the circuit disconnecting/protective devices of the functional units. Typical busbar circuits are illustrated in Fig 5.55.

Main and tee-off busbars are contained in separate compartments within the switchboard. They are usually air-insulated, but may feature solid insulation at the option of the manufacturer. Where insulation is other than by air, it must be in the form of sleeving with joints encased in moulded or similar covering. Because of the possibility of deterioration with age,

402