
reading / British practice / Vol D - 1990 (ocr) ELECTRICAL SYSTEM & EQUIPMENT
.pdf
Low voltage switchgear, controlgear and fusegear
FIG. 5.47 3.3 kV fused units of Whipp and Bourne manufacture, generally as depicted in Fig 5.46 but
Shown withdrawn and tilted for inspection/maintenance. The left hand unit features a vacuum switching device and that on the right an air-break interrupter.
Utilisation category |
— AC4. |
Mechanical endurance — 1 million no-load operating cycles.
• Substantially non-inductive loads switched on for long periods
Rated duty — uninterrupted. Utilisation category — AC1 Mechanical endurance — 0.3 million no-load operating cycles.
Additionally, contactors shall be capable of making tt nd carrying the specified prospective short-circuit current of the system, as limited in magnitude and duration by the associated circuit short-circuit protective device, i.e., fuselinks.
The co-ordination between the contactor and the circuit short-circuit protective device, in accordance
oith 13S4941: Part 1: Appendix C, is basically as follows:
•Type b co-ordination for equipment utilising overload devices to BS4941: Part 1.
•Type c co-ordination for equipment utilising overload relays to BS142.
Type b co-ordination accepts that the characteristics of any overload relay may be altered per-
manently. Type c co-ordination requires that no damage (including permanent alteration of the characteristics of any overload relay) shall occur.
However, light burning of contacts, and risk of their welding — the latter provided that no flashover occurs — is accepted.
6.2 Design and construction
6.2.1 General
This section describes the design and construction of the switchgear, controlgear and fusegear found on the 415 V and lower voltage systems. The requirements outlined are those for equipment concerned directly with the control of operational plant. They are not necessarily applied in non-operational plant areas, e.g., offices, welfare blocks, stores, etc. Henceforth in the text, the switchgear, controlgear and fusegear will be
referred to simply as |
the switchgear, |
In AC applications, |
the switchgear is classified into |
two duty classes commensurate with the severity of |
|
the system conditions. These duty classes are: |
Duty Class I For use in systems where the power factor of short-circuit current is extremely low, e.g., where the switchgear is connected in relatively close proximity to the source of generation. Duty Class 1 is the normal requirement.
Duty Class 2 For use in 'distribution' systems in which the power factor of short-circuit is not likely to be lower than 0.3.
Mostly the switchgear is arranged in multi-circuit switchboard formations accommodated in purpose built switchrooms. However, it is expedient in certain instances to locate items, such as small motor starters and distribution fuseboards, local to the plant involved.
Except in the case of distribution fuseboards, although there is now a tendency towards grouping starters into small multi-motor control centre formations, the requirement 'local to plant' is largely for single-circuit units — floor standing or wall mounted.
Main switchboards, i.e., unit and station auxiliaries switchboards, usually comprise a combination of circuit-breakers, fused motor starters and fused distribution gear. The incoming supply circuits of such switchboards are almost always circuit-breakers. In many cases the supply to the switchboard is derived from a 3.3 kV/415 V transformer housed in the switchboard — the high voltage feed being by cable connected directly to the transformer HV terminals. The switchgear includes all protective and interposing relays, main and any necessary interposing current trans- . formers, transducers, instruments, control, selector and test switches.
393

Switchgear and controlgear |
Chapter 5 |
|
ItG, 5.48 3.3 kV switchboard of Reyrolle manufacture. The three left hand units are 'fused equipments Class Sl4A' and the three right hand units are 'air circuit-breakers Class SA'.
(see also colour photograph between pp 496 and 497)
The general assembly of the switchgear complies with BS5486: Low voltage switchgear and controlgear assemblies: Part 1, Specification for type-tested and partially type-tested assemblies (general requirements): ■thich is identical with IEC Publication 439-1: 1985.
However, for power station service it is necessary to augment and interpret the British Standard as outlined below. Representative switchboard formations are shown in Figs 5.49 to 5.51. Typical examples of the individual cubicle arrangements, air circuit-breakers
394

Low voltage switchgear, controlgear and fusegear
395

Switchgear and controlgear |
Chapter 5 |
|
|
|
|
|
|
|
|
|
= = |
= |
= |
= = |
= |
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
- |
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
21 |
|
|||||||
|
|
|
|
|
|
|
|
|
|
7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
, |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
:4> |
|
|
|
|
L_J |
|
|
|
|
|
||||
|
|
|
|
|
LI |
|
|
|
L |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
" |
|
|
|
|
|
|
|
|
|
|
|
|
|
. 21 |
|
|
|
||
|
|
|
|
|
|
7r=j |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
.9.] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
j |
• |
( |
3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
71I |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
.yj |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
_ |
B RCNNN |
Lon•NCE |
D GAM/ |
|
GENERAL |
EOPMPS5 |
FOPuTTPSS |
|
SE RtLE E A A |
.EATER BAT |
HEATER BAT |
|
COW.ESSOR |
COARVOLU |
CONTROLS |
|
ALA OATER 2 |
NSTRUNENTATION INSTRUMENTATION |
|
|
|
COMPRESSOR AT4COmPARESSOR |
|
|
|
|
A4RORYER |
|
Lc,' GREEN |
JWYIIE |
YELLOW |
|
SPARE |
FOALIMPTA |
SPARE |
|
APED. |
NEATER OAT |
IEGUIRRECT |
|
|
CONTROL .1 |
|
|
|
lrysTROVENTAILON |
|
|
|
AIR COmP , ESSCR 2 |
|
|
|
|
c |
|
TE L LON,' |
0 AL ACA |
V RED |
|
socTe,c,eR |
TO TULIPS A |
GENERAL |
|
HIll CGORRSSSOR lEATER BAT |
SERLICES |
|
|
STAGE |
CONTROL A |
AIR COMPRESSOR |
|
|
INST.LIMENTATION |
AF FERCOOLER |
|
|
Alp COYPRESSOR PAN 2 |
COOLING FAN 1
wHITE |
0 YELLOW |
0 BROWN |
SOOT BLOWER |
4155 |
LISA AUX |
AIR COMPRESSOR |
CHIMNEY |
BOIL ERHOUSE |
PAOTOR HEATER I |
SERVICES |
BOARD,CHIAINEr |
|
BOARD |
PLANT BOARD 2 |
|
SECTION 2 |
FEEDER |
BLPTC |
0 RED |
|
SOOTBLOwER |
raTvOC |
|
AIR C OM PRE S SOB |
CONTROL |
|
MOTOR HEATER 2 |
BATTERY |
|
|
CUBICLE |
|
0 BLUE |
ORANGE |
|
SOOT BL ENTER |
FLOODLIGHT |
|
AIR COMPRESSOR |
TOWER II |
|
MOTOR HEATER 3 |
|
|
RED |
9ROWN |
ORANGE |
scrovaLCNE |
FOR'JJMTAA |
GENERAL |
ALA COMPRESSOR |
SEATER BAY |
SERVICE AIR |
2NC STAGE |
CONTROL I. |
COMPRESSOR |
-IA.% °VW' 5 |
,NSTRUmENTATON INTERCOOLER |
|
|
ARA COMPRESSOR &ONAOER |
|
|
7.001I52 FA'22 FAN |
A |
vimiTE |
|
GREEN |
||
|
||
SPARE |
CHIMNEY |
|
I UN—EOUIPPED |
WASH CRAIN |
|
|
PUMP |
|
|
BLACK |
|
|
MISCALL |
|
|
ANECTUS |
|
|
TRACE |
|
|
HEATING |
|
|
SECTION 2 |
|
|
V BLUE |
|
|
249VAC |
|
|
CUBICLE |
|
|
HEATERS |
|
|
I TV AC. DC |
|
|
TEAT SUPPLIES |
A YELLOW |
0 RED |
0 WHITE |
IL SLUE |
LIST CHIMNEy |
SOOTEILOWER |
SOOTTILOwER |
SOOTBLO.ER |
PLANT BOARD |
AIR Comp R ESSOR |
AIR COMPRESSOR |
AIR COMPRESSOR |
I NTERCONNECTOR |
SF STAGE LAB |
ST STAGE LUB |
COOL NO WATER |
|
OIL ROAR A |
OIL PUMPS |
PUMP 5 |
|
E3 ORANGE |
C. BLACK |
VSROwN |
|
SERVICES |
SOCRIILOWR |
SPARE |
|
DISTRIBUTION |
AIR COMPRESSOR IUN—ECUIPPED |
|
|
&NAPO 2 |
COOLING |
|
|
|
WATER PUMP A |
|
FIG. 5.50 Typical 415 V switchboard of Electric Construction Co manufacture
and starter equipment that comprise the switchboard formations are illustrated in Figs 5.52 to 5.54.
Basically, switchgear arranged in switchboards is of Form 4 to BS5486. The 'Form' of construction determines the degree of separation by barriers and partitions (within the switchgear structure) of the major components. 'Form 4' specifies the separation of bus- bars from the functional units, and separation of all functional units, including their outgoing terminals, one from the other. Essentially, the whole of the busbar system up to the point of connection to the short-circuit protective devices of each circuit must be capable of withstanding a short-circuit at any point other than in the immediate vicinity of the short-circuit. There
of course, be damage from arcing at the point of short-circuit. Also, the whole switchboard assembly must withstand any external fault. In the event of an internal arcing fault on any functional unit, the damage
must, as far as possible, be confined to that unit, so that the busbars and all other functional units remain fit for service. In addition to the basic requirements of BS5486, specialised equipment and components, e.g., circuit-breakers, contactors, fuse-switches, etc., must comply with the appropriate British Standard.
Withdrawable and removable parts (see Definitions in BS5486) of the same manufacture, type, rating and duty must be interchangeable. Withdrawable and removable parts of the same manufacture, type and rating, but of different circuit duty must be interchangeable, subject to any necessary modification to auxiliary circuits, protective devices, etc.
Handling equipment, e.g., lifting devices, is provided for withdrawable and removable parts exceeding 25 kg gross weight.
The use of hygroscopic or flammable materials is avoided as far as practicable. Terminals in which a
396

co |
FIG. 5.51 Typical 415 V swifchboarcl of Flo:fro-Mechanical l`vialinfacitiring Co mantilaotfie |
|
(see also colour photograph heiwceu pp 496 and 497) |
||
|
fusegear and controlgear switchgear,voltage Low

CUBICLE VENT |
TOP APERTURE COVER |
CONTROL FUSES
AND LINKS
|
|
|
|
|
|
|
|
|
|
|
|
|
VOLTMETER |
||
|
|
|
|
|
SWITCH |
||
|
|
Q |
|||||
|
|
|
|
|
|
||
v I |
|
|
|
|
|||
|
e — |
|
—LOCKING |
|
|||
|
|
|
HASP |
|
|||
|
|
||||||
|
|||||||
|
|
|
|
|
|
|
NEUTRAL BUSBAR
|
---- |
|
|
|
|
|
|
|
|
|
||
|
|
|
LOCAL CONTROL |
|
||||||||
|
|
|
|
|
SWITCH |
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
LOCAL REMOTE |
|||||||||
|
|
SELECTOR SWITCH |
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
P V.C.GA$BAEFLE |
|||||||||
|
|
|
|
ARC CHUTES |
||||||||
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
DOOR HANDLE |
||||||||
|
|
|
|
CLOSING MECH. |
|
|
|
|
||||
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
AIR CIRCUIT |
|||||||
|
|
|
|
|
BREAKER |
|
|
|||||
|
SHUTTER LOCKING |
|||||||||||
|
|
|
|
|
|
|
|
|
||||
|
|
270V D.C. MONITOR |
||||||||||
|
|
|
LAY — TYPE VAA11 |
|||||||||
|
|
|
|
|
|
|
|
|
||||
|
|
|
AUTO TRIP FLAG |
|||||||||
I |
|
|
|
|
INDICATION |
|
|
|||||
|
RELAY — TYPE VA F |
|
||||||||||
|
|
|
|
|
|
|||||||
il |
HEATER INDICATION |
ftva LAMP (BLUE)
- HEATER SWITCH
HEATER LINK
HEATER FUSE
TRIP SUPERVISORY
RELAY — TYPE VAX 31
SHUTTER LOCKING
LEVERS
SHUTTER
FRONT VIEW
FIG. 5.52 GEC type N.1180 415
PARALLELING
CONNECTIONS
iNTERTRIP RECEIVE — RELAY —TYPE VAJY13
RESTRICTIVE EARTH
FAULT
RELAY — TYPE CAG 14
BUCHHOLZ
RELAY—TYPE VAAll
BUSBARS
NEUTRAL LINK
NEUTRAL/EARTH
CONNECTION AND
NEUTRAL CABLE RISERS
BUSBAR CHAMBER
BARRIER
CABLE SIDE CONNECTIONS
CABLE SIDE NEUTRAL
CONNECTIONS
MASTER TRIP
RELAY —TYPE VAJY11
STANDBY EARTH FAULT
RELAY — TYPE COG 14
MAIN CABLE GLAND PLATES
(BOTTOM ENTRY)
EARTH CONNECTIONS
SIDE VIEW |
REAR VIEW |
V air cireidl-bri,iaker cubicle, used iypically :is switchboard incoming, interconticciing and bosbar-sectioning equipmeni
f
JeabloJluop pue .leaEqi!Aiss

Low voltage switchgear, controlgear and fusegear
ARC CHUTES
POSITION INDICATOR
OPERATION COUNTER
ARCING CONTACTS
MOVING CONTACTS
FIXED CONTACTS
ISOLATING
CONTACTS
SLIDE RAIL
AUXILIARY SWITCHES
REAK ER RACKING MECH
COVER PLATE
MANUAL TRIP BUTTON
LOCKING FLAP
LOCKING BOLT
MANUAL CLOSING MECH
COVER PLATE
VENTILATION GRILL |
H |
FRONT PLATE |
FIG. 5.53 DEC type M80 circuit-breaker shown withdrawn from cubicle
399

Switchgear and controlgear |
Ch |
|
|
VIEW INSIDE TOP
COMPARTMENT
D ROPP E R
COMPARTMENT
FUSE SWITCH
L--71 •
AUML;ARY SWITD•1
CONTACTOR
ANINIE7ER CT 40/1
OVERLOAD RELAY
I NTERPOSING RELAYS |
TEST SWITCH |
TRANSFORMER 415/110V |
Flu. 5.54 Typical interior of a motor control unit fitted to the type of switchboard illustrated in Fig 5.50
screw compresses a bare wire conductor directly are not permitted. Whilst, in general, no diversity factor is allowed for Duty Class 1 equipment, the provisions of BS5486: Part 1 in this respect are accepted for Duty Class 2.
As for switchgear at the other voltages, the temperature rise of terminals for external cabling must not, when carrying rated operational current continuously, exceed 50 ° C, or the limits specified in the appropriate
apparatus specification, whichever is the lower. All main conductors and incoming/outgoing terminals must be identified with their phase/polarity colours, presently in accordance with BS158. The colours at the various points of identification must be of durable material and a minimum of 300 mm 2 in area. Because in the course of time the adhesive may fail; thus allowing 'unwinding' and introducing the risk of fault, identification by taping is not accepted.
400
|
|
|
|
|
|
|
|
|
|
Low voltage switchgear, controlgear and fusegear |
||
|
|
|
|
|
|
|
|
|
|
|
||
0,2 |
|
|
closures |
|
• |
In the case of outdoor equipment, any fixings which |
||||||
|
|
|
|
of necessity pierce the Walls of the enclosure for |
||||||||
|
|
|
|
|
|
|
||||||
1 ti,..lo‘tires. unless specified or approved otherwise, are |
|
the attachment of external fittings must begas- |
||||||||||
|
ii:ctal. ventilated naturally, and provide a degree of |
|
||||||||||
|
|
ketted. Exceptions to this rule are the fixings of |
||||||||||
|
|
|
|
Oil to 13S5400 as follows: |
|
|||||||
|
|
|
|
|
labels. These may penetrate the walls of the enclo- |
|||||||
|
|
,I mpinent for |
indoor use — Code IP31. |
|
sure provided that they do not exceed 5 mm dia- |
|||||||
• |
|
|
meter and are effectively sealed. Fixings for the |
|||||||||
|
,luirineni for outdoor use — Code IP44, or of |
|
attachment of outdoor enclosures to supporting |
|||||||||
• |
|
|
||||||||||
|
|
|
|
'first' and 'second' numeral as necessary. |
|
structures must not pierce the walls of the enclosure. |
||||||
|
|
.2!Icr |
|
|||||||||
|
|
|
|
ichgear featuring withdrawable parts, the spe- |
To protect persons against electric shock, the provi- |
|||||||
, |
|
|
dciirce of protection must obtain whether the |
sions of protection by barriers or enclosures, protec- |
||||||||
|
|
|
|
|
|
the connected or disconnected posi- |
tion by insulation of live parts and protection by using |
|||||
. „„ T ment is in |
||||||||||||
|
|
|
.i nd must be independent of the fitting of closing |
protective circuits, specified in BS5486: Part 1, are |
||||||||
|
|
|
' or other sealing arrangements at the point of |
followed. |
|
|||||||
|
|
|
if external |
cabling. Unless the specified degree |
|
Particular requirements with respect to doors and |
||||||
|
rrotectiOn provi cled by the enclosure is maintained |
covers are: |
|
|||||||||
|
|
or c \ample, shutters or shrouding, temporary |
• |
Hinged doors shall open not less than 90 0 but, in so |
||||||||
|
|
|
|
are supplied for use when withdrawable or re- |
|
doing, the movement must be limited to prevent |
||||||
- |
|
,, He |
parts are removed. Such covers have captive |
|
||||||||
|
|
damage to equipment mounted on the doors, and |
||||||||||
|
|
iries and padlocking facilities. |
|
|||||||||
|
|
|
also damage, or the application of tension, to wiring |
|||||||||
|
\,.liiicionallv, all enclosures must provide: |
|
||||||||||
|
|
connecting equipment on doors to that in the static |
||||||||||
|
|
|
|
|
|
|
|
|
|
|||
• |
\,L cqu aie support of withdrawable parts during with- |
|
part of the enclosure. |
|
||||||||
|
,h |
- ,ok al, and when left in the disconnected position. |
• All indications must be clearly visible when doors |
|||||||||
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
||||
• |
po,iti‘e restraint of a withdrawable part at the limit |
|
are closed, and the equipment available for service. |
|||||||||
|
|
|
|
|
|
the means adopted must require deli- |
|
Additionally, to assist in the prevention of unau- |
||||
|
|
rite |
manual manipulation before it •is possible to |
|
thorised interference with the intended functioning |
|||||||
|
Ji ,engage the withdrawable part from the enclosure. |
|
of the equipment, provision is made for padlocking |
|||||||||
• |
\.ces to main and auxiliary contacts from the front |
|
all doors closed. |
|
||||||||
|
|
|
||||||||||
|
of |
he |
equipment. Access to fuses in control and |
• Doors and covers which give access to parts live at |
||||||||
|
Luixiliarv circuitry, relays, instruments, etc., is nor- |
|
main circuit voltage are secured by fastenings, e.g., |
|||||||||
|
talk from the front of the equipment in the case |
|
screws and nuts, the release of which necessitates |
|||||||||
|
ol L'ontactor controlgear, but usually from the rear |
|
the use of tools. Fastenings intended primarily for |
|||||||||
|
, , t) circuit-breaker |
equipment. |
|
operation by coins are not acceptable in this context. |
||||||||
• |
I or |
work in safety on the de-energised side of any |
As far as is practicable, bus wiring is segregated from |
|||||||||
|
.11,111) circuit isolating device with adjacent main |
|||||||||||
|
|
|
|
|
live. This is a most essential requirement |
all other wiring and run in ducting, conduit, etc., |
||||||
|
|
|
|
Ls rarely possible, other than during planned |
preferably metallic. Largely from considerations of |
|||||||
|
, htitLlov. n , in the |
more important switchboards to |
mechanical security, the minimum permissible cross- |
|||||||||
|
mak,: dead circuits |
other than those requiring par- |
sectional area of bus wiring is 2.5 mm 2 . |
|||||||||
|
:1L.o |
|
|
auenticm |
Iso, any main circuit parts which |
|
To facilitate efficient operation of the switchgear, |
|||||
|
|
remain fix |
lieu access has been gained to the |
the following dimensional limits above operating floor |
||||||||
|
:merior of an cii,loure, other than through doors |
level are observed wherever possible: |
||||||||||
|
|
|
, ki ■ |
cr-, secured by fastenings necessitating the |
|
|
|
|||||
|
|
|
|
|
tools, must |
be further enclosed to prevent |
Overall height |
2600 mm (max) |
||||
|
LLdeIttaI touching by persons. The aim in such cases |
Operating handles — (highest |
2000 mm (max), 450 mm (min) |
|||||||||
|
|
lo achieve a degree of protection of not less than |
||||||||||
|
I 1);() (co 13S5490), Where it is physically impossible |
|
and lowest positions reached |
|
||||||||
|
|
by an operator's hand), |
|
|||||||||
|
:0 meet this requirement in respect of the contact |
|
protective relays, instruments |
|
||||||||
|
.. Tries |
of the larger sizes of fuse-switch and fuse |
|
and mechanical indicators |
|
|||||||
|
|
|
|
|
t he openings must be as small as practicable |
Doors and panel handles/locks |
2000 mm (max), 300 mm (min) |
|||||
|
Li.,inutaciuring tolerances will allow; additionally, |
|||||||||||
|
|
|
|
|||||||||
|
|
tna ■ |
be deemed necessary to fit 'obstacles' to |
|
|
|
||||||
|
|
|
|
|
To promote a movement of air through the switchgear |
|||||||
|
|
slruct access |
by |
hands/fingers. |
||||||||
• |
f or |
a |
cce ss to main circuit fuselinks only when they |
that is sufficient to prevent condensation when it is |
||||||||
out of service, heaters of the metalclad black heat |
||||||||||||
|
|
|
|
|||||||||
|
,ire dead. |
|
|
|
|
|
pattern are provided within the enclosures.
401
Switchgear and controlgear |
Ch |
|
|
6.2.3 Cabling arrangements
Wherever practicable, external cabling is arranged to enter equipment from below. To allow some freedom of choice as to the type of cabling used in a particular circumstance, main circuit terminals must be suitable for the reception of conductors of either copper or aluminium, and arranged to minimise the bending of t he cores.
The main circuit terminals of each functional unit in a switchboard are enclosed separately in an air insulated compartment or barriered section/subsection of earthed metal or approved insulation material. Such a compartment may also accommodate current transformers for instrument and protection purposes.
Terminals for the connection of external control and auxiliary circuits are grouped and positioned relative to the main circuit with which they are associated. Whilst not necessarily so in the past, it is in most cases now policy to enclose each group separately, and thus reduce the risk of work or a fault on one group jeopardising another.
Ali terminal arrangements must, with cables connected, ensure achievement of the clearances and creepage distances shown in Tables 5.1 and 5.2.
TABLE 5.1
Indoor equipment
|
Minimum clearance |
|
Minimum creepage, mm |
|
hquipmeni |
in air between |
|
|
|
|
CTI less |
CTI 200 |
||
phases and from |
|
|||
|
|
|||
|
phase to earth, mm |
|
than 200 |
or greater |
|
|
|
|
|
Duty Class |
19 |
|
25 |
19 |
Duly Class 2 |
19 |
|
19 |
19 |
|
|
|
|
|
|
TABLE 5.2 |
|
|
|
|
Outdoor equipment |
|
||
|
|
|
|
|
Equipment |
Minimum |
|
Minimum creepage, mm |
|
|
|
|
||
Duty Clases |
clearance |
|
CTI less |
CTI 200 |
1 and 2 |
in air, mm |
|
||
|
than 200 |
or greater |
||
|
|
|
||
|
|
|
|
|
Idetv,een phases |
25 |
|
38 |
25 |
Phase to earth |
25 |
|
25 |
25 |
|
|
|
|
|
The physical disposition of main circuit cabling relative to auxiliary cabling at the point of entry into the equipment enclosure is arranged to minimise the risk of fault or fire on the former affecting the proper function of the latter. For this reason, where the design of equipment necessitates the installation of lengths of both main and auxiliary incoming/outgoing cabling within the enclosure, the former is segregated from the latter by earthed metal or other mechanically robust
fire-resistant material. Cable armour alone is not cepted as satisfying this requirement.
Terminal boxes and gland plates for single-core L. bles rated in excess of 400 A are required to be designe, specifically to minimise the production of inducet., currents.
Gland plates are supplied on the basis of one plat per cable gland, and must be detachable to facilitate drilling to suit by the cable contractor.
Insulation must be so mounted and the method of attachment of connections thereto such as to minimise the likelihood of mechanical overstressing during normal tightening of the mounting and connection fixings. Particular care is taken to ensure that expansion and contraction of components shall have no damaging effect, having especial regard to the temperatures likely to be attained under fault conditions. Additionally, the configuration of the surfaces of insulation must be designed to minimise the accumulation of airborne pollutants.
6.2.4 Electrical clearances and creepage distances
As a general rule, the electrical clearances and creepage distances shown in Tables 5.1 and 5.2 are observed as minima. However, some relaxation is permitted specifically in the following areas:
•Contactors and associated overload protective devices may have clearances and creepage distances not less than those specified in BS5424: Part 1: Appendix B.
•Circuit disconnectors (isolating devices), fuse-switches, switched and other disconnectors may have clearances not less than 12.5 mm.
The relaxed dimensions may be maintained on connections to the terminals of these components for a distance not exceeding 40 mm.
The clearances shown must be maintained irrespective of any insulation applied, unless such insulation is capable of withstanding the full power frequency high voltage test.
6.2.5 Busbar systems
The busbar circuit of a switchboard comprises the complete conductor system up to its points of connection to the circuit disconnecting/protective devices of the functional units. Typical busbar circuits are illustrated in Fig 5.55.
Main and tee-off busbars are contained in separate compartments within the switchboard. They are usually air-insulated, but may feature solid insulation at the option of the manufacturer. Where insulation is other than by air, it must be in the form of sleeving with joints encased in moulded or similar covering. Because of the possibility of deterioration with age,
402