168 • CANopen

Network Communication

5.3.4.3.22Object 0x5000, Read Input Process Image

 

Idx

 

 

S-Idx

 

 

Name

 

 

Type

 

 

Attribute

 

 

Default Value

 

 

Meaning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x5000

 

0

 

number of input byte

 

Unsigned16

 

RO

 

-

 

 

Number of relevant bytes in input PA

 

 

 

 

1

 

input segment 1

 

Octed_String

 

 

RO

 

-

 

 

1. Input PA segment (the bottom 255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

bytes of 512 bytes PA)

 

 

 

 

2

 

input segment 2

 

Octed_String

 

 

RO

 

-

 

 

2. Input PA segment (the top 255 bytes of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

512 bytes PA. Is only available, if > 255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

bytes input data)

 

Permits reading of the entire input process image as a domain via SDO, allowing access to all input data „as a block“.

Note

The access via SDO being slow, we recommend transmitting time critical data only via PDO.

5.3.4.3.23Object 0x5001, Write Output Process Image

Idx

S-Idx

Name

Type

Attribute

Default Value

Meaning

0x5001

0

number of output byte

Unsigned16

RO

none

Number of relevant bytes in output PI

 

1

input segment 1

Octed_String

RW

none

1. Output PA segment (the bottom 255

 

 

 

 

 

 

bytes of 512 bytes PA)

 

2

input segment 2

Octed_String

RW

none

2. Output PA segment (the top 255 bytes

 

 

 

 

 

 

of 512 bytes PA. Is only available, if >

 

 

 

 

 

 

255 bytes output data are possible accord-

 

 

 

 

 

 

ing to the module configuration)

Permits writing of the entire output process image as a domain via SDO „as a block“.

Note

The access via SDO being slow, we recommend transmitting time critical data only via PDO.

5.3.4.3.24Object 0x5200, Controller Configuration Object

Idx

S-Idx

Name

Type

Attribute

Default Value

Meaning

0x5200

0

max. supported Subin-

Unsigned8

RO

-

Maximally supported Subindex

 

 

dex

 

 

 

 

 

1

PDO processing

Unsigned8

RW

0

specifies the processing of the received

 

 

 

 

 

 

PDOs.

 

 

 

 

 

 

0: Logical data output, that means as

 

 

 

 

 

 

soon as a PDO arrived doubly, an

 

 

 

 

 

 

internal bus cycle starts.

 

 

 

 

 

 

1: Data of the last PDO win.

 

2

Deactivate blink display

Unsigned8

RW

0

activates/deactives the display of the

 

 

Warning Level

 

 

 

Warning Level

 

 

 

 

 

 

0: The display of Warning Level is

 

 

 

 

 

 

activated

 

 

 

 

 

 

1: The display of Warning Level is

 

 

 

 

 

 

deactivated

 

3

Deactivate global

Unsigned8

RW

0

activates/deactivates the transmission of

 

 

module diagnostics via

 

 

 

global module diagnostics via Emergency

 

 

Emergency messages

 

 

 

messages

 

 

 

 

 

 

0: dispatch diagnostic messages

 

 

 

 

 

 

1: do not dispatch diagostic messages

WAGO-I/O-SYSTEM 750

CANopen

CANopen • 169

Network Communication

5.3.4.3.25Object 0x5201, Diagnostics Configuration Object

Idx

S-Idx

Name

Type

Attribute

Default Value

Meaning

0x5200

0

max. supported Sub

Unsigned8

RO

-

Maximally supported Subindex = Num-

 

 

index = Number of

 

 

 

ber of modules

 

 

modules

 

 

 

 

 

1

Diagnostics behavior of

Unsigned8

RW

0

Each bit within the byte represents a

 

 

the 1st put module

 

 

 

channel of the module (bit 0 channel 0,

 

 

 

 

 

 

bit 1 channel 1..., bit 7 channel 7)

 

 

 

 

 

 

Bit n = 1: no diagnostics messages are

 

 

 

 

 

 

transmitted via Emergency

 

 

 

 

 

 

(n=0...7)

 

 

 

 

 

 

If all bits are set to 1 (255)

 

 

 

 

 

 

the transmission of the diagnostics mes-

 

 

 

 

 

 

sages via Emergency is deactivated for

 

 

 

 

 

 

this module, independently of the channel

 

 

 

 

 

 

number of the module.

 

….

 

 

 

 

....

 

64

Diagnostics behavior of

Unsigned8

RW

0

Each bit within the byte represents a

 

 

the 64th put module

 

 

 

channel of the module (bit 0 channel 0,

 

 

 

 

 

 

bit 1 channel 1..., bit 7 channel 7)

 

 

 

 

 

 

Bit n = 1: no diagnostics messages are

 

 

 

 

 

 

transmitted via Emergency

 

 

 

 

 

 

(n=0...7)

 

 

 

 

 

 

If all bits are set to 1 (255)

 

 

 

 

 

 

the transmission of the diagnostics mes-

 

 

 

 

 

 

sages via Emergency is deactivated for

 

 

 

 

 

 

this module, independently of the channel

 

 

 

 

 

 

number of the module.

WAGO-I/O-SYSTEM 750

CANopen

Соседние файлы в папке 750-837