Fieldbus Controller 750-837, /02x-000, 750-838, /02x-000

• 73

Process Image

 

 

 

These modules present themselves with 1x 12...48 bytes, so that the object 0x4200-0x4202 for Gateway Modules, Inputs and the object 0x4300-0x4302 for Gateway Modules, Outputs are used. Therefore for each module one Subindex is occupied, within the Subindex 1 containes the mailbox size, Subindex 2 the mailbox and Subindex 3 to 48 the process data.

3.1.4.2.6 System Modules

System Modules with Diagnostics

750-610, -611

The 750-610 and 750-611 Supply Modules provide 2 bits of diagnostics in the Input Process Image for monitoring of the internal power supply.

Input Process Image

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

 

 

 

 

 

 

Diagnostic bit S 2

Diagnostic bit S 1

 

 

 

 

 

 

Fuse

Voltage

For the digital inputs the object 0x6000 (also 0x2000 possible) is used.