      1. Requirements for coupling filter (wl-110 kV)

Description

Information:

Note

Required Customer

Guaranteed Contractor

1.

Type

2.

Manufacturer

3.

Standards

4.

Technical requirements for connection filters

4.1

Number modification

1 - 4

4.2

Capacity accession pF

2200 - 6400

4.3

Line voltage kV

110 кВ

4.4

The nominal resistance of the overhead line, Ohm

450

4.5

The range of the input filter resistance, Ohm

560 - 587

4.6

Range bandwidth kHz

36 - 1000

      1. Requirements for coupling filter (wl-330 kV)

Description

Information:

Note

Required Customer

Guaranteed Contractor

1.

Тype

2.

Manufacturer

3.

Standards

4.

Technical requirements for connection filters

4.1

Number modification

8 - 9

4.2

Capacity accession pF

7000

4.3

Line voltage kV

330

4.4

The nominal resistance of the overhead line, Ohm

330

4.5

The input impedance of the filter, Ohm

439

4.6

Range bandwidth kHz

36 - 1000

      1. Requirements for Radio-frequency cables

Description

Information:

Note

Required Customer

Guaranteed Contractor

1.

Type

Аnalog RC-75-7,2-a65PT

2.

Manufacturer

3.

Standards

4.

Technical description

4.1

Cross section, not less, mm

1.0

4.2

The insulation of the inner conductor

Broken

4.3

Material Outer braid

copper

4.4

Impedance, no more, Ohm

75

4.5

The attenuation in the cable, no more:

  • dB / km at frequencies up to 1.0 MHz

  • dB / km at a frequency of 10 MHz

3

0.011

4.6

Dielectric strength, kV (at 50 Hz for 1 min.)

6.0