- •16.1 General requirements 22
- •21.1 General requirements 26
- •22. Requirements to Organization of Construction Works 32
- •22.1 General requirements 32
- •23. Requirements to works 38
- •29. Requirements for the switchgear arrangement 330 kV and 110 kV 60
- •35.1 Special requirements 79
- •36. Assortment and quantity 96
- •37 Information about a nomenclature and amount of the required equipment, materials, wares 97
- •38 Tables of technical information 98
- •III. Special technical requirements to relay protection and automation system 116
- •39 General 116
- •39.4 Training 118
- •40 General Functional Requirements to Elements of Relay Protection and Special Automatics System 123
- •41 Nomenclature and amount supplied with the equipment of the systems electric defense and automation of substation 330 kV «Zhovtneva» 143
- •42 Tables of technical information for the system of relay protection and automation 145
- •43. General 204
- •43.1 Scope of Works 204
- •44. Purpose and Objectives of acs tp ss 206
- •45. Functions Performed by the acs tp ss 207
- •46. Description of the Automation Object 212
- •47. Implementation of acs tp basic functions 213
- •48. Organization of acs tp ss 220
- •48.3.1 General requirements 221
- •48.5.1 General Requirements 230
- •49. Requirement to the Types of Support 235
- •55. Technical data table for acsee 269
- •Section I. General technical requirements
- •General requirements
- •Feasibility study
- •Scope of works
- •Improvement and land scaping territory:
- •System of units The entire technical documentation shall use the International System of Units (si), in accordance withthe provisions of theIso/iec 80000.
- •Guaranteed values
- •Special requirements
- •Coordination of activities
- •Regulations, Standards and Rules
- •Unification and interchangeability
- •Materials and quality
- •Quality assurance system
- •Main principles
- •Notification on defects
- •Standard tools
- •Special accessories, instruments and tools
- •Spare parts
- •Basic requirements
- •Mandatory spare parts
- •Recommended spare parts
- •Packing, shipping, transportation and load-lifting mechanisms
- •Packing
- •Shipping and transportation
- •Load-lifting operations
- •Labels and Nameplates
- •Signs essential in case of emergency
- •Mandatory signs
- •Factory tests and factory test reports
- •Inspections and site tests
- •Test reports and test programs
- •Factory test reports
- •Test programs
- •Warranty
- •Training
- •Documentation
- •General requirements
- •Design coordination procedure
- •Responsibility for errors in data and drawings
- •Design alteration procedures
- •Works implementation program and schedule
- •Project for Organization of Construction
- •Reports on works performed
- •Progress meetings reports
- •Installation and commissioning instructions
- •Operating and maintenance manual
- •Requirements to Organization of Construction Works
- •General requirements
- •Permits and licenses for works implementation
- •Temporary sites
- •Supply of construction site
- •Maintenance and cleaning of construction site
- •Organization and quality assurance of civil and erection works
- •Safety and labour protection requirements
- •Fire safety
- •Environmental protection. Environment protection and socialmanagement plan.
- •Requirements to works
- •Land measuring
- •Earthworks
- •Concrete Works
- •Foundations
- •Covered-up works and covered-up works reports
- •Erection works
- •Electrical installation works
- •Start-up and commissioning
- •Insulation and corrosion-protection works
- •Painting
- •Roofing and waterproofing
- •Operational acceptance of the completed facility
- •Section II. Specific technical requirements primery equipment
- •General information on the project
- •System 110 kV
- •The scope of works and services
- •General Provisions
- •The scope of work for the substation
- •Buildings primary purpose
- •The design solutions for buildings main destination
- •Requirements for the switchgear arrangement 330 kV and 110 kV
- •Basic design-layout solutions
- •Monitoring subsystem gis 330/110
- •Purpose and functions
- •Auxiliaries substation
- •Shields own needs
- •Power supply consumers during construction
- •Monitoring of existing at
- •31 Requirements to works, services, materials, structures and main electrical equipment
- •Overvoltage protection , external insulation, grounding system, lighting system , beacons mounted on top of high structures, biological protection
- •Lightning protection system
- •External insulation
- •Requirements grounding system implementation
- •Handing over in exploitation of the earth system
- •Lighting system
- •Biological protection
- •Requirements to works and structural materials
- •Concrete and reinforced-concrete structures
- •Metallic structures
- •Corrosion protection
- •Painting
- •Deviation tolerances of building structures
- •Shipment and transportation
- •Load-lifting mechanisms and accessories
- •Warranty
- •General layout and transportation system ; Access roads at the site
- •Inspection and tests
- •Factory tests and factory test reports
- •Site tests
- •Fire safety
- •Requirements to materials, equipment, structures, systems, conductors and cables
- •Special requirements
- •Insulating gas
- •Isolating switch
- •Inputs are «insulating gas-air»
- •Terminators of overstrain
- •Shield of own needs 0,4 kV
- •Shield of direct-current 220 V
- •Cables and cable trays
- •Power cables
- •Control cables
- •Requirements to the equipment hf treatments for organization hf ducting’s on wl (hf minelayer, condensers of connection)
- •Technical data sheets for primary equipment and infrastructure
- •Assortment and quantity Technical Data Schedules Description
- •37 Information about a nomenclature and amount of the required equipment, materials, wares
- •Information about a nomenclature and amount of the required high-voltage equipment and equipment of own needs.
- •Information about a nomenclature and amount of the required materials (wires, cables and terminal closets)
- •Information about a nomenclature and amount of the required devices of instruments and adaptations
- •Tables of technical information
- •Expls to the tables
- •Technical requirements to gis - 330 kV
- •Technical requirements to gis – 110 kV
- •Technical requirements to the terminator of overstrain 330 kV
- •Technical requirements to the terminator of overstrain 110 kV
- •Technical requirements to the shield of own needs 0,4 kV
- •В Technical requirements to the shield of direct-current 220 V
- •Technical information of high-frequency minelayer for wl 330 kV
- •Technical information of condensers of connection for wl 330 kV
- •Technical information of high-frequency minelayer for wl 110 kV
- •Technical information of condensers of connection for wl 110 kV
- •III. Special technical requirements to relay protection and automation system
- •General
- •Scope of Work Overview
- •Contractor`s Duties
- •Dismantling
- •Training
- •Operational Conditions
- •General Design Requirements
- •Requirements to Microprocessor Devices Regarding External Interface
- •Software Requirements
- •Requirements to Control Cables
- •Spare Parts and Special Tools
- •Warranty Maintenance
- •Requirements to Methodology Buidelines Regarding Selection of Setting for Relay Protection and Special Automatics
- •General Functional Requirements to Elements of Relay Protection and Special Automatics System
- •Devices of Protection of Automatic Transformers 330 kV for at with Phase Shifting Transformer
- •High-frequency transceivers for basic differential-phase defense of line on a microelectronic element base
- •Complete set of automation of management a switch 330 kV with the functions of dbrs, ari
- •Complete set by a basic differential-phase hf defense of wl-110 kV with the functions of reserve defense
- •Complete set of basic differential defense of wl-110 kV (transmission of signal on fibre-optic communication line) with the functions of reserve defense
- •Complete set of defense wl-110 kV (on the controlled from distance and current principle) with funk-ciey dbrs,ari
- •Complete set of defense cs(connecting switch) -110 kV, bcs(bus connecting switch )-110 kV on current principle with the function dbrs
- •Complete set of automation of management a switch 110 kV with the functions dbrs, ari, fld (fixing of line disconnecting)
- •Dbrs function
- •Functions of ari device
- •Device of fixing disconnecting and including line (fld and fli))
- •Automation device of liquidation asynchronous mode (adla)
- •Complete set for the transmission commands rp (relay protection) and sa (special automatic )
- •Requirements to the dividing filters for organization hf ductings
- •Requirement to the joining filter for organization hf channels
- •Requirements to the radio-frequency cable for joining hf apparatus to the hf highway
- •Requirement to the devices of determining damage location (ddl) by a wave method
- •Complete set for the transmission of command rp and sa on fcl
- •Complete set of defense autotransformers 330 kV on differential, controlled from distance and current principle (basic and dublicate)
- •Complete set of defense transformers 110 kV on differential, controlled from distance and current principle
- •Complete set of differential defense of tires 330 kV and 110 kV
- •Complete set of differential defense bus arrangement 330 kV and 110 kV
- •Complete set for adjusting and verification equipment of relay protection and special automatic
- •Verification of devices rp and sa
- •Nomenclature and amount supplied with the equipment of the systems electric defense and automation of substation 330 kV «Zhovtneva»
- •Tables of technical information for the system of relay protection and automation
- •Generals
- •Terminology
- •Technical information of complete set of basic differential-phase defence wl-330 kV
- •Technical data post high-frequency protection (for overhead lines of 330 kV and 110 kV)
- •Technical data sets main differential protection of 330 kV overhead (with signal transmission on fiber optic)
- •Technical data set up protection of 330 kV overhead (on the remote and current principle)
- •Technical data sets automatic control switch with 330 kV circuit breaker failure protection, ar
- •Technical data sets basic differential-phase protections of 110 kV
- •Technical data sets main differential protection of wl-110 kV
- •Technical data set up protection of 110 kV (on the remote and the current principle)
- •Technical Data Security Kit cs-110 kV, bcs- 110 kV bus coupler on the current printsipes the breaker failure protection
- •Technical data sets automatic control switch with 110 kV circuit breaker failure protection, ar, fld
- •Technical data sets of differential busbar protection / busbar 330 kV
- •Technical data sets of differential busbar protection / busbar 110 kV
- •Technical Data Security Kit autotransformers 330/110 kV differential, distance and current principle (main and backup set)
- •Technical Data Security Kit transformers 110/35 kV differential, distance and current principle
- •Technical data protection management set rpn transformers
- •Technical data kit
- •Technical Data Automation Kit elimination of asynchronous operation
- •Technical data set command rp and sa - Tx, Rx
- •Technical data sets and data relay protection and emergency teams on fcl
- •Requirements Crossover
- •Requirements for coupling filter (wl-110 kV)
- •Requirements for coupling filter (wl-330 kV)
- •Requirements for Radio-frequency cables
- •Technical data sets to test relay protection
- •Technical data test set to test hf devices
- •Technical Data laptop
- •Special IV. Special technical requirements to automated control system for technological process
- •General
- •Scope of Works
- •Project Structure
- •Contractor`s duties
- •Purpose and Objectives of acs tp ss
- •Purpose of acs tp of the Substation
- •Objectives of the acs tp of the Substation
- •Equipment operating modes monitorin
- •Automated substation equipment control
- •Warning and alarm system organization
- •Warning system
- •Alarm system:
- •Registration of emergencies
- •Prоviding current and archived data for operating personnel and other users
- •Data exchange with other levels of control hierarchy
- •System-wide functions
- •Description of the Automation Object
- •Implementation of acs tp basic functions
- •General requirement
- •Monitoring of the Substation Current Mode and the Key Diagram Status
- •Equipment Status Monitoring
- •Process parameters monitoring
- •Control Process Automation
- •Automated Management Services
- •Control of the Substation Components
- •Control of 330 – 110 kV Switching Units
- •Control of 35 – 10 kV Switching Units
- •Software and hardware of acs tp
- •General requirements
- •Requirements to the substation level devices
- •Requirements to the connection and process level devices
- •Intelligent Electronic Devices (ied)
- •Requirements to lan
- •Requirements to electromagnetic compatibility of shs acs tp
- •Requirement to reliability of the acs tp software/hardware
- •Requirement to Safety
- •Ensuring of equipment operating conditions
- •Requirement to control and optical cables
- •Testing and self-diagnostics of the shs components
- •Requirements for the maintenance and repair
- •Arrangement of power supply
- •Requirement for Embodiment of Control Cabinet
- •Data exchanges with higher levels of dispatcher control
- •Interaction with adjacent subsystems
- •General Requirements
- •Interaction with aspfm
- •Interaction with relay protection an emergency controls
- •Interaction with substation main equipment monitoring subsystem
- •Interaction with the security video surveillance subsystem
- •Requirement to cyber security
- •Requirements to ergonomics and industrial design
- •Requirement to patent clearance
- •Requirements to standardisation and unification
- •Requirement to the Types of Support
- •Requirements to mathematical support
- •Requirements to information support
- •Requirement to linguistic support
- •Requirements to software
- •Requirements to measurement assurance/metrological support
- •Requirements to spare parts and accessories
- •Requirement to Documentation
- •Technical documentation
- •Project documentation
- •Operational documentation
- •Requirement for acceptance tests
- •General
- •Guarantees
- •Technical data table for the acs tp
- •General
- •Functional requirement Table 1.1: Technical requirements to acs tp hardware and software
- •Section V. Special specifications for automated metering system
- •Setting and purpose of creation the system
- •Purpose acsee ss
- •The purpose of the acsee ss
- •Description of object of automation
- •System requirements
- •General system requirements
- •Requirements for the structure and functioning of the system
- •Reliability requirements
- •Requirements for Safety
- •Requirements to ergonomics and technical aesthetics
- •Requirements for the operation, maintenance, repair and preservation of the system components
- •Requirements for the protection of information from unauthorized access
- •Requirements for the preservation of information in case of emergencies
- •Requirements for protection from the influence of external factors
- •Requirements for the standardization and unification
- •Power Requirements
- •Feature Requirements acsee ss
- •Functions and settings tasks acsee ss
- •Requirements for the type of collateral
- •Requirements of a software
- •Requirements for data provision
- •Requirements for linguistic support
- •Software Requirements
- •Hardware requirements
- •Requirements for the counters of electric power
- •The requirements for communication cabinet acsee ss
- •The requirements for awp
- •The requirements for communication channels
- •Requirements for metrological support
- •Requirements for Organizational Support
- •Requirements to acsse
- •Regulations
- •Technical data table for acsee
- •The range and number
- •Table 2.1: Information regarding the number and amount of equipment required for electricity metering points ss
- •Table 2.2: Data on the nomenclature and the amount of the required hardware and software acsee
- •Table 2.3: Composition Software
- •Technical data table
- •Table 5.1 Technical requirements for electronic multifunction electricity meter
Table of these technical devices, equipment, systems, subject delivery on substation 330 kV «Zhovtneva» in accordance with a nomenclature and amount of supplied with an equipment (see is the special technical requirements)
Technical information of complete set of basic differential-phase defence wl-330 kV
№ |
Description |
Information: |
Note |
||
Required Customer |
Guaranteed Contractor |
||||
Complete set of basic differential-phase defense line 330 kV with the transmission of signals on HF channel |
|||||
1. |
Type |
|
|
|
|
2. |
Customer |
|
|
|
|
3. |
Standards |
IEC 61850 |
|
|
|
4. |
Technical descriptions: |
||||
4.1 |
Amount of groups setpoints, no less |
4 |
|
|
|
4.2 |
Amount of alarm light-emitting diodes, things, no less |
12 |
|
|
|
5. |
Chains of alternating current of terminals: |
||||
5.1 |
Nominal measuring current, A |
1.0 or 5.0 |
|
|
|
5.2 |
Amount of alarm light-emitting diodes, things, no less |
6 |
|
|
|
5.3 |
Current of thermal firmness (long) |
3 х Iн |
|
|
|
5.4 |
Current of the onesecond firmness |
100 х Iн |
|
|
|
5.5 |
Consumption on a phase at Iн, ВА |
No less 0,25 |
|
|
|
6. |
Chains of variable tension terminals: |
||||
6.1 |
Nominal second tension, В |
Un = 100 |
|
|
|
6.2 |
Amount of entrances chains of variable tension (100 V) no less, things.: |
6 |
|
|
|
6.3 |
Variable tension of thermal stability (long) |
1,5 x Uн |
|
|
|
6.4 |
Variable tension of the onesecond stability |
2,5 x Uн |
|
|
|
6.5 |
Control of good condition chains of tension |
yes |
|
|
|
7. |
Working frequency of chains of alternating current and tension of terminals |
||||
7.1 |
Nominal frequency, Hertzs |
fn= 50 |
|
|
|
7.2 |
Working range of frequencies |
50 ± 5% |
|
|
|
8. |
Operative direct current |
||||
8.1 |
Nominal tension of operative direct-current, V |
Un = 220 |
|
|
|
8.2 |
Working range of tension operative direct-current |
(0,8 – 1,1) x Un |
|
|
|
8.3 |
Pulsations are in tension of direct-current |
No more than 6% from a mean value |
|
|
|
8.4 |
The normal functioning of terminals must not be violated at disappearance or decline of U of the below put limit for a time, sec |
0,04 |
|
|
|
8.5 |
There must not be false wearing-outs or violations of the normal functioning of terminals at a removal or serve of U feed |
Yes |
|
|
|
8.6 |
The serve tension of feed reverse polarity must not cause the damage of terminal |
yes |
|
|
|
9. |
Binary entrances of terminals |
||||
9.1 |
Permanent nominal tension of every entrance, V |
Uent. n = 220 |
|
|
|
9.2 |
Working range of every entrance |
(0,8 – 1,1)xUent.n |
|
|
|
9.3 |
Tension of the "unassured wearing-out" of every entrance, V |
(0.65 – 0.8)xUent.n |
|
|
|
9.4 |
Discrete entrances must provide: |
||||
9.4.1 |
unwearing-out at appearance contactors on any of poles; |
Yes |
|
|
|
9.4.2 |
unwearing-out during work devices of auto search "ground" at determinations of shorting on any of poles |
yes |
|
|
|
9.5 |
Rate of return |
К ≥ 0,95 |
|
|
|
9.6 |
Freely programmable binary entrances |
Yes |
|
|
|
10. |
Contact outputs of terminals |
||||
10.1 |
Connected tension of direct-current, V |
220 |
|
|
|
10.2 |
Eliminate galvanic connection with elements, located into a terminal |
yes |
|
|
|
10.3 |
Including ability at the inductive loading with L/r>10 msec |
10 А, for a time, sec |
1.0 |
|
|
30 А, for a time, sec |
0.2 |
|
|
||
10.4 |
Protracted flowing of current, А |
5 |
|
|
|
10.5 |
Disconnecting ability of current 1/0,4/0,2 A at tension 48/110/220 V and permanent time of chain of L/r ≤ 40 msec |
Yes |
|
|
|
10.6 |
Freely programmable output relays |
yes |
|
|
|
11. |
Differential-phase defense |
||||
11.1 |
Corner of displacement of the mixed signal: |
0 to 360° |
|
|
|
11.2 |
Setting of asymmetry signal, msec |
–5.0 to 5.0 |
|
|
|
11.3 |
Setting of delay channel, msec |
0.00 to 30.00 |
|
|
|
11.4 |
Timer of 2nd coincidence, msec |
10 to 200 |
|
|
|
11.5 |
Extended corner of blocking, hail.deg |
40 to 180° |
|
|
|
11.6 |
Setpoint on a rate to the combined filter of currents must be regulated scope |
6…10 |
|
|
|
11.7 |
Setpoint of organ comparison of phases on a corner at which operating of defense is blocked on disconnecting must be regulated scope, |
from ± 40° to ± 70° |
|
|
|
11.8 |
An error must not exceed (without the account of phase changes in HF channel) on the corner of blocking, deg° |
± 5° |
|
|
|
11.9 |
Exactness of wearing-out starting organ the relay of current of a zero sequence, % |
± 5 |
|
|
|
11.10 |
Exactness of wearing-out of starting organ the relay tension of reverse sequence, % |
± 5 |
|
|
|
12. |
Controlled from distance defense (21) |
||||
12.1 |
Amount of areas |
4 |
|
|
|
12.2 |
Characteristics |
quadrangular |
|
|
|
12.3 |
Setting resistance, Ohm |
0.05 to 500.00 |
|
|
|
12.4 |
Error setting resistance |
±5% |
|
|
|
12.5 |
Remote characteristic angle |
30 to 90° with a step 1 |
|
|
|
|
Control orientation: |
||||
12.6 |
Characteristic angle |
30 до 90°with a step 1 |
|
|
|
12.7 |
The maximum angle |
30 до 90°with a step 1 |
|
|
|
12.8 |
Exposure time with |
0.000 to 10.000 |
|
|
|
13. |
Ground distance protection (21N) |
||||
13.1 |
Amount of areas |
4 |
|
|
|
13.2 |
Characteristics |
quadrangular |
|
|
|
13.3 |
Setting resistance, Ohm |
0.02 до 500.00 |
|
|
|
13.4 |
Remote characteristic angle |
30 до 90°with a step 1 |
|
|
|
|
Control orientation: |
||||
13.5 |
Characteristic angle |
30 до 90°with a step 1 |
|
|
|
13.6 |
The maximum angle |
30 до 90°with a step 1 |
|
|
|
|
Compensation for residual: |
||||
13.7 |
Amplitude Z0/Z1 |
0.00 to 10.00 |
|
|
|
13.8 |
Angle Z0/Z1 |
–90 tо 90°in step of 1 |
|
|
|
|
Compensation of mutual zero sequence: |
||||
13.9 |
Amplitude Z0M / Z1 |
0.00 tо 7.00 |
|
|
|
12.10 |
Angle Z0M / Z1 |
–90 до 90°in step of 1 |
|
|
|
13.11 |
Exposure time, sec |
0.000 to 10.000 |
|
|
|
14. |
Load Encroachment |
||||
14.1 |
Positive sequence voltage (Umin) |
0 – 0.7 r.u |
|
|
|
14.2 |
Resistance to direct sequence, Ohm |
0.1 – 250.00 |
|
|
|
14.3 |
Angle impedance load zone |
(15– 65)0 |
|
|
|
15. |
Power swing detection |
||||
15.1 |
Full coverage of internal resistance characteristics "line";, Ohm |
0.10 - 500.00 |
|
|
|
15.2 |
Full coverage of internal resistance characteristics "to tires; Ohm |
0.10 - 500.00 |
|
|
|
15.3 |
External blocking characteristic wobble, degrees |
(20 – 90)° |
|
|
|
15.3 |
Timers ,sec |
0.00-10.00 |
|
|
|
16. |
Function breaker failure protection (DBRS) |
||||
16.1 |
Select the type of breaker failure: 3-phase / 1-phase |
Yes |
|
|
|
16.2 |
Using the current supervision |
Yes |
|
|
|
16.3 |
Receive triggers protection switching and catch on the lifetime of the current in the breaker failure protection |
Yes |
|
|
|
16.4 |
Phase current operation |
0.02 – 3.0 r.u |
|
|
|
16.5 |
The current operation of the residual |
0.001 – 0.8 r.u |
|
|
|
16.6 |
Repeat the action on the circuit breaker without delay (action "over") |
Yes |
|
|
|
16.7 |
Return breaker failure timers if successful disconnecting switch |
yes |
|
|
|
16.8 |
Timers ,sec |
0.000 – 10.000 |
|
|
|
17. |
Automatic reclosing (AR) for a three-quarter circuits (1,5-breaker) |
||||
17.1 |
Number of reclosing attempts |
1, 2, 3, 4 |
|
|
|
17.2 |
Program restart |
3ph; 1/2/3ph |
|
|
|
17.3 |
Functions TAR,OAR,FAR with the choice of trip |
yes |
|
|
|
17.4 |
Possibility of the prolonged dead time reclosing in case of loss of HF link line protection to enable signal |
Yes |
|
|
|
17.5 |
Control of the circuit breaker to reclose cycle: "off-on-off" |
Yes |
|
|
|
17.6 |
AR synchronism with the control and the presence of voltage |
Yes |
|
|
|
18. |
Synchrocheck and energizing circuit for a three-quarter (1.5-breaker) |
||||
18.1 |
Selecting phase voltage reference tires |
Yes |
|
|
|
18.2 |
Selecting phase reference voltage on the line |
Yes |
|
|
|
18.3 |
Selection of the circuit breaker and the circuit line |
Yes |
|
|
|
18.4 |
The maximum voltage difference, V |
1 tо 120 |
|
|
|
18.5 |
Maximum angle difference, deg. |
0 tо 90° |
|
|
|
18.6 |
The maximum difference in frequency, Hz |
0.005 tо 2.00 Гц |
|
|
|
18.7 |
Function setting under stress |
Yes |
|
|
|
19. |
Phase / residual / neutral |
||||
19.1 |
Start value |
0.08 tо 30.00 r.u. |
|
|
|
19.2 |
Setting the return from the start value,% |
≥ 95 % |
|
|
|
19.3 |
Modifier time, sec |
0.00 to 100.00 |
|
|
|
20. |
Current cutoff phase / residual / neutral |
||||
20.1 |
Start value |
0.08 to 30.00 r.u |
|
|
|
20.2 |
Setting the return from the start value,% |
≥ 95 % |
|
|
|
20.3 |
Shutter response time, sec |
0.00 to 100.00 |
|
|
|
21. |
Current cutoff reverse order |
||||
21.1 |
setting run |
0.08 to 30.00 r.u |
|
|
|
21.2 |
Setting the return from the start value,% |
≥ 95 % |
|
|
|
21.3 |
Shutter response time, sec |
0.00 to 100.00 |
|
|
|
21.4 |
Reaction time |
<20 msec at 3th multiple increase of starting |
|
|
|
22. |
Tripping logic |
||||
22.1 |
Action trip |
Three-phase, 1/2/3-phase |
|
|
|
22.2 |
Logic teleuskoreniya |
yes |
|
|
|
22.3 |
Pulse width off (timers), sec |
0.00 – 50.00 |
|
|
|
23. |
Measurement |
||||
23.1 |
Frequency |
Yes |
|
|
|
23.2 |
Voltage |
Yes |
|
|
|
23.3 |
Current |
Yes |
|
|
|
23.4 |
Phase angle |
Yes |
|
|
|
23.5 |
Active power, P |
Yes |
|
|
|
23.6 |
Reactive power, Q |
Yes |
|
|
|
23.7 |
Full power, S |
Yes |
|
|
|
23.8 |
The power factor, cos (φ) |
Yes |
|
|
|
24. |
Event recorder |
||||
24.1 |
Capacity events |
500 |
|
|
|
24.2 |
The maximum count rate, pulse / s |
10 |
|
|
|
24.3 |
Start on any change in the state |
Yes |
|
|
|
24.4 |
Storage of data in nonvolatile memory |
Yes |
|
|
|
25. |
Disturbance recorder |
||||
25.1 |
The number of recordable analog channels |
12 |
|
|
|
25.2 |
Mode of operation: continuous or launch |
Yes |
|
|
|
25.3 |
Time resolution , msec |
1 |
|
|
|
25.4 |
Operating parameters: the current value of any analog |
Yes |
|
|
|
26. |
Fault location on line (FLL) |
|
|||
26.1 |
Method for determination |
one-sided |
|
|
|
27. |
Оscillographic testing |
||||
27.1 |
The number of entries, at least: |
10 |
|
|
|
27.2 |
Starts: |
||||
27.3 |
start-up, dropout, or operate any item; |
Yes |
|
|
|
27.4 |
digital input change of state; |
Yes |
|
|
|
27.5 |
change of state contact output; |
Yes |
|
|
|
27.6 |
Storage of data in nonvolatile memory |
Yes |
|
|
|
|
|
|
|
|
|