    1. Complete set of defense autotransformers 330 kV on differential, controlled from distance and current principle (basic and dublicate)

The complete set of defense can consist of one or a few microprocessor devices and must realize next functions:

  • differential defense (three/two) of puttee AT;

  • controlled from distance defense with four independent areas and rebuilding from loading;

  • protecting from a thermal overload;

  • differential current defense of a zero sequence;

  • maximal current defense (on complete currents and currents of a zero sequence);

  • current pinch-off (on complete currents and currents of a zero sequence);

  • automatic control tension of transformer;

  • control of the second chains of tension;

  • control of the second current chains;

  • amount groups of setpoints – not less than 4th;

  • synchronization of time-signals;

  • free-programmable logic;

  • internal recorder of events;

  • oscillographic testing;

  • energyindependent memory;

  • measurings: currents, tensions, frequency, power;

  • self-diagnostic of device;

  • liquid-crystal screen on a front panel;

  • user-programmable light-emitting-diode indicators for signaling;

  • signaling about the state and functioning of device;

  • support of protocol of MEK 61850, and presence of standard international protocols of exchange by information for integration in ACS;

  • front port of Ethernet (Rs232) for connection with a device;

  • back port with an optical fibre ethernet-interface for connection with ACS substations;

    1. Complete set of defense transformers 110 kV on differential, controlled from distance and current principle

The complete set of defense can consist of one or a few microprocessor devices and must realize next functions:

  • differential defense of transformer;

  • controlled from distance defense with independent areas and rebuilding from loading;

  • protecting from a thermal overload;

  • differential current defense of a zero sequence;

  • maximal current defense (on complete currents and currents of a zero sequence);

  • current pinch-off (on complete currents and currents of a zero sequence);

  • automatic control tension of transformer;

  • control of the second chains of tension;

  • control of the second current chains;

  • amount groups of setpoints – not less than 4th;

  • synchronization of time-signals;;

  • free-programmable logic;

  • internal recorder of events;

  • oscillographic testing;

  • energyindependent memory;

  • measurings: currents, tensions, frequency, power;

  • self-diagnostic of device;

  • liquid-crystal screen on a front panel;

  • user-programmable light-emitting-diode indicators for signaling;

  • signaling about the state and functioning of device;

  • support of protocol of MEK 61850, and presence of standard international protocols of exchange by information for integration in ACS;

  • front port of Ethernet (Rs232) for connection with a device;

  • back port with an optical fibre ethernet-interface for connection with ACS substations;

    1. Complete set of differential defense of tires 330 kV and 110 kV

Functional requirements:

  • differential current protection with braking;

  • three-phase created with two-zone differential protection;

  • choice of the protection zone based on the position of the auxiliary contacts high-voltage apparatus;

  • sensitive organ differential protection;

  • control algorithm protection zones;

  • two options to monitor the situation isolator / switch;

  • fixing algorithm incorporating the measured current connection to the zone A (B);

  • merger of the two areas into one in the "fixing broken" connection or, if necessary, (regardless of the position of disconnectors);

  • selective disconnection of the differential busbar protection switches related area;

  • functional testing circuits TT incoming connections;

  • Blocking protection with fault circuits;

  • Reserve non-directional overcurrent protection;

  • Three-phase and phase-segregated breaker failure start, the control current position of the auxiliary contacts switch or adaptive combination of the two signs;

  • free-programmable logic;

  • amount groups of setpoints – not less than 4th;

  • signaling about the state and functioning of device;

  • self-diagnostic of device;

  • internal recorder of events;

  • oscillographic testing;

  • energyindependent memory;

  • liquid-crystal screen on a front panel;

  • displayed on the screen information about the status of switching devices connection;

  • user-programmable light-emitting-diode indicators for signaling;

  • support of protocol of MEK 61850, and presence of standard international protocols of exchange by information for integration in ACS;

  • front port of Ethernet (Rs232) for connection with a device;

  • back port with an optical fibre ethernet-interface for connection with ACS substations;