    1. Complete set of defense cs(connecting switch) -110 kV, bcs(bus connecting switch )-110 kV on current principle with the function dbrs

The complete set of defense can consist of one or a few microprocessor devices and must realize next functions:

  • four the step current directed protecting of a zero sequence from contactors;

  • maximal current defense (MCD);

  • fast-acting MCD (current pinch-off);

  • defense at including on a damage;

  • action on the three-phase disconnecting;

  • freely programmable logic;

  • presence of three-phase DBRS;

  • internal recorder of events;

  • oscillographic testing;

  • energyindependent memory;

  • measurings of current parameters;

  • self-diagnostic of device;

  • signaling about the state and functioning of device;

  • groups of setpoints: no less 4th;

  • synchronization from the outsourcing of exact time;

  • support protocol of IEC 61850, and similarly presence of standard international protocols of exchange by information for integration in ACS;

Requirements to software part:

  • liquid-crystal screen on a front panel;

  • user-programmable light-emitting-diode indicators for signaling;

  • front port of Ethernet (Rs232) for connection with a device;

  • two back port`s with an optical fibre ethernet-interface for connection with ACS substations;

    1. Complete set of automation of management a switch 110 kV with the functions dbrs, ari, fld (fixing of line disconnecting)

The complete set of management automation can consist of one or a few microprocessor devices and must realize next functions:

  • Control of switching device (on - off);

  • realization of the three-phase disconnecting of switch with starting DBRS;

  • fixing of line disconnection (a function is FLD and FLI);

  • control of good condition of current chains;

  • control of good condition chains of tension (circuit-disconnection fault);

  • freely programmable logic;

  • free configuration of entrances/outputs of device;

  • determination and reflection of current parameters of object;

  • synchronization from the outsourcing of exact time;

  • amount of groups of setpoints - no less 4th;

  • operative blocking for a chart with one switch on joining;

  • autoreclosing;

  • internal recorder of events;

  • oscillographic testing;

  • energyindependent memory;

  • measurings of current parameters;

  • self-diagnostic of device;

  • signaling about the state and functioning of device;

  • support of protocol of IEC 61850, and also presence of standard international protocols of exchange by information for integration in ACS;

Requirements to software part:

  • liquid-crystal screen on a front panel;

  • user-programmable light-emitting-diode indicators for signaling;

  • front port of Ethernet (Rs232) for connection with a device;

  • two back port`s with an optical fibre ethernet-interface for connection with ACS substations;

    1. Dbrs function

  • reception to on phase or three-phase signals about the wearing-out of outside / inside defense in a time of existence of current in DBRS;

  • repeated operating on disconnecting of switch (for a phase / three-phase) without a temporal hitch ("DBRS on itself");

  • at starting DBRS from defense, presence of current more setpoint of wearing-out and completion of the set dwell, to form the output signals of the three-phase disconnecting of contiguous switches, prohibition ARI saying no and contiguous switches, to provide disconnecting and prohibition ARI of switches of opposite end of line or middle tension of AT-330/154 (330/110) kV.

  • return of elements of dwells DBRS at the successful disconnecting of switches.