    1. Complete set of basic differential defense of wl-110 kV (transmission of signal on fibre-optic communication line) with the functions of reserve defense

The complete set of defense can consist of one or a few microprocessor devices and must realize next functions:

  • differential defense with the transmission of signals on FCL (fibre-optic communication line);

  • controlled from distance protecting from all kinds between phase contactors and contactors to earth;

  • four step current protecting from contactors with the organ of direction of power a zero sequence;

  • logic of the three-phase disconnecting;

  • logic of teleacceleration of reserve defense;

  • exposure of disrepair of current chains;

  • blocking at the disrepair of chains of tension;

  • protecting from the incompletely phase mode;

  • autoreclosing;

  • amount of groups of setpoints – not less than 4th;;

  • distance-finding to the site of damage;

  • real-time clocks with synchronization from an outsourcing;

  • free-programmable logic;

  • internal recorder of events;

  • oscillographic testing;

  • energyindependent memory;

  • measurings: currents, tensions, frequency, power;

  • self-diagnostic of device;

  • liquid-crystal screen on a front panel;

  • user-programmable light-emitting-diode indicators for signaling;

  • signaling about the state and functioning of device;

  • support of protocol of MEK 61850, and presence of standard international protocols of exchange by information for integration in ACS;

  • front port of Ethernet (Rs232) for connection with a device;

  • back port with an optical fibre ethernet-interface for connection with ACS substations;

    1. Complete set of defense wl-110 kV (on the controlled from distance and current principle) with funk-ciey dbrs,ari

The complete set of defense can consist of one or a few microprocessor devices and must realize next functions:

  • step controlled from distance protecting from all kinds between the phase shorting;

  • four the step current directed protecting of a zero sequence from contactors;

  • step controlled from distance protecting from all types of contactors;

  • maximal current defense (MCD);

  • fast-acting MCD (current pinch-off);

  • defense at including on a damage;

  • logic of the three-phase disconnecting;

  • logic of teleacceleration of reserve defense;

  • control of good condition of current chains;

  • control of disrepair of chains of tension;

  • freely programmable logic;

  • presence of three-phase DBRS;

  • presence of three-phase ARI;

  • internal recorder of events;

  • oscillographic testing;

  • energyindependent memory;

  • measurings: currents, tensions, frequency, power;

  • self-diagnostic of device;

  • liquid-crystal screen on a front panel;

  • user-programmable light-emitting-diode indicators for signaling;

  • signaling about the state and functioning of device;

  • location damage on a line;

  • groups of setpoints: no less 4th;

  • synchronization from the outsourcing of exact time;

  • support of protocol of MEK 61850, and presence of standard international protocols of exchange by information for integration in ACS;

  • front port of Ethernet (Rs232) for connection with a device;

  • back port with an optical fibre ethernet-interface for connection with ACS substations;