    1. Complete set of automation of management a switch 330 kV with the functions of dbrs, ari

The complete set of management automation can consist of one or a few microprocessor devices and must realize next functions:

  • Control of switching device (on - off));

  • realization of the one / three phase disconnecting of switch with starting DBRS;

  • control of good condition of current chains;

  • control of good condition chains of tension (circuit-disconnection fault);

  • freely programmable logic;

  • free configuration of entrances/outputs of device;

  • determination and reflection of current parameters of object;

  • synchronization from the outsourcing of exact time;

  • amount of groups of setpoints: no less 4;

  • operative blocking for an one-and-a-half chart;

  • control of synchronization and presence of tension;

  • autoreclosing ;

  • internal recorder of events;

  • oscillograph working;

  • energyindependent memory;

  • measurings of current parameters;

  • self-diagnostic of device;

  • signaling about the state and functioning of device;

  • support of protocol of IEC 61850, and also presence of standard international protocols of exchange by information for integration in ACS;

Requirements to software part:

  • liquid-crystal screen on a front panel;

  • user-programmable light-emitting-diode indicators for signaling;

  • front port of Ethernet (Rs232) for connection with a device;

  • two back ports with an optical fibre ethernet-interface for connection with ACS substations;

    1. Complete set by a basic differential-phase hf defense of wl-110 kV with the functions of reserve defense

The complete set of defense can consist of one or a few microprocessor devices and must realize next functions:

  • differential-phase defence with the transmission of signals to on HF to the channel;

  • controlled from distance protecting from all kinds between phase contactors and contactors to earth;

  • rebuilding from loading;

  • four step current protecting from contactors with the organ of direction of power a zero sequence;

  • possibility of starting DPD (different phase defense) from reserve defense;

  • operating on the three-phase disconnecting;

  • exposure of disrepair of current chains;

  • blocking at the disrepair of chains of tension;

  • blocking at swinging of power;

  • protecting from the incompletely phase mode (PIP);

  • autoreclosing ;

  • amount of groups setpoints – not less than 4th;

  • distance-finding to the site of damage;

  • real-time clocks with synchronization from an outsourcing;

  • free-programmable logic;

  • logic of teleacceleration of reserve defense;

  • internal recorder of events;

  • oscillographic testing;

  • energyindependent memory;

  • measurings: currents, tensions, frequency, power;

  • self-diagnostic of device;

  • liquid-crystal screen on a front panel;

  • user-programmable light-emitting-diode indicators for signaling;

  • signaling about the state and functioning of device;

  • support of protocol of MEK 61850, and presence of standard international protocols of exchange by information for integration in ACS;

  • front port of Ethernet (Rs232) for connection with a device;

  • back port with an optical fibre ethernet-interface for connection with ACS substations;