    1. Guarantees

The Supplier must ensure reliable and efficient operation of the whole system provided in accordance with the technical specifications for the system.

The warranty period for technical equipment must be at least 36 month from the date of delivery to the Employer on conditions that storing them at the Employer’s site, installation and commissioning works in accordance with the specifications of the Supplier

During the period of the warranty the Supplier must perform a warranty repair of technical equipment and eliminate errors and/or discrepancies with the technical requirements in the software of the system.

In the future, the Supplier should guarantee the supply of spare parts to the extent necessary for a fee the entire life of the hardware.

The Supplier must offer the terms of maintenance after the warranty period in the framework of a service contract.

  1. Technical data table for the acs tp

    1. General

The technical data sheets (TDS) presented below shall be completely filled in by the Tenderer and presented together with the Tender to the Employer.

Characteristics and guaranteed values included in these sheets shall become a part of the Contract and as such be binding. Deviations from the requirements, without the written agreement with the Employer, are not allowed

The Tenderer shall present all necessary catalogues and data for complete description of the offered equipment, mechanisms, accessories, devices and materials to be used for civil-erection works and commissioning.

The Tenderer shall bear responsibility for any errors, discrepancies or omissions in the characteristics offered by the Tenderer in the TDS.

The Tenderers shall realize that incomplete answers to questions asked mean discrepancy with the requirements of the Employer (Contract requirements), and such incomplete answers may result in the Employer's refusal from such Tenders.

The Tenderers in their Tenders shall confirm general compliance of the Tenders to the requirements of the Employer in general (without any deviations) or incompliance.

If there are any deviations/discrepancies, they shall be described and explained for each item of tables in the column "Note" or in separate sheet.

    1. Functional requirement Table 1.1: Technical requirements to acs tp hardware and software

Description

Data:

Notes

Required by the Employer

Guaranteed by the Contractor

Manufacturer

Network hardware

1.

SCADA system server

1.1

Reserved

yes

1.2

Industrial design, 19’’ Rackmounted

yes

1.3

Reserved power supply 230 VAC

yes

1.4

RAID controller

yes

1.5

Dual Port LAN adapter

yes

1.6

Internal monitoring

yes

1.7

Remote control

yes

2.

Gateways

2.1

Industrial design, 19’’ Rackmounted

yes

2.2

Reserved power supply 230 VAC

yes

2.3

Support of IEC 60870-5-101 protocol

yes

2.4

Support of IEC 60870-5-104 protocol

yes

2.5

Internal monitoring

yes

2.6

Remote control

yes

3.

Server of time synchronization with GPS receivers

3.1

Support of IEEE 1588

yes

3.2

Support of NTP(SNTP)

yes

3.3

GPS/GLONASS

yes

4.

Network switchers and routers LAN

4.1

Reserved power supply 230 VAC / DC

yes

4.2

Reserving of network connections

yes

4.3

Compliance with IEC 61850-3

yes

4.4

Compliance with IEEE 1613

yes

4.5

Compliance with IEC 61000

yes

4.6

Internal monitoring, watchdog-relay

yes

4.7

SNMP support

yes

4.8

Remote control/ configuration (web. telnet)

yes

5.

Reserved power supply 230 VAC / DC

5.1

Inverters 230 V AC/220 V DC – 230 V AC

yes

5.2

Two independent power supply lines

yes

5.3

SNMP support

yes

6.

Visualization tools

6.1

WS

6.1.1

Industrial design

yes

6.1.2

Reserved LAN adapter

yes

6.2

Display, diagonal not less 24’’, 2items

6.2.1

Matrix IPS, viewing angles are not worse than 178’

yes

6.3

Keyboard and optical mouse

yes

6.4

Remote viewing display

6.4.1

Display, diagonal not less 55’’, 1item

yes

6.4.2

Management (individual or by an operator station)

yes

6.5

Printer black & white

6.5.1

A4 format

yes

6.5.2

Connection via Ethernet

yes

7.

Technological function

7.1

Management

7.1.1

SU 330 kV – circuit-breakers

yes

7.1.2

SU 330 kV - disconnectors

yes

7.1.3

SU 330 kV – earthing blades

yes

7.1.4

SU110 kV – circuit-breakers

yes

7.1.5

SU 110 kV - disconnectors

yes

7.1.6

SU 110 kV – earthing blades

yes

7.1.7

SU 35 kV – circuit-breakers

yes

7.1.8

SU 10 kV – circuit-breakers

yes

7.1.9

SU 35 kV - disconnectors

Perspective

7.1.10

SU 10 kV -trolleys

Perspective

7.1.11

SU 35kV – earthing blades

Perspective

7.1.12

SU 10 kV – earthing blades

Perspective

7.1.13

Automatic Circuit-breaker 0.4 kV of auxiliary system (if operating mechanism is present)

yes

7.1.14

Automatic Circuit-breaker 0.4 kV of DC board (if operation mechanism is present)

yes

7.1.15

OLTC of autotransformers (AT)

yes

Perspective

7.1.16

Fire-extinguishing system’s elements (valves, gates)

yes

7.2

Position monitoring

7.2.1

SU 330 kV – circuit-breakers

yes

7.2.2

SU 330 kV - disconnectors

yes

7.2.3

SU 330 kV – earthing blades

yes

7.2.4

SU110 kV – circuit-breakers

yes

7.2.5

SU 110 kV - disconnectors

yes

7.2.6

SU 110 kV – earthing blades

yes

7.2.7

SU 35 kV – circuit-breakers

yes

7.2.8

SU 10 kV - circuit-breakers

yes

7.2.9

SU 35 kV - disconnectors

yes

7.2.10

SU 10 kV -trolleys

yes

7.2.11

SU 35 kV – earthing blades

yes

7.2.12

SU 10 kV – earthing blades

yes

7.2.13

Automatic Circuit-breaker 0.4 kV of auxiliary system (if operating mechanism is present)

yes

7.2.14

Automatic Circuit-breaker 0.4 kV of DC board (if operation mechanism is present)

yes

7.2.15

OLTC of autotransformers (AT)

yes

Perspective

7.2.16

Fire-extinguishing system’s elements (valves, gates)

yes

8.

Bay controllers

8.1

IEC 61850 support

yes

8.2

PLC IEC 61131-3

yes

8.3

Local MMI

yes

8.4

Reserved network connections

yes

9.

Integration into ACS TP

9.1

APAS system

yes

9.2

RP & SA system

yes

9.3

Security video surveillance system

yes

9.4

SURS monitoring system

yes

9.5

Meteorological monitoring system

yes

9.6

Electrical measurements system

yes

9.7

Fire-extinguishing system

yes

9.8

Ventilation and air conditioning system

yes

9.9

DC board (if controller is present)

yes

9.10

Auxiliary board (if controller is present)

yes

9.11

SS main equipment diagnostic system

yes

10.

System of data retransmission to higher levels of SS

10.1

IEC 60870-5-104 (101) protocol

yes

11.

Software for SHS of ACS TP

11.1

Basic (firm) software

yes

11.2

Application software

yes

12.

Local area network (LAN)

12.1

Fast Ethernet

yes

12.2

Gigabit Ethernet

yes

12.3

IEC 61850

yes

12.4

IEC 60870-5-101

yes

12.5

IEC 60870-5-103

yes

12.6

ІЕС 60870-5-104

yes

12.7

MODBUS

yes

12.8

PROFIBUS

yes

12.9

DNP

yes

12.10

Use of “ring” scheme

yes

12.11

Use of “star” scheme

yes

13.

Reservation of SS LAN

13.1

RSTP

yes

13.2

PRP

yes

13.3

HSR

yes

14.

User interface lauguage

14.1

Ukrainian

yes

14.2

Russian

yes

15.

Data export

15.1

Comtrade

yes

15.2

Excel

yes

15.3

Word

yes

16.

Operating requirements

16.1

Equipment self-diagnostics

yes

16.2

Software self-diagnostics

yes

16.3

Communication channels self-diagnostics

yes

16.4

Fault location testing

yes

17.

Requirements to protection of data against unauthorized access

17.1

Physical protection level

yes

17.2

Software protection level

yes

17.3

Devices polling interval not less than 1 sec

yes

17.4

DB used

yes

17.5

MS SQL Server

yes

17.6

ORACLE Database Server

yes