
reading / British practice / Vol D - 1990 (ocr) ELECTRICAL SYSTEM & EQUIPMENT
.pdf
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DC switchgear |
|||
•h „,„ |
, |
|
|
|
|
|
|
|
DISCRIMINATION 9Er.,IEEN FL:50 |
,_!NKS S ICH 103 |
||||||||
|
|
|
|
|
|
|
THE 'OTAL ; 2 ! OF THE MINOR FUSE LINT DOES NO ExCEED |
|||||||||||
|
450 |
|
|
|
|
THE PRE.ARC , NG i 2 : OF THE v0005 EL5E- |
|
|
||||||||||
|
; |
|
400 |
|
1 |
4- TOTAL OPERAflNG : |
|
500 |
|
|
|
|
|
|
|
|||
|
|
355 |
|
|
|
|
|
|
|
|
|
|||||||
|
IA |
|
315 |
|
|
-4- TOTAL OPERAT:NG I:. AT 0500 |
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
1 |
1 |
1 |
1 |
|||
|
|
1 |
60 |
|
|
|
|
|
|
|
|
|
|
|||||
1 I 1 |
|
250 |
10 ' |
|
4. TOTAL OPERATING 1 2 1 |
AT 2!5:., |
|
|
|
|
|
|
|
|||||
kiVie |
- 200 |
- 4- PRE ARCiNG i2t |
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
sasim |
125 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
80 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
1 |
1 |
1 |
1 |
1 |
1 |
i |
i |
|
|
|
|
|
|
|
|
|
. 0' |
|
i |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
.TI
|
|
|
|
|
1,000 |
10,000 |
200 250 315 355 400 450 SOO 560 630 670 7 0 750 aao !010 '_50 |
||
FUSE RATING A |
||||
RMS SYMMETRICAL PROSPECTIVE CURRENT, A |
||||
|
|
|||
F10. 5.62 Time/current characteristics |
|
Fla. 5.63 1 2 t characteristics |
is installed be capable of withstanding, at the circuit prospective current, the values of 'cut-off current and 'energy' 0 2 0 let-through commensurate with the higher rating, e.g., 100 A in the example.
Cartridge fuselinks of UK manufacture and com-
pliant with the appropriate British/DEF Standard are precision devices which have proved highly reliable in service when applied properly, i.e., selected, in the
•of motor circuits, with due regard to:
•The ratio of the starting/running current.
•The duration of the starting period.
•The number of sequential starts to be allowed for, i.e., successive starts without intervals between starts long enough to permit cooling.
Hie principles of the selection of fuses in schemes protection is described in Chapter 11.
8 DC switchgear
8.1 General
At the beginning of electricity supply, the sources of
such supply — dynamo charged batteries of secondary cells — produced unidirectional current (DC). A first
essential of any system of supply is means for establishment and interruption of current flow, i.e.,
switching on and off. The most elementary means are, of course, the coming together, and parting, in ambient atmosphere (air) of contacts of conducting material. The earliest devices for circuit 'making' and 'breaking' were as simple as this.
All practicable forms of interruption of an electric current involve the production of an arc, which must be extinguished to complete the interruption. The arc, an intensely hot column of conductive gas, is extinguished by cooling and lengthening to the point where the potential difference (voltage) across the contact gap, as it widens, becomes incapable of sustaining the arc. At full opening of the contacts, the dielectric strength of the gap must withstand the voltage across it.
The build-up of dielectric strength across the contact gap takes place similarly in the interruption of AC. However, the process of interruption in an AC circuit is assisted markedly by the occurrence of natural current zeros at every half cycle — arc extinction taking place at or near a current zero. The absence of naturally occurring current zeros in the case of DC thus
413
Switchgear and controlgear |
Chapter 5 |
|
|
renders the interruption of such currents a more difficult process.
From the simplest of devices initially, switching current in air, the switchgear evolved into open-type, i.e., unenclosed, air-break contact systems, at first operated manually, mounted on vertical panels of insulation material, such as slate. As systems developed, arc control became necessary to achieve satisfactorily reliable interruption. Development along these lines led, in due course, to the circuit-breaker concept as presently understood (see Section 2.1 of this chapter for definition of a circuit-breaker.)
Whilst development and general acceptance of the metal-enclosed concept followed rapidly upon the appearance, in the early part of this century, of the oil circuit-breaker in the AC field, DC switchgear continued firmly in the open-type tradition for several decades. However, for many years now, the bulk of DC switchgear in UK power stations has been at least metal-enclosed and, wherever possible, metalclad. A definition of `metalclad' is given in Section 4.2 of this chapter.
Broadly, the several types of switchgear equipment comprising a DC system installation, e.g., circuitbreakers, contactor controlgear, fusegear, are two-pole versions of their three-phase AC counterparts.
8.2 System conditions
The usual system voltages and fault levels are:
• |
System voltage nominal, V DC |
48 |
110 |
220 |
250 |
• |
System short-circuit level |
|
|
|
|
|
Fault current, kA |
20 |
40 |
40 |
40 |
|
Time constant, s |
0.015 |
0.02 |
0.02 |
0.02 |
To meet these system conditions, the basic capability required of the major components of a DC switchgear installation is described in the paragraphs that follow.
8.2.1 Short-circuit withstand strength of busbar systems
•The full fault current level of the system for 3 s, where the busbar protective device is a circuitbreaker.
•The full fault current level of the system, as limited in magnitude and duration by the 'cut-off' characteristic of the fuses, where the busbar protective device features fuses.
8.2.2 Current making/breaking and short-circuit capability of main circuit switching devices
Circuit- breaker equipment
Rated short-circuit making and breaking current — 40 kA at a time-constant appropriate to the system.
Short-time current capability — the full fault current level of the system for 3 s.
Contactors
As for AC applications, contactors are selected as follows in accordance with the 'duties' and 'utilisation categories' recognised in BS5424: Part I:
•Motor control
Rated duty. Utilisation category:
is the starting and switching off, of shunt-motors.
DCI where the duty is as for DC2, but with the addition of 'inching' or 'plugging'.
DC4 where the duty is the starting and switching off, of series motors.
DC5 where the duty is as for DC4 but with the addition of 'inching' or 'plugging'
Mechanical endurance: 1 million no-load operating cycles
Accelerating contactors may be of intermittent duty.
•Substantially non-inductive loads switched on for long periods
Rated duty: |
Uninterrupted |
Utilisation category: DCI
Mechanical endurance: 0.3 million no-load operating cycles
Additionally, contactors must be capable of making and carrying the prospective short-circuit current of the system as limited in magnitude and duration by the associated circuit short-circuit protective devices, i.e., fuselinks.
Starting resistors must limit motor starting currents to not more than 250% of the normal full-load current, or such lower value as may be dictated by a particular motor design. They must be capable of carrying starting current for a minimum of five minutes.
9 Construction site electrical supplies equipment
9.1 General
The following sections outline equipment for the provision of site electrical supplies at 4 15, 240 and 110 volts AC 50 Hz, single or three-phase, for site construction purposes.
414

Fhe equipment comprises:
• Portable substations.
Pori,ible distribulion units 4.15/240 V.
•
Portab!.... distribulion units 110 V.
•
supply scheme is shown in Fig 5.64.
Construction site electrical supplies equipment
9.2 Portable substations
The substations provide supplies at 415/240 V, derived from an ii kV source. Figure 5.65 depicts a typical arrangement.
The transformer in the substation has a rating of 1000 kVA at a primary voltage of 11 kV. The high
|
'kV SUPPLIES FROM AREA |
|
BOARD OR POWER STATION |
111A/ RING MAIN |
ttkV RING MAIN |
PORTABLE |
PORTABLE |
SUBSTATION |
SUBSTATION A |
No ,5 Cr |
Not 11 |
|
|
|
|
|
|
415/240V PORTABLE |
||
|
|
|
|
|
|
DISTRIBUTION UNITS* |
||
|
|
|
|
|
|
No3 |
||
|
|
|
|
|
|
* |
|
|
|
|
|
|
|
|
|
|
|
|
|
11 11 11 11 1 |
1 |
|
|
|
|
11 11 11 11 11 |
|
110V PORTABLE |
|
|
|
||||
|
|
|
|
|
||||
|
No.4 |
|
|
110V |
||||
|
DISTIRBUT ON |
|
|
PORTABLE |
||||
|
|
UNIT |
|
|
DISTRIBUTION |
|||
|
|
|
|
|
|
|
|
UNIT |
I |
|
PORTABLE |
|
WI] |
||||
|
|
SUBSTATION D |
I
PORTABLE
SUBSTATION C
FIG. 5.64 Typical site supply scheme
415

Switchgear and controlgear |
Chapter 5 |
|
|
|
|
1000kVA TRANSFORMER |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TRUNKING |
||||||
|
|
|
|
TRLINKING |
||||
415/240V |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
DISTRI6LIT1ON PILLAR |
|
|
|
|
|
|
|
t1kV RING MAIN UNIT |
RN
LIFTING LUGS
LV CABLES |
HV CABLES |
SKID BASE
ELEVATION FENCE REMOVED)
ALL ACCESS COORS
ARRANGED FOR
PADLOCKING
DISTRIBUTION PILLAR 4151240V 3 PHASE & N
11 11 11 11 11 11
2509mr1 HIGH
SECTIONAL |
|
METAL MESH |
PLATE STEEL FLOORING |
SCREEN |
2300mm MAX
4600mm APPROX
PLAN
1000 kVA |
|
TRANSFORMER |
IIkV RING |
|
MAIN UNIT |
UV RING MAIN
400A 630A
DIAGRAM OF CONNECTIONS
Fro. 5.65 Portable substation, 11 006/415/240 V
416
|
|
|
|
Construction site electrical supplies equipment |
|||||
|
|
|
|
|
|
||||
o |
we switchgear comprises an oil-immersed, on-load |
padlockable access gates, is affixed around the peri- |
|||||||
main unit with tee-off fuse switch incorporat- |
meter of the assembly. A label is attached to the fence |
||||||||
|
|
||||||||
|
e high breaking capacity (HBC) fuses. Operating |
indicating the gross weight of the equipment. |
|||||||
rae-chanisnis are of the independent manual type. The |
|
|
|
|
|
||||
|
|
s,.vitch is tripped automatically upon operation |
9.3 Portable distribution units (415/240 V) |
||||||
|
|
anv one fuse. Nlechanical interlocking is provided |
|||||||
|
|
protect the operator from contact with live parts |
These distribution units provide supplies at 415/240 V. |
||||||
|
|
replacing. fuselinks. Integral earthing devices are |
|||||||
|
|
The equipment is enclosed in a weatherproof housing |
|||||||
|
|
to facilitate the earthing of the transformer and |
|||||||
|
|
mounted on a rigid steel base, suitable for handling |
|||||||
one or both ring, main cables. A safety device pre- |
|||||||||
by crane or winch onto a roughly levelled hard-core |
|||||||||
|
|
it s aLicess to switches or bushings unless all switches |
|||||||
|
|
foundation. Figure 5.66 depicts a typical construction. |
|||||||
|
|
in the 'earth' position. A maximum demand am- |
The units are equipped with triple-pole and neutral |
||||||
|
|
|
current operated, is fitted to the tee-off fuse- |
fuse switches complete with NBC fuselinks, entries for |
|||||
|
|
i tc h portion. Cable boxes with cable glands pointing |
|||||||
• |
|
power cables, one 12-way 32 A triple-pole and neutral |
|||||||
ertically downwards are provided for the incoming |
distribution fuseboard feeding 32 A socket outlets, |
||||||||
aild outgoing ring main cables. |
featuring earth leakage protection. |
|
|
||||||
|
|
The 415/240 V distribution pillar is a weatherproof |
The unit is provided with a voltmeter, visible when |
||||||
,hect steel housing having padlockable access doors |
|||||||||
the doors are closed. Bulkhead type light fittings are |
|||||||||
front and rear. The base plate is constructed in two |
|||||||||
provided at front and rear. Electric heaters are fitted |
|||||||||
.eetions which can be removed separately to aid the |
to combat condensation. These items are supplied direct |
||||||||
process of cable installation. The base plate is sealed |
|||||||||
from the busbars and are protected by HBC fuses. |
|||||||||
a2ainst the ingress of moisture or vermin. The fuse |
|||||||||
The unit enclosure is provided with a substantial |
|||||||||
units are screened so that work can be carried out on |
|||||||||
earth terminal for connection to the site earthing system. |
|||||||||
He load side of any circuit when the adjacent circuits |
|||||||||
|
|
|
|
|
|||||
are 'live'. |
|
|
|
|
|
||||
|
|
The pillar unit comprises: |
9.4 Portable distribution units {110 V} |
||||||
• |
|
Three 630 A (three-phase and neutral) fuse units |
These distribution units provide supplies at |
110 V sin- |
|||||
|
|
0,ith 630 A HBC fuses, neutral links and gland entries |
gle or three phase. Units are rated 5, 10 or 25 kVA. |
||||||
|
|
for 4-core power cables. |
|||||||
|
|
Figures 5.67 and 5.68 illustrate typical constructions. |
|||||||
|
|
|
|
||||||
• |
|
Three 400 A (three-phase and neutral) fuse units |
The units are of sheet steel weatherproof construc- |
||||||
|
|
ith 400 A HBC fuses, neutral links and gland entries |
tion mounted on rubber-tyred wheels. All components, |
||||||
|
|
for 4-core power cables. |
such as fuse-switches and distribution boards mounted |
||||||
|
|
on the transformer tank, are secured by welded attach- |
|||||||
|
|
|
|
||||||
Lich circuit is fitted with a current-transformer- |
ments. The units are equipped as follows: |
|
|
||||||
|
|
|
|
|
|||||
|
perated maximum demand ammeter. |
|
|
|
|
|
|||
|
|
(he pillar is fitted with a phase selector switch and |
|
|
|
|
|
||
|
|
Rating |
Input 415 V |
Output 110 V |
No of |
||||
.1 |
|
oltmeter, visible from the front of the unit when the |
|||||||
|
kVA |
|
|
Socket outlets |
|||||
Joors are closed. Door operated bulkhead lighting is |
|
|
|||||||
|
|
|
|
|
|||||
.i kluded, together with an electric heater of adequate |
5 |
63A |
6-way, 20 A three-phase |
|
|
||||
|
|
|
to prevent condensation. These items are |
|
triple-pole |
and neutral distribution |
|
|
|
, uoplied directly from the busbars and protected by |
|
switch |
fuseboard |
6 |
|
||||
I I li C fuses. |
10 |
63A |
I2-way, 20 A three-phase |
|
|
||||
• |
|
I he connecting busbars between transformer, HV |
|
triple-pole |
and neutral distribution |
12 |
|
||
|
ichgear and pillar are of copper, enclosed in a |
|
switch |
fuseboard |
|
||||
|
|
|
trunking. |
25 |
63A |
Three-phase and neutral |
|
|
|
|
|
1 copper earth bar with a section of about 500 min |
|
triplepole |
fuse-switch fitted with |
|
|
||
|
|
inm is provided, to which is connected the neutral |
|
switch |
1 60 A fuselinks |
|
|
||
|
|
|
|
|
|
|
|||
c.irthing li nk of the distribution pillar, the earthing |
|
|
|
|
|
||||
|
|
|
|
|
|||||
points of equipment and all metal framework and |
|
|
|
|
|
||||
, |
|
reens. The earth bar is connected to the site earthing |
The transformer is a three-phase ON type having a |
||||||
|
|
|
|
voltage ratio of 415/115 V at no-load, suitable for |
|||||
|
|
[he equipment is mounted on a rigid steel baseframe |
operation on a nominal 415 V three-phase system |
||||||
, i][!,thle for handling by crane or winch onto a roughly |
having its neutral point solidly earthed. |
|
|
||||||
1:: ■ c.11ed hard-core foundation. Steel plate flooring is |
An earthing terminal of approximately 12 mm dia. |
||||||||
nosuioned around the plant, fixed to the frame, to |
x 25 mm long is provided on the enclosure. |
||||||||
Pro‘Ide safe access for operation and maintenance. |
Neutral links are of the bolted type. Distribution |
||||||||
|
|
-1 metallic fence, approximately 2500 mm high, sec- |
fuseboards are connected directly to the LV terminals |
||||||
|
|
ried to facilitate easy removal and provided with |
of the transformers. |
|
|
|
417

|
|
|
Switchgear and controlgear |
Chapter 5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
BUSBAR |
|
|
BUSBAR |
|
VOLTMETER |
|
CHAMBER |
|
LIFTING LUGS |
|
CHAMBER |
|
|
|
||||
|
|
|||||
|
|
|
|
|
|
|
2COA TP&N
ELI 0
1C0A TP&N
TP&N
[ aCOA TP&N
IN
_
12 WAY 32A
TP&N
DISTRIBUTION FUSEBOARD
1800mm APPROX
FRONT ELEVATION (DOORS OPEN)
REAR ELEVATION (DOORS OPEN)
-■■■•■■,.
— -r
200A TP&N
0
TP&N
EARTHING POINT
|
|
|
|
|
|
|
|
II |
/ |
|
|
|
|
|
I/ |
/I |
|
|
||
|
/ |
|
|
|
I I |
|
|
|
|
|
|
|
|
|
/0. |
|
|
I I |
|
|
e |
|
|
||||
e |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SIDE ELEVATION |
INCOMING
SUPPLY
?I, 400A
( AT INI gENEEPUT l 'ISAIE_ (TP&NI
J5 Zc |
b |
FUSE
SWITCHES
THREE PHASE
AND NEUTRAL
FUSE BOARD
32A SOCKET OUTLETS
Fro, 5,66 Portable distribution unit, 415/240 V
4'18

Construction site electrical supplies equipment
X rt11111 |
Ymm |
LIFTING LUGS
, JEuTRAL EARTH LINK
Li
11,
63A TP SWITCH
SOCKET
O u TLETS
EARTH
TERMINAL
DISTRIBUTION
FUSE BOARD
INCOMING 4I5V
3 PHASE. 50Hz
|
|
|
|
RATING |
01ST RIB— |
No. OF |
APPROX DIMENSIONS |
||
|
|
|
|
UTION |
|||||
|
|
|
|
kVA |
BOARD |
SOCKETS |
|
|
|
63A TP SWITCH |
|
|
X |
Y |
7 |
||||
|
|
|
|||||||
|
|
|
|
|
|
||||
|
|
|
|
5 |
6 WAY |
6 |
760 |
760 |
640 |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10 |
12 WAY |
12 |
920 |
920 |
840 |
|
|||||||||
|
|
|
|
|
_ |
|
|
|
|
415,110V TRANSFORMER |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
NEUTRAL
EARTHING
|
|
|
|
|
|
|
|
|
|
|
|
THREE PHASE |
|
|
|
|
|
|
|
|
|
|
|
|
AND NEUTRAL |
|
|
|
|
|
|
|
|
|
|
|
|
DISTRIBUTION |
|
|
|
•■■•• |
|
|
|
|
|
|
|
FUSE BOARD |
|
|
|
|
|
|
|
|
|
|
|
|
|
16A SOCKET |
t*".■ rm |
|
|
|
|
|
|
|
|
|
|||
|
|
(Th e•—•■ (Th f.m (Th (Th (-1 OUTLETS |
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
• |
DIAGRAM OF CONNECTIONS
Fia. 5.67 Portable distribution units, 110 V/5 and 10 kVA
419

|
|
Chapter 5 |
Switchgear and controlgear |
12C.-.; mr, APR FI C X |
|
|
1000mm APPROX |
71, |
|
LIFTING LuGS
MOnini APPROX
TP AND N FUSE S,V,TCH
INCOMING 415V
3 PHASE, 50Hz
63A TR SWITCH
25kVA 415/110V TRANSFORMER
NEL;THAL |
TP AND N FUSE SWITCH |
EAPTHING |
FITTED WITH 160A |
LINK |
FUSE LINKS |
DIAGRAM OF CONNECTIONS
FiG. 5.68 Portable distribution unit, 110 V/25 kVA
420
|
|
Future trends in development and application |
|
|
|
|
|
Socket outlets are situated on the exterior of the sheet |
decreased proportionally. These changes not only im- |
||
qeel |
housing, and connected to the distribution board |
prove the mean time between failure but also achieve |
|
by cable. |
a marked reduction in operating storage batteries. |
||
The earthing terminals of fuse-switches and distri- |
The trends toward simpler and more reliable con- |
||
mit i on boards are connected to the earth terminal on |
struction also enable costs to be reduced, both for initial |
||
he transformer tank. The neutral point of the LV |
purchase and for subsequent preventive and corrective |
||
inding is connected to the earth terminal on the |
maintenance. However, the engineer must always be |
||
;Linsformer tank through a bolted link located in an |
conscious of the fact that innovation and improve- |
||
Jccessible position. |
ment do not always go hand in hand. New designs of |
||
switchgear still require careful evaluation and thorough |
|||
|
|
||
|
|
type testing. Where switchgear forms part of 'strategic' |
|
10 Future trends in development and |
or 'safety related' systems, in which its failure could |
||
have serious effect, then proven service reliability may |
|||
application |
|||
need to be demonstrated prior to its full scale adop- |
|||
|
|
tion. Trial installations for evaluation purposes are of |
|
10.1 |
General |
long term benefit both to user and manufacturer. |
|
|
|||
With the trend towards use of plant requiring minimum |
10.2 Oil-break switchgear |
||
maintenance, and the ever present quest for first cost |
|||
and space optimisation, the types of switchgear on offer |
Switchgear employing oil for both insulation and inter |
||
to the applications engineer has changed dramatically |
|||
rupting purposes has not found favour for application |
|||
recent years. That such changes have particularly |
|||
in UK power stations for many years, not least because |
|||
affected the voltage range from 1 kV to 36 kV can be |
|||
of the hazards of explosion and fire which, although |
|||
attributed to the fact that investment worldwide in |
|||
minimised by careful design, can never be eliminated. |
|||
clectrical plant is necessarily biased toward distribution |
|||
Nevertheless, the oil circuit-breaker, whether it be of |
|||
vsterns. Whereas the ratings required of distribution |
|||
the bulk oil or minimum oil type, still continues to give |
|||
switchgear are generally lower than those of power |
|||
reliable service in distribution systems but is steadily |
|||
station switchgear, there is no doubt that research and |
|||
being replaced by the new ranges of low maintenance, |
|||
development aimed at the former has also been of |
|||
low fire-risk switchgear now available. |
|||
benefit to the latter. |
|||
|
|||
Since switchgear exists to control and protect the |
|
||
electrical system to which it is connected, it is of |
10.3 Air-break switchgear |
||
paramount importance that it can perform these duties |
|||
The progressive development of the early air-break |
|||
with maximum reliability. The duty of short-circuit |
|||
protection has particular significance in power stations, |
'knife switch' with plain gap into a reliable circuit- |
||
since the close coupling of several high energy sources |
breaker has taken a number of decades and has today |
||
leads to very high short-circuit currents and the me- |
been perfected to the level where sophisticated inter- |
||
chanical stresses resulting therefrom to system plant, |
rupting devices, employing magnetic blow-out circuits, |
||
husbars and cabling. |
arc guidance systems and arc-resistant insulation, en- |
||
It is a well established fact that the failure rate of |
able very high breaking capacities to be achieved with |
||
any item of engineering plant is proportional to the |
air-break switchgear. |
||
number of components comprising that item. A com- |
The use of such complex and bulky interrupting |
||
parison between the latest designs of interrupter unit |
devices, coupled with the more generous air clearances |
||
for switchgear and long established designs shows clear- |
required, is not without its penalties. These ate, for |
||
]y that there is a distinct trend towards the reduction |
power station auxiliary HV switchgear, evidenced by the |
||
of components, particularly in the interrupter. This |
i mpressive size and weight of switchgear panels, their |
||
move |
has doubtless been assisted by an increasing |
high-initial cost and the skills required to perform major |
|
understanding of arc control technology and the uti- |
maintenance work. |
||
lisation of modular construction, together with new |
There have been some savings possible at HV with |
||
materials a,nd assembly methods. |
the introduction of the motor switching device, which |
||
Statistics show that the majority of switchgear fail- |
has been described earlier in this chapter, and further |
||
ures can be attributed to mechanical rather than electri- |
development of this device is expected albeit by em- |
||
cal breakdown. Switchgear development has therefore |
ploying power fuses in combination with low rated |
||
eoncentrated much effort upon improving mechanical |
vacuum or alternative modern arc control devices. |
||
reliability. A distinct merit of the latest interrupter |
At LV, the application of reliable high breaking |
||
devices is that the mechanical stresses occurring within |
capacity fuses of UK design means that the demand |
||
the switchgear during short-circuit breaking and making |
for high capacity air-break circuit-breakers is generally |
||
have |
been reduced and the resultant energy require- |
li mited to main feeder circuits only. However, some |
|
ments of the opening and closing mechanisms have |
other industrialised countries were less successful in |
421
Switchgear and controlgear |
Chapter 5 |
|
|
the development of HBC fuses and as a result a viable alternative known as the moulded case circuit-breaker ( MCCB) was developed and subsequently introduced to the UK.
The moulded case circuit-breaker, as its name implies, uses moulded insulation materials, permitting space and weight reduction. in some instances the filler in the moulding material is claimed to assist in the arc extinguishing process by producing gases favourable to current interruption. Current-limiting properties, similar to those of HBC fuses, can also be utilised to reduce fault damage and a regime of rating steps (as for fuses) must also be followed to ensure discrimination. As an alternative to 'traditional' fuse switchgear, the MCCB can also fulfil a role within motor starter circuits. MCCBs now available on the UK market have found limited favour with some users but have yet to make their mark in UK power station applications. With a specified service life for power station plant MCCBs in 'non-maintainable' form would not be acceptable.
The maintenance of power station switchgear at service capability is based upon the programmed overhaul/repair of equipment installed for the station designed life. Whilst 'maintainable' moulded-case circuitbreakers may have a place, the 'non-maintainable' form is as yet unacceptable by virtue of the difficulty of determining the performance capability after a period of service, particularly if fault clearances have been a feature of that service.
10.4 Air- blast switchgear
Exploitation of the improved 'dielectric withstand of air subjected to pressures above atmospheric level has resulted in present day designs of air-blast switchgear. Designs of air-blast interrupter employing compressed air stored at pressures of the order of 30 bar, with sophisticated gas flow technology applied to the nozzles and contacts in the arc region, are capable of achieving the highest short-circuit breaking capacities demanded today. These units therefore find ready application as generator circuit-breakers for the largest steam turbinegenerator units available and can be forced cooled, where necessary, to match generator load currents.
The high cost of air-blast switchgear which must also include ancillary compressor and air storage plant, plus the noise accompanying each switch opening, precludes the wider application of these units to power station general auxiliary systems.
Similar air-blast switchgear was also developed for distribution and transmission systems up to highest EHV levels. However, with the advent of new arcinterruption technology and more environmentally acceptable low maintenance switchgear, the air-blast circuit-breaker has declined rapidly in favour during the last decade and now worldwide is being applied only under special circumstances. This trend can be expected to influence future application of air-blast
technology to power station generator switchgear where alternatives are now available for all but the very highest short-circuit breaking capacities.
10.5 Vacuum switchgear
Although researched in the 1920s, vacuum arc-inter- rupting devices did not achieve commercial viability until the 1960s. The factory sealed vacuum interrupter has subsequently introduced to the switchgear field a unit which is claimed by some to approach the 'ideal' circuit-breaker of electrical theory. However, the aura which tends to surround all 'black-box' components has also given rise to some concern over their performance and reliability, particularly in power station applications, in their behaviour when switching motors and the possibility of loss of vacuum.
Satisfactory service experience with vacuum switchgear during the last decade has dispelled most of the doubts. Furthermore, research in the laboratory and in the field has tended to confirm that some phenomena are not unique to vacuum interrupters and that for critical service conditions some special precautions may be appropriate to both established and innovative designs.
The success of any electric arc-interrupting device lies in its contact geometry and, particularly with the vacuum unit, the chemistry of the contact materials is also of great significance. Whilst the reader wishing to study the contact materials technology in detail can refer to the many learned papers now published on the subject, it is sufficient to note here that it is the precise composition of the basic contact metal, copper, together with controlled additives and the exclusion of impurities, which dictate performance.
Vacuum interrupter development has produced units for circuit-breaker application, with its demands for high short-circuit breaking capacity and moderate number of switching operations, and for contactor application, with moderate short-circuit breaking capacity and high number of switching operations. A basic advantage of the contactor interrupter, as manufactured in the UK, is that it provides a 'soft' operating characteristic particularly suited to regular switching of load currents including high reactance transformers and small motors, etc. Compared with the contactor type, the circuit-breaker interrupter has a relatively 'hard' characteristic. This is presently unavoidable, being an inherent feature of interrupters designed specifically for very high currents, i.e., short-circuit currents. Briefly, a 'soft' interrupter is one with a negligible propensity to 'current chop', and thereby produce overvoltage likely to damage plant insulation. Conversely, a 'hard' interrupter is one with a tendency towards such behaviour. Current chopping is the term used to describe the sudden reduction to zero, during the process of interruption, of an alternating current at a ti me other than the instant of a natural zero. Theoretically, an interrupter 'breaks' an alternating current
422