Добавил:
Upload Опубликованный материал нарушает ваши авторские права? Сообщите нам.
Вуз: Предмет: Файл:
CHAPTER_4.docx
Скачиваний:
0
Добавлен:
01.04.2025
Размер:
160.47 Кб
Скачать

7.14 Air supply and distribution system

The design of all systems must comply with the ASHRAE handbook and to the require­ments of NFPA Standards Nos. 90A, 90B, and 91.

7.14.1 Basic Design Principles

All designs will be based on the following basic principles:

  • Interior design conditions, including temperature, humidity, filtration, ventila­ tion, and air changes, will be suitable for the intended occupancy.

  • The designer will evaluate all energy conservation items that appear to have potential for savings, such as heat recovery for HVAC and service water heating, economizer cycles, and plastic door strips for load docks, and will include those items in the design that are life cycle cost-effective.

  • The design will be as simple as possible.

  • Adequate space will be provided for maintenance access to ancillary equipment such as filters, coils and drain pans, and strainers.

  • To the extent practical, system airflow will be minimized. Integrated air- conditioning and lighting systems will be used whenever the general lighting level is 100 fc or greater.

  • Recovered heat will be used for reheat where possible.

7.14.2 Temperature Settings

HVAC sequence of control should include procedures for personnel to reset HVAC control settings in occupied zones from 76°F (24°C) up to 78°F (26°C) if future energy con­servation actions are required.

  • The design relative humidity will be at least 50% or the design temperature equal to the outside air dew point design temperature, whichever is less.

  • The indoor design specific humidity will not exceed the outdoor design specific humidity; otherwise the indoor design relative humidity will be 50%.

  • The indoor design temperature provided by evaporative cooling or comfort mechanical ventilation will be 80°F.

7.14.3 Air-Conditioning Loads

• Air-conditioning loads should be calculated using ASHRAE methods. The designer should plot the following on a psychometric chart:

—Entering and leaving air temperature conditions for the coil

—Expected room conditions

—Outside air conditions for each air system

7.14.4 Infiltration

Where acceptable, air distribution systems for the central HVAC systems will be designed to maintain a slight positive pressure within the area served to reduce or eliminate infiltration.

7.14.5 Outdoor Air Intakes

Outdoor air intakes will be located in areas where the potential for air contamination is lowest. This is a common design problem that routinely needs correction. Basic guide­lines for air intake location include the following:

  • Maximize distance between the air intakes and all cooling towers, plumbing vents, loading docks, and traffic stations

  • Maintain a minimum distance of 30 ft (9.2 m) between air intakes and exhausts— more if possible

  • Locate air intakes and exhausts on different building faces

7.14.6 Filtration

For administrative facilities, commercial facilities, and similar occupancies where IAQ is of primary concern, the combined supply air, including return and outside air, should be filtered. Filtration uses a combination of 25 to 30% efficient prefilters and 80 to 85% efficient final filters as determined by the dust spot test specified in ASHRAE Standard 52.

Due to the decrease in system airflow as the pressure drop across the filters increases, fans should be sized for the "dirty" filter condition. This sizing will ensure that the fan has adequate capacity to deliver the design airflow as the filter becomes loaded. To ensure that this fan capacity is "available," test and balance criteria need to estimated appropriately.

Соседние файлы в предмете [НЕСОРТИРОВАННОЕ]