Ip Information

This is where the CXC factory unit default values are displayed. Scroll bars enable the user to navigate the list of

text items for viewing; i.e., IP address, Subnet Mask, Gateway and Ethernet/MAC Address.

Ip Address (“Ethernet” per web interface)

This menu item enables the Supervisor to program the web interface parameters, see Figure 84 below:

Discard changes and

return to previous screen

Toggle the check box to select

0350046-J0 Rev C

Tap on the number to edit

Via a virtual numeric keypad

Figure 84–IP Address window

Sliders and scroll bars

are used for navigation

Accept changes and

return to previous screen

Page 83 of 127

Refer to the back of this manual for Factory Service and Technical Support contact information

6.8.3.1

CXCI IP Address Reset and Startup

This feature enables the user to reset the IP address of the CXCI. It is a function of the front

panel reset button on Cordex controllers that have only a 4-digit display.

The reset button located on the front panel of the CXCI is for restarting the microprocessor.

When pressed momentarily, the unit beeps twice then resets. The front-panel LED’s will

illuminate temporarily, but will extinguish after the system has finished its 15-second self-test.

To reset the IP address, press and hold the front panel reset button for three seconds. The unit

will beep three times, IP will be reset (to 10.10.10.201) and DHCP (see 8.1.1.5) will be disabled.

The settings will be saved and the unit will then reset.

There is also a “hard” reset button located on the side of the CXCI. Pressing this button will

reset the CXC but will not affect any settings; has the same functionality as the reset button on

a CXC with a touch screen LCD.

5

1.

2.

3.

4.

Attempt to synchronize with the NTP server (see www.NTP.org), otherwise:

Retrieve the last time stamp from the Event Log, otherwise:

Retrieve the last time stamp from the Statistics Log, otherwise:

Set the time to 2005-01-01 midnight (if the above methods fail).

6.8.4

Modem (“PPP Connection Device/Rear Modem Port” per web interface)

This menu item enables the Supervisor to set the baud rate and the CXC’s rear port device (Internal / External /

6

See 8.3 for modem compatibility. See tables

for factory defaults (baud rate and initialize

string). Modem baud rate is initialized to the

value stored in the settings file on start up.

Discard changes and

return to previous screen

Select from the pull-down menus

Modem menu/window may appear different

for systems equipped with a CXCI

Factory setting is displayed here and may

be edited via the web interface

Figure 85–Modem window

Accept changes and

return to previous screen