page 173

TT - timer timing bit

DN - timer done bit

PRE - preset word

ACC - accumulated time word

• Counter C5 values are addressed using the number of the counters, and an associated data type. For example the accumulator value of counter 3 is C5:3.ACC or C5:3/ACC.

CU - count up bit

CD - count down bit

DN - counter done bit

OV - overflow bit

UN - underflow bit

PRE - preset word

ACC - accumulated count word

7.12.1.4 - PLC Status Bits (for PLC-5s)

• Some of the more commonly useful status bits in data file S2 are given below. Full listings are given in the manuals.

S2:0/0 carry in math operation

S2:0/1 overflow in math operation

S2:0/2 zero in math operation

S2:0/3 sign in math operation

S2:1/14 first scan of program file

S2:8 the scan time (ms)

S2:18 year

S2:19 month

S2:20 day

S2:21 hour

S2:22 minute

S2:23 second

S2:28 watchdog setpoint

S2:29 fault routine file umber

S2:30 STI (selectable timed interrupt) setpoint

S2:31 STI file number