Fuzzy PID Controllers for Industrial Applications

G. Ron Chen

Lecture for EE 6452

City University of Hong Kong

Summary

∙Proportional-Integral-Derivative (PID) controllers are the most widely used controllers in industries today

∙Statistics: > 90% controllers in industries are PID or PIDtype of controllers (the rest are programmable logical controllers (PLC))

∙Merits of PID controllers: simple, cheap, reliable, and effective

∙For lower-order linear time-invariant systems and processes, PID controllers have good set-point tracking performance with guaranteed stability

∙Fuzzy logic provides a certain level of artificial intelligence to the conventional PID controllers

∙Fuzzy PID controllers have self-tuning ability and on-line adaptation to nonlinear, time -varying, and uncertain systems

∙Fuzzy PID controllers provide a promising option for industrial applications with many desirable features

Outline of the Presentation

∙Overview of the Fuzzy Logic Technology

∙Overview of Conventional PID Controllers

∙Introduction to Fuzzy PID Controllers

∙Some Successful Examples of Applications

∙Concluding Remarks

Overview of the Fuzzy Logic Technology

Closed-Loop Set-Point Tracking System

Consider the typical set-point tracking system:

r

+

Σ

e

Controller

u

Plant

y

(reference

(error

(control

 

 

 

(output

 

signal)

−

signal)

 

signal)

 

 

 

 

 

 

 

 

signal)

Figure 1 A typical closed-loop set-point tracking system

Objective:

e(t) := r(t) − y(t) → 0 (t→∞)

Approach: Design a fuzzy logic controller (FLC)

e

Fuzzification

Fuzzy Rule Base

Defuzzification

u

controller

controller

 

 

 

input

 

 

 

output

 

 

Fuzzy Logic Controller (FLC)

 

 

 

Figure 2 General structure of a fuzzy logic controller

 

temperature

 

 

b

c

y(t )

r = 45 o

d

 

 

 

e(t )

 

 

a

 

 

0

 

 

 

t

Figure 3 Temperature set-point tracking example

(i) If e > 0 then

 

 

 

 

e = r − y > 0

or

 

r > y

the output y is at position

a

or

d

(ii) Furthermore, if

e& < 0

then

 

e& = r& − y& = 0 − y&

 

or

y& > 0

(iii) Therefore, the output

y

is at position a

Fuzzy Logic Rule Base:

 

R1:

IF e > 0

AND e& < 0 THEN u(t+) = u(t)

R2:

IF e < 0

AND e& < 0

THEN u(t+) = − u(t)

R3:

IF e < 0

AND e& > 0

THEN u(t+) = u(t)

R4:

IF e > 0

AND e& > 0

THEN u(t+) = − u(t)

Fuzzy Controller Design

A. Fuzzification

Purpose: Enable the input physical signal to use the rule base

Approach: Use membership functions

 

 

 

 

1

μPS

μPL

μNL

μNS

1

 

 

 

 

0

H

.

−H

 

0

.

e, e

 

e, e

 

 

(a)

(b)

 

 

 

Figure 4 Four membership functions for signals e and e&

 

 

 

B. Programmable Rule Base

R1:

IF e = PL AND e&

R2:

IF e = PS AND e&

R3:

IF e = NL AND e&

R4:

IF e = NS AND e&

R5:

IF e = NL AND e&

R6:

IF e = NS AND e&

R7:

IF e = PL AND e&

R8:

IF e = PS AND e&

<0 THEN u(t+) = μP L(e) . u(t)

<0 THEN u(t+) = (1−μPS(e)) . u(t)

<0 THEN u(t+) = −μNL(e) . u(t)

<0 THEN u(t+) = −(1−μNS(e)) . u(t)

>0 THEN u(t+) = μNL(e) . u(t)

>0 THEN u(t+) = (1−μNS(e)) . u(t)

>0 THEN u(t+) = −μPL(e) . u(t)

>0 THEN u(t+1) = −(1−μPS(e)) . u(t)

To implement the FLC on a digital computer:

u(t) = u(kT) and u(t+) = u((k+1)T)

where T is the sampling time.

R1:

IF e(kT) = PL AND e& (kT) < 0

 

THEN u((k+1)T ) = μ (e(kT)) . u(kT)

 

 

 

 

PL

R2:

IF e(kT) = PS AND e& (kT) < 0

 

THEN u((k+1)T) = (1−μ (e(kT))) . u(kT)

 

 

 

 

PS

R3:

IF e(kT) = NL AND e& (kT) < 0

 

THEN u((k+1)T ) = −μ (e(kT)) . u(kT)

 

 

 

 

NL

R4:

IF e(kT) = NS AND e& (kT) < 0

R5:

THEN u((k+1)T ) = −(1−μNS(e(kT))) . u(kT)

IF e(kT) = NL AND e& (kT) > 0

 

THEN u((k+1)T ) = μ (e(kT)) . u(kT)

 

 

 

 

NL

R6:

IF e(kT) = NS AND e& (kT) > 0

 

THEN u((k+1)T ) = (1−μ (e(kT))) . u(kT)

 

 

 

 

NS

R7:

IF e(kT) = PL AND e& (kT) > 0

 

THEN u((k+1)T ) = −μ (e(kT)) . u(kT)

 

 

 

 

P L

R8:

IF e(kT) = PS AND e& (kT) > 0

 

THEN u((k+1)T) = −(1−μPS(e(kT))) . u(kT)

where e&

(kT) ≈

1

[e(kT) − e((k−1)T)], with initial conditions

 

 

 

 

T

y(0) = 0,

e(−T) = e(0) = r − y(0), e& (0) =

1

[e(0) − e(−T)] = 0

 

 

 

 

 

 

T

C. Defuzzification

Select membership functions for the different control outputs from the rule base

μN

1 μZO

μP

 

 

 

 

 

u

–H

0

H

 

Figure 5 Typical membership functions for u

Then, the overall control signal, u, is generated by a weighted average formula:

N

åμiui (kT )

 

i=1

N

 

 

, (mi ³ 0, åμi > 0)

u((k+1)T) =

N

å μi

 

i =1

 

i=1

 

where control outputs ui(kT), i = 1, ..., N=8 are from the rule base.

Overview of Conventional PID Controllers

In the time domain:

(i) P-controller

u(t) = KP e(t)

 

t

(ii) I-controller

u(t) = KI òe(τ) dτ

 

0

 

 

(iii) D-controller

u(t) = KD

d

e(t)

dt

Control gains, KP, KI, and KD, are constants to be determined in the design for set-point tracking and stability consideration.

r

+

e

 

KP

u

system

y

 

 

 

 

–

 

 

 

 

 

 

 

 

 

 

 

 

(a)

Proportional controller

 

r

+

e

 

t

u

 

y

 

KIò

system

 

 

–

 

 

 

 

 

0

 

 

 

 

 

(b)

Integral controller

 

r

+

e

 

KDd

u

system

y

 

 

–

 

dt

 

 

 

 

 

(c)

Derivative controller

 

 

 

Figure 6.

Conventional PID controllers

 

In the frequency domain:

(i) P-controller

U(s) = KP E(s)

(ii) I-controller

U(s) =

K I

E(s)

 

 

 

s

(iii) D-controller

U(s) = KD s E(s)

Use Laplace transform L{×} for continuous-time signals:

U(s) = L{ u(t) } and E(s) = L{ e(t) }

Use z-transform Z{×} for discrete-time signals.

r

+

KIò0t

 

 

 

+

u

y

e

 

 

 

 

 

 

 

 

 

 

 

+

 

system

 

 

−

 

 

 

 

 

 

 

 

KP

 

 

 

 

 

(a)

PI controller

 

 

 

 

 

 

 

 

 

K d

 

 

 

 

 

r

+

e

Ddt

 

 

+

u

y

 

 

 

 

 

 

 

 

 

 

 

+

 

system

 

 

−

KP

 

 

 

 

 

 

 

 

 

 

 

 

(b)

PD controller

 

 

 

 

 

 

 

 

 

 

KP

 

 

 

 

 

r

+

e

 

t

 

+

+

u

y

 

 

KIò0

 

+

 

system

 

 

−

 

dtd

 

 

 

 

 

 

K

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

(c)

PID controller

 

 

 

 

 

 

 

 

 

K ò0t

 

 

 

 

 

 

 

r

+

I

 

 

+

 

+

u

y

e

 

 

 

 

 

 

 

 

+

 

 

 

system

 

 

−

 

 

 

 

−

 

 

 

KP

 

 

 

d

 

 

 

 

 

 

 

 

 

KDdt

 

 

(d)

PI+D controller

 

 

 

 

 

 

 

Figure 7 Some typical combination of P, I, D controllers.