Добавил:
Опубликованный материал нарушает ваши авторские права? Сообщите нам.
Вуз: Предмет: Файл:

reading / British practice / Vol D - 1990 (ocr) ELECTRICAL SYSTEM & EQUIPMENT

.pdf
Скачиваний:
3
Добавлен:
17.07.2023
Размер:
30.18 Mб
Скачать

Uninterruptable power supply (UPS) systems

STATIC SWITCH

a

I a

 

I

OF

 

 

N NORMAL POSITION

I

I

MAINTENANCE

POS TiON

BY-PASS SWITCH

I A N'ENANCE POSITION

AT PASS SUPPLY 50,1Z NOMINAL

RED &BRIE PHASES ONLY

TO 4 , 5V

(gLAYN vT EvE DBNIFTt um ENT

Fic. 1.34 Littlebrook D power station — unit GIS illustrating maintenance by-pass switch

being 48 hours. In order to minimise time to repair a faulty inverter system a spare set of inverter system components is provided.

Station GM system

The station GIS system has two inverter systems, each including an associated lead-acid battery, 415 V station

GIS switchboard and a distribution network as indicated on Fig 1.36.

Either of the two inverter systems is capable of supplying the total normal station load and each battery is rated for a 30 min standby duty. This makes it possible to operate with one out of service if necessary. Under normal operating conditions the load is shared as equally as possible between the two inverter systems.

Transfer of the load from one inverter to another is only possible with a break of up to 100 ms, using the changeover contactors on the local distribution units.

53

Following the problems experienced

Efectrical system design

Chapter •

 

 

UNIT GUARANTEED INSTRUMENT SUPPLIES DISTRIBUTION BOARD

STAND. INORMAL

STAND

FIG. 1.35 Unit GIS distribution switchboard

Local distribution units are provided for each 110 V single-phase supply point, each comprising two singlephase main and standby transformers, changeover contactors, switches and distribution switchboard as indicated on Fig 1.37. These are located around the station at suitable load centre positions.

Each 110 V AC GIS switchboard has an automatically connected standby supply arranged via changeover contactors.

The changeover scheme is almost identical to that previously described in the unit GIS section, except that a supply priority selector switch is provided.

Following a loss of supply from an inverter and its associated bypass supply, the 415 V interconnector can be closed if a prolonged outage is expected. The load

distribution units affected are then transferred back to the 'main' supply in stages.

6.3.2 Drax power station schemes

There are six 660 MW coal-fired units at this station, also six 35 MW gas-turbine generators.

Unit GIS system

with the original scheme fitted to the first three units (Fig 1.30), a 30 kVA development inverter was installed on Unit 2 in 1978. The inverter system is identical to the Littlebrook D power station type.

The unit system for the first 3 units is basically identical to the Littlebrook D power station unit sys-

54

Gas turbine inverters

Uninterruptable power supply (UPS) systems

415V 50Hz

415V 50Hz

30kVA

415V 50Hz

LOAD CENTRE

1 OV 50Hz

Fla. 1.36 Littlebrook D power station — station GIS

tem. Units 4, 5 and 6 have two separate inverter systems per unit, one for the computer and the second for all other loads. The total unit load was estimated to be in excess of one 30 kVA inverter already developed and proved on Unit 2, hence the reason for two systems per unit.

Station GIS system This is similar to the scheme previously described for the Littlebrook D station GIS in Section 6.3.1.

Each gas turbine has a separate single-phase inverter of less than 5 kVA with 110 V output and 110 V DC input. These supplies are required to enable the gas turbines to start in the absence of normal AC supplies.

6.3.3 Heysham 2 power station

This is an advanced gas cooled reactor station with two reactors and two 660 MW generating units. The UPS systems can be broadly divided into two groups:

Essential UPS systems, i.e., those required for normal reactor operation and those which are necessary for post-trip cooling of the reactor.

Non-essential UPS systems, i.e., those which are not safety related. These are described in the section on unit and station UPS systems later in this chapter.

Each reactor is arranged into quadrants, each quadrant having two diverse modes of reactor cooling called X and Y. Consequently each quadrant has four independent UPS systems. The UPS system associated with one quadrant is shown on Fig 1.38.

415 V essential UPS system X The UPS system rating is 100 kVA and the output is 415 V. 3-phase and neutral, 50 Hz (nominal). Only essential loads are connected to this system. These are mainly control and instrumentation loads and various motors and valves. The previous advanced gas cooled reactors used motorgenerator sets for this duty.

55

Electrical system ds

 

Chapter 1

 

 

 

ci)

STATION GUARANTEED INSTRUMENT SUPPLIES DISTRIBUTION BOARD

(1

FIG. 1.37 Station GIS distribution switchboard

The system has been fully type tested to very stringent requirements, including seismic tests and 11 kW motor direct-on-line starts.

The UPS battery is capable of supplying the full UPS load for considerably longer than the 30 minutes specified.

110 V essential UPS system Y This system is designed to provide both 110 V AC and 110 V DC supplies. The inverter is rated at 6.3 kVA, 110 V, 50 Hz and DC output is rated at 50 A continuous load. The loads are mainly various control and instrumentation supplies.

A standby battery and charger are provided, which can supply the inverter and DC loads of the Y 'train'

or 110 V DC loads of the X train, This equipment is also seismically qualified and in order to minimise the common-mode failure probability diverse equipment is provided for the X and Y UPS systems.

Non-essential UPS systems Unit and station UPS systems which consist of four 150 kVA, 415 V, 50 Hz single-phase UPS systems are provided at this station. Each is made up of 3 x 50 kVA inverters, a 600 A, 360 V DC battery charger and a 200 kVA static switch. The system can be expanded to 200 kVA by adding another 50 kVA inverter and another battery bank for which the stands are already installed.

Inverters operate in a redundant mode of operation providing that the load does not exceed 100 kVA limit

56

UPS system

Uninterruptable power supply (UPS) systems

 

41ST ESSENTIAL SERVICES BOARO -

 

 

4 , 55 ESSENTIAL SERVICES ECAEIC. - Ay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

it$

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOT TALLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

"5:,'

ESSENTIAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPEN

 

 

LINI:%7EP.R.,PT.BLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER SU.PLY

 

 

 

 

 

 

 

 

 

 

 

 

 

12 , 55 , ALA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LAY

 

 

 

 

 

 

'2

3.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STANDBY TO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X OR Y SYSTEM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.,--doro

 

 

Or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1'05 ESSENTIAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STANDBY BATTERY LA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To ,• Dv DC ESSENTIAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOARD LAX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• 5N 50Hz

 

 

 

 

 

60Hz

 

 

 

 

 

 

 

 

 

 

 

3 PHASE A NEUTRAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SINGLE PHASE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63 K yA

 

 

 

1

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

"

 

 

 

ESSENTAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC DR,vES

 

 

 

 

 

 

 

NORMALLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPEN

 

 

 

 

 

 

 

 

A,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11 05 DC ESSENTIAL BOARD 7 AY

 

 

 

 

 

ESSEN -71AL LAS E.:',39,=

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.?N GLE PHASE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ooLiaLE Pc,E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1105 50Hz

NOTE. ESSENTIAL UPS SYSTEM REPEATED EON EACH QuA0HANT

SINGLE PHASE

 

DOUBLE POLE

 

FIG. 1.38 Heysham 2 power station — essential X and Y UPS systems

(or 150 kVA when up-rated to 200 kVA). The scheme is illustrated on Fig 1.39.

Unit Each unit has an UPS, 415 V, 50 Hz, double-pole unit UPS switchboard and a distribution network. The maximum step-down transformer rating is 16 kVA and the loads are switched-in sequentially to avoid excessive inrush current and undesirable transfer to the bypass supply.

The following loads are supplied from this system:

Those which are required for post-incident monitoring and recordings following a main unit trip.

Those which because of stringent supply requirements would not have adequate reliability if operated from the electrical auxiliary system only.

Those which are required for the main unit shutdown.

The equipment upon which the reactor safety case depends is not connected to this system.

Local distribution units are provided for each 110 V single-phase supply point, each comprising two singlephase main and standby transformers, changeover contactors, switches and distribution switchboard.

These are located around the station, in the control block, etc., at suitable load centre positions. This type of distribution unit is mainly used for loads which require a single supply of high availability.

Loads which require two battery-backed supplies, e.g., microprocessor systems with plant input and output, derive one supply from the unit UPS system and the other from the station UPS system via step-down transformers.

Station UPS system This comprises two UPS systems, t wo 415 V, 50 Hz, double-pole station UPS boards

57

0c)

 

 

415V ESSENTIAL SERVICES BOARDS

 

415V ESSENTIAL SERVICES BOARDS

 

 

7DY

••••=

icy •1==

 

EDT'

8DX ■■■=

 

7CX

8C y

7DX

 

 

 

 

 

 

 

 

 

 

fi

 

415V STN

 

415V STN

 

415V LINIT

UPS7

UPS8

UPSE

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

a-oeci-i

 

 

a-cea-1

 

415V 1PH 50Hz

 

o-cea-I

415V 1PH 50Hz

1 50 (200) KVA

 

 

 

 

 

 

150 (200) KVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

415V UNIT UPS BOARD 7

6

FROM 415V STATION

TURBINE SERV BD 7

TYPICAL 110V 50Hz

C & 1 SUPPLIES LOAD

CENTRE UNIT 7

461

1' '

 

 

 

 

 

 

 

 

 

 

 

 

415V STATION

 

 

415v STATION

 

 

 

 

 

 

 

 

UPS BOARD 7

 

 

UPS BOARD 8

 

 

4I5V UNIT UPS BOARD 8

 

 

 

 

 

 

 

 

-6

-6

6

-6

 

 

 

 

 

 

 

 

 

6 6 6

 

 

 

 

 

B

FROM 415V STATION TURBINE SERV BD 8

TYPICAL 110v 50Hz

& I SUPPLIES LOAD CENTRE UNIT 8

UNiT

 

 

 

 

 

UNIT

MAIN

 

 

 

STANDBY

COMPUTER

 

 

 

COMPUTER

7

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

STANDBY

NORMAL

 

 

 

 

 

 

 

 

 

 

110V 50Hz

 

 

 

1 HOUR FIRE BARRIER

UNIT

STANDBY COMPUTER

8

NORMALLY

UNIT MAIN ' OPEN

COMPUTER 8

isTANDBY• • NORMAL

 

 

 

 

1 0v 50Hz

 

 

II

IL

II

II

II

II

II

I

II

II

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BATTERY BACKED

 

NON-BATTERY

 

 

 

 

 

 

 

 

 

 

 

 

BATTERY BACKED

NON BATTERY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLIES

 

BACKED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLIES

BACKED SUPPLIES

 

 

SUPPLIES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a

 

 

 

 

 

 

 

a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8A

 

 

 

 

 

 

 

7A

 

7B

 

II

 

 

8B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

110V 501-1z

 

 

 

 

 

110V 50Hz

 

 

 

 

 

 

 

 

 

 

 

II

II

II

II

II

II

NORMALLY

II

II

II

II

II

II

OPEN

FiG. 1.39 Heysham 2 power station — unit and station UPS systems

aqsap walsAs Iepploal3

Inverter input DC voltage too low.

Uninterruptable power supply (UPS) systems

and a distribution network. Either of the two UPS systems is capable of supplying the following loads:

Total station load.

Standby compuier for one unit.

Standby supply to loads of one unit which require two battery-backed supplies, e.g., microprocessor

system dth plant input and output.

Under normal operating conditions the station load is shared as e wally as possible between the two UPS systems. Transfer of the station loads from one UPS system to another is off-load at the 110 V load centres. An interlock is provided using coded keys to prevent parallel operation of the supplies derived from the two station UPS systems. Only the following C and I station loads are connected to the station UPS Boards:

Those which are required for post-incident monitoring and recordings following loss of station AC

supplies.

Those which because of stringent supply requirements would not give adequate standards of reliabi-

lity if operated from the electrical auxiliary system only.

Those which are required for shutdown of any common services.

6.4 System configuration and method of operation

Each UPS has the following main components (see Fig 1.34):

Battery charger.

Battery.

Inverter.

Static switch.

Maintenance bypass switches.

The charger and bypass AC supplies operate normally with identical frequency. Under adverse system conditions the supplies could operate at different frequencies.

Under normal operating conditions the UPS is in service and the load is normally supplied from the im, erter. The battery charger maintains the battery on float charge.

In the event of failure of the charger supply the load continues to be supplied by the battery/inverter. The load is transferred automatically from the inverter to the bypass supply without interruption in the voltage waveform under any of the following abnormal conditions, providing the inverter is synchronised in both phase and frequency to the bypass supply:

Inverter failure.

Output voltage outside the set limits.

Excessive inverter overload or load inrush current.

Short-circuit on the load side.

If the inverter is not in phase with the bypass supply under the above abnormal conditions, then the load is transferred automatically from the inverter to the bypass supply with a break of at least 60 ms and less than 100 ms.

The load re-transfer, back to the inverter, is completed automatically without interruption in the voltage waveform when the inverter has returned to normal and maintained a stable output for approximately 5 to 10 seconds.

Static switch redundancy

Means are provided within the static switch to parallel automatically the bypass power semiconductors, following a transfer from the inverter to the bypass supply, using a contactor or circuit-breaker. The control and power circuits are arranged to achieve a matching level of redundancy between the static and electromechanical portions of the static switch. In the event of the static portion failing to operate, the electromechanical portion operates to transfer the load automatically and/or manually from the inverter to the bypass supply with a voltage break of at least 60 ms and less than 100 ms. Following a transfer to the bypass supply, both static and electromechanical portions usually continue to operate to achieve maximum redundancy. Both portions are fully rated.

6.5 System considerations and components

6.5.1 Voltage regulation

With the inverter in service the voltage at the terminals of any instruments, control equipment and computers is maintained within + 6% to - 6% of nominal (steady state) voltage. This is achieved as follows for 415 V UPS systems:

 

Regulation

Voltage

 

 

adjustment

Inverter

+2%

95-105%

415 V cable between

 

 

inverter and load

 

 

centre

2%

 

415/115 V transformer

2%

100% +5%

110 V cable between

 

 

load centre and

2%

 

instrument or computer

 

 

terminals

 

 

59

• Environmental conditions

Electrical system design

Chapter 1

 

 

Output voltage and number of phases — 110 , 50 Hz single-phase output is usually used for ratings up to 10 kVA and where distribution cables are relatively short. One pole of the output is connected to earth and a 415/110 V bypass transformer is included.

A 415 V, 50 Hz single-phase output is used for ratings above 10 kVA, particularly where distribution cables are long. The largest single module used today is 50 k VA. The inverter output is not earthed, but is continuously monitored with an insulation monitor.

A 415 V, 50 Hz 3-phase output is used in exceptional cases where load requires 3-phases, e.g., motors. The largest rating used at present is 100 kVA.

6.5.2 UPS system loads

In order to specify a UPS system it is necessary to define the load in detail as follows:

Load profile versus time.

Loads requiring or generating harmonic (especially even) currents.

Loads requiring the circulation of a DC current.

Load steps.

At existing installations, a survey of available loads is undertaken where access is possible. Measurements are taken using a two-channel digital oscilloscope with magnetic storage. The analysis of the waveforms obtained is carried out using a portable computer and a 'HARMD 1 program developed by the CEGB. A typical waveform and harmonic analysis are shown in Fig 1.40.

6.5.3 Step-down transformers

These have been developed to minimise the inrush currents and the associated voltage drops on the system, up to a rating of 16 kV. No ferro-resonance problems have been experienced with these transformers when switching them onto inverters.

The transformers are of the naturally air cooled single-phase double-wound type and are suitable for operation on a nominal 415 V, 50 Hz supply derived from a single-phase inverter or from two phases of the 415 V, 3-phase, 4-wire, 50 Hz (nominal), solidly earthed system with a maximum symmetrical shortcircuit fault level of 31 MVA.

The transformers comply generally with BS171, BS3535 and BEBS T2 (1966) Section 5 where applicable.

The winding insulation is Class F to BS2757 and is non-hygroscopic, but the design is such that the temperature rise limits given in 13S3535, Table 2D are not exceeded for Class E materials. The use of asbestosbased materials is not permitted.

A metallic screen is provided between the windings, one end of which is brought out and connected to the earth terminal of the transformer.

Each transformer is provided with a facility for off-load tapchanging on the 415 V primary winding. Voltage variations of +5% in 2.5% voltage steps. The method of tapchanging is by means of bolted li nks.

The nominal flux density at rated voltage and frequency and with the transformer connected on the principal tapping is specified not to exceed 1.0 tesla. The impedance voltage at rated current and frequency does not exceed 2% of the rated voltage on any tapping.

The transformers are capable of operating with nonlinear loads having relative current harmonic content of up to 50%.

The basic transformer parameters are given in Table 1.1.

6.5.4 Standby and spares philosophy

In the event of inverter failure, automatic transfer to mains supply occurs. The quality of the mains supply is acceptable for the UPS outage time, which does not therefore justify the provision of a standby UPS system.

In order to minimise time to repair, a spare set of inverter system components is kept at each station.

6.6 UPS equipment specification

As part of the development work on UPS systems, detailed technical requirements and documents for purchasing UPS equipment have been written to ensure that identified problems are overcome.

The following are brief details of the main technical requirements:

Battery capacity The system should be capable of maintaining specified conditions for 30 minutes following complete failure of all incoming AC supplies.

The equipment should meet environmental class B3 requirements of specification CEGB-EES (1980). The ambient temperature range should be taken to be + 5 ° C to 40 ° C with air temperature not exceeding 35 ° C average in any one day and not exceeding 20 ° C average in any one year.

The equipment enclosure shall provide a degree of protection to Code IP31 of BS5490.

Life of equipment All equipment should have a designed operating life of 30 years.

Reliability A high degree of reliability and availability is required and the following reliability targets are specified:

 

UPS

UPS

 

3-phase output

1-phase output

 

MTBF (years)

MTBF (years)

Charger

10

10

Inverter

2

3

Static switch

10

15

Reliability calculations are based on mean time to repair a UPS system of 48 hours.

60

Uninterruptable power supply (UPS) systems

DD DFESET REMOVED

-

MULTIPLY AMPLITUDES BY 1C0 % v v AND TIME VALUES BY O00020 $

-

 

 

 

 

 

MULTIPLY AMPLITUDES BY

2555 A V AND TIME VALUES By 0 000020 5

Harmonic Analysis using Program HAMAD

 

 

 

Number of points for analysis :1024

Highest harmonic order 255

Number of cycles averaged

 

4

 

 

 

Fundamental Frequency (Hz).

50.03

Voltage

Current

Total RMS

 

 

-236- - 21V

7 31A

Peak value - - - - - - - - - - - - -

- -

- - - - - - - - -

- - 319.29V - - - - -

16.01A

PeakiFtMS rano . — - - - - - - - -

-

- - - - - - - - -

- - 1.35

2_19

 

Maximum harmonic component rRMS) _ _ _ _ — 236_05V

6.19A

DC level removed -

 

 

-4.28V - - - - -

-0.40A

Relative fundamental content -

- -

- - - - - - - - -

- - 99.9% - - - - -

847%

 

Relative harmonic content - - - -

-

- - - - - - - - -

- - 3 7% - - - - -

53.2%

 

High frequency content ,.2 k Hz) _

 

- - 03% - - - - - -

0.6%

 

Total apparent power _ - - - - - -

1.727kVA

Total active power - - - - - -

1.383kIN

Power factor - - - - - -

0 801

-

X

00

0t.

AAWWWWNWNN

 

Voltage

 

 

 

Cur writ

-

 

0

471,

eo

 

 

a 2

 

0 G

aulm.Nrw,i.moma-wamarro,rmm-cn , c -,:towacoaar-coaa.. -:rta.vru,nar ma .

—NC.0,J10,4p0A00

 

 

,M!

 

 

 

0

 

0 -0000000000 •0100-rn 'ft, roA (n.-0

CD

 

00 000000000000000000ri

 

 

,

 

 

 

 

 

 

 

00 -

 

 

 

 

tn

 

 

00,10 —

 

 

 

 

 

 

 

 

 

 

 

 

'0

 

 

 

 

 

 

 

 

 

 

DC components are excluded from all other parameters

CD

o c‘iorioa•i,nu,,acn o .70t0(900,,. 141,VNLO7k0 , 40 ,1104[2.01.Nt

FIG. 1.40 Typical voltage and current waveform analysis

61

Electrical system design

 

 

 

 

 

 

 

Chapter 1

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 1.1

 

 

 

 

 

 

 

 

Step-down transformers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BS posker rating, kVA

 

16

10

8

6.3

4

2.5

1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of phases

 

1

1

1

1

1

I

1

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency (nominal), Hz

 

50

50

50

50

50

50

50

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated primary voltage, V

 

415

415

415

415

415

415

415

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated secondary voltage, V

 

115

115

115

115

115

115

115

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltaee ratio at no-load

 

415/

415/

415/

415/

415/

415/

415/

 

 

on the principal tapping

 

115

115

115

115

115

115

115

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum impedance on any tapping, 'Yip

 

2

2

2

2

2

2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuse links current

 

50

32

25

20

15

10

6

 

 

rating at 415 V

 

 

 

 

 

 

 

 

 

 

(to 13588-2, 1975, Class QI), A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum inrush magnetising current (peak), A

 

272

170

136

107

68

43

27

 

 

 

 

 

 

 

 

 

 

 

 

Maintenance and repair The equipment, excluding

 

batteries, should not require maintenance more fre-

 

quently than once annually. The mean time to repair

 

the equipment should not exceed two hours.

Transformers and inductors

These should have

 

non-hygroscopic insulation with the temperature rise

 

necessary to give the specified life at rated output.

Power semiconductor devices

The temperature rise

 

at the device reference point (case) shall not exceed

 

50 ° C at the rated output. The maximum permissible

 

temperature rise should not exceed 70 ° C under any

 

operating conditions. For fan cooling this should

 

apply with any single fan out of service.

Remote alarms and indications All locally indi-

 

cated faults should be grouped into the following

 

remote alarms or indications:

 

(a)UPS system failure

(b)Inverter in service

(c)Inverter on battery

(d)Battery in service

(e)Static switch inhibited.

Reliability monitoring A non-resetting counter and elapsed time indicator should be provided on UPS systems above 10 kVA rating for each of the following operating conditions:

(a)Inverter in service

(b)Bypass in service

(c)Static switch inhibited

(d)Inverter on battery.

6.7UPS equipment performance requirements

Charger output voltage

The charger output voltage should be automatically maintained within ± 1 % of the voltage setting when operating under any combination of the following conditions:

Load between 0 to 100% of the rated output.

Nominal input AC voltage ± 10o.

Frequency 50 Hz +5%.

Specified environmental conditions.

Inverter output voltage tolerance (steady state)

The output voltage should be maintained within +2% of the voltage setting when operating under any combination of the following conditions:

Load between 0 to 100 07o of the rated output over the entire inverter input voltage range.

Specified environmental conditions.

Load power factor between 0.7 lag to unity.

Output voltage adjustment

The output voltage and adjustment shall be stepless over the range of ±5% of nominal voltage.

62

Соседние файлы в папке British practice