Добавил:
Опубликованный материал нарушает ваши авторские права? Сообщите нам.
Вуз: Предмет: Файл:

reading / British practice / Vol D - 1990 (ocr) ELECTRICAL SYSTEM & EQUIPMENT

.pdf
Скачиваний:
9
Добавлен:
17.07.2023
Размер:
30.18 Mб
Скачать

 

 

 

 

 

 

Future trends in development and application

 

 

 

Mien the dielectric strength across the arc gap at a

than air. The need to seal the gas system in order

natural zero becomes sufficient to prevent the recovery

to exclude air and moisture, together with problem

 

 

oe (across the gap) re -establishing the current flow.

experienced with compression and storage of recycled

 

j :a llows, therefore, that a dielectric strength suffi-

gas, led to the derivation of the 'puffer' interrupter,

 

fo-

 

 

 

in which a minimal overpressure is held for insulation

 

 

o bring about interruption of a high value of

'

ivrent

,

 

, a short-circuit current, will be more severe

purposes and where, during the interrupting cycle, a

 

 

local blast of gas is created in the region of the arcing

 

necessary to deal with much lower values. Thus

 

 

„thics

of current relatively low, by comparison

contacts by a direct-driven piston/cylinder unit.

 

i(11

the maximum capability of the interrupter, which

At transmission voltage levels, development con-

 

,usceptib'e to chopping, i.e., forced to zero before

tinues into interrupters of increasing breaking capacity,

,, r e

 

be instant of a natural zero.

the trend towards

a simplification of units for use

 

Vacuum contactor interrupters in combination with

at voltages from 1

kV to 36 kV has also progressed.

1113C fuses to form motor switching devices, are avail-

The puffer principle is presently retained

at these

jblc

 

rated voltage from 1 kV to 7.2 kV. Such units

voltages for short -circuits of 15 - 20 kV and above.

 

 

 

successfully applied in limited quantity in

Designs are also available at low fault levels and are

11

,1 %e been

LK power stations and it is anticipated that their

continuing in development by a number of manufac-

 

J oe will increase, particularly where they can demon-

turers worldwide to higher fault levels, using various

grate a

first cost advantage over air-break types. Fig-

forms of self-extinction system, including electromag-

ures

5.69 and 5.70 illustrate examples of controlgear

netic deflection and rotating arc techniques.

The self-

i.c..ituring vacuum interrupters in association with HBC

extinguishing interrupter results in designs of switchgear

fuse

protection.

with minimal requirements in operating energy, whilst

 

Vacuum circuit-breakers have also been successfully

the insulating and heat conductive capabilities of SF 6

a pplied in UK power stations but await full recogni-

enable unit sizes to be held to a minimum.

 

tion as an alternative to the current standard air-break

The specialised metalclad and phase-segregated

units. The trend to wider application of vacuum circuit-

generator circuit-breaker is now available with SF 6

breakers can be expected to follow demonstration of

technology for all but the very highest normal cur-

the highest

short-circuit breaking and normal current

rent and fault ratings. Short-circuit breaking capacity

capacities appropriate for the largest power plant sys-

up to 100 kA has already been achieved using self-

tems, i.e., 40 kA and 3150 A respectively. Rated volt-

extinguishing principles and it can be expected that

ages of 3.6 kV and 12 kV will be required and although

development will continues, resulting ultimately in the

a motor switching duty at 11 kV is specified, this will

phasing out of air-blast switchgear for generator switch-

relate to large motors i.e., 1000 kW and above.

ing duties.

 

 

 

 

 

 

 

 

The exploitation of the electrical insulation proper-

 

 

 

S F6

 

ties of SF6 in isolation from its arc interrupting

10.6

switchgear

characteristics occurred in the late 1960s in the UK,

Research into the use of SF6 (sulphur-hexafluoride)

when trial installations of multiple-unit vacuum inter-

rupters immersed in SF6 gas were made on the 132 kV

12L1S

for electrical insulation purposes can be traced

system. Gas insulation, also employed at EHV levels

hack

to the 1930s but it was not until the 1950s that

for current and voltage transformers, enables internal

its performance as an insulation medium was noted.

dimensions to be minimised. Also, because a small

‘,1: 6 is odourless, colourless, non-toxic and non-flam-

overpressure is employed, the enclosure gives full en-

inable.

At normal temperature and pressure its spe-

vironmental protection. More recently, some European

cific

density is five ti mes that of air and its thermal

manufacturers have introduced HV metalclad switch-

transfer

coefficient 1,6 times that of air. Its dielectric

gear with SF6 gas insulation and oil or vacuum inter-

strength

at only 3 atmospheres absolute is comparable

rupters. Whilst such equipment becomes particularly

to that of electrical insulating oil.

attractive because of space saving at voltages in the

 

Initial application of SF 6 to switchgear was at trans-

range of 24 kV to 72 kV, it is less important at power

inksion voltage levels where it was a logical develop-

station auxiliaries system voltages, especially if available

ment

of the

air-blast principle to employ a gas other

only with fixed type isolation.

 

423

JeeEloiluop pue

Flo 5.69 Switchboard formation of control gear featuring vacuum interrupters in association with IIBC fuse protcciion Jr 3.1 kV service I nclusirial Controls Lod)

(see also Colollr photograph betwceil pp 496 .1 mi 497)

Future trends in development and application

Fit„ 5.70 Example of control gear featuring vacuum interrupters in association with HBC fuse protection — for 3.3 kV service, showing the demonstration of the circuit earthing switch (GEC Industrial Controls Ltd)

(see also colour photograph between pp 496 and 497)

425

Switchgear and controlgear

Chapter 5

 

11Bibliography

11.1British Standards {BS)

Where an International Electrotechnical Commission (lECI number is given, the British Standard is identical with the IEC document,

BS4727: Part 1: Glossary of electrotechnical, power, telecommunication, electronics, lighting and colour terms: Part 2: Terms particular to power engineering Group 06. Switchgear and controlgear terminology (including fuse terminology): 1985

BS5311: Parts 1-7: Specification for a.c. circuit-breakers of rated voltage above 1 kV: 1976

8S5227: Specification for a.c. metal-enclosed switchgear and controlgear of rated voltages above 1 kV and up to including 72.5 kV: 1984

BS4752: Part 1: Specification for switchgear and controlgear for voltages up to and including 1000 V a.c. and 1200 V d.c. Part 1. Circuit-breakers: 1977 (IEC 157-1975: IEC 157-1A: 19761

88775: Part 2: Specification for contactors: Part 2, a.c. contactors for voltages above 1 kV and up to including 12 kV: 1974

BS3659: Specification for air-break circuit-breakers for alternating current systems above 1 kV and up to and including 11 kV: 1963 ( withdrawn and replaced by BS5311)

BS5424: Part 1: Specification for controlgear for voltages up to and including 1000 V a.c. and 1200 V d.c. Part 1, Contactors: 1977 1IEC158-1: 1970, IEC158-1A: 1975)

BS5419: Specification for air-break switches, air-break disconnectors, air-break switch disconnectors and fuse-combination units for voltages up to and including 1000 V a.c. and 1200 V d.c.: 1977 1IEC408: 19721

BS5486: Part 1: Low-voltage switchgear and controlgear assemblies. Part 1, Specification for type-tested and partially type-tested assemblies (general requirements): 1986 1IEC439-1: 1985)

BS5490: Specification for classification of degrees of protection provided by enclosures: 1977 (IEC529: 1976)

9S1432: Specification for copper for electrical purposes. Strip with drawn or rolled edges: 1970

B52898: Specification for wrought aluminium and aluminium alloys for electrical purposes. Bars, extruded round tube and sections: 1970

8S5253: Specification for a.c. disconnectors (isolators) and earthing switches of rated voltage above 1 kV: 1975

1352692: Part 1: Fuses for voltages exceeding 1000 V a.c. Part 1. Specification for current-limiting fuses: 1986 (IEC2821: 1985)

8S3938: Specification for current transformers: 1973 (19831

BS3941: Specification for voltage transformers: 1975 119821

BS162: Specification for electric power switchgear and associated apparatus: 1961

BS6581: Specification for common requirements for high-voltag e switchgear and controlgear standards: 1985 IIEC694: 1980)

854941: Part 1: Specification for motor starters for voltages up to and including 1000 V a.c. and 1200 V d.c.: 1979 1IEC292-1: 1969, IEC2921A: 19711

BS142: Electrical protection relays: 1982

BS158: Specification for the marking and arrangement of switchgear busbars, main connections and small wiring: 1961 (withdrawn)

BS3535: Specification for safety isolating transformers for industrial and domestic purposes: 1962

BS88: Parts 1 and 2: Specification for cartridge fuses for voltages up to and including 1000 V a.c. and 1500 V d.c: 1975 11982)

854343: Specification for industrial plugs, socket-outlets and couplers for a.c. and d.c. supplies: 1968

85196: Specification for protected-type non-reversible plugs, socket outlets, cable couplers and appliance-couplers with earthing contacts for single phase a.c. circuits up to 250 volts: 1961

11.2 Electricity supply industry (ESI) Standards

ESI Standard 37-1: 415 V a.c. switchgear, controlgear and fusegear

ESI Standard 37-3: A.C. metal-enclosed switchgear and controlgear of rated voltages 3.6 kV and 12 kV: Part 1: Circuit-breaker equipment (air-break): Part 2: Fused switching device equipment of 3.6 kV rated voltage

ESI Standard 50-18: Design and application of ancillary electrical equipment

11.3 Other relevant documents

Memorandum on the Electricity Regulations (SHW 928): UK Factories Act: 1961

DEF 59-100 Part 1: Fuseholders, carriers and bases electrical fuse (Block and extractor post types)

DEF 59-96 Part 1: Fuselinks electrical

Power Circuit Breaker Theory and Design: Edited by C.H. Flurscheim: Published by Peter Peregrinus Ltd

426

 

CHAPTER 6

 

Cabling

Introduction

5.5.6 Plant-mounted devices

5.5.7 Application of short-time fireproof cables

2 Cable systems and layout

6 Cable support systems

2.1 Segregation requirements

6.1 Introduction

2.1.1

Segregation requirements for fossil-fired and hydro

6,2 Design philosophy

 

power stations

2.1.2 Segregation requirements for nuclear power stations

6.3 Basic system components

2.1.3 General layout requirements

6.4 System design and application

 

 

6.5 Seismically qualified cable supports

3 Cable types

7 Cable installation practices

3.1 11 kV cables

7.1 Introduction

3.2 3.3 kV cables

3.3 415 V cables

7.2 The need for cable restraint

3.4 Cables for DC power circuits

7.3 Cable cleating design parameters

3.5 Multicore control cables

7.4 Cleating philosophy for cables installed on steel-

3.6 Multipair control cables

work

3.7 Short-time fireproof cables

7.4.1 Straight horizontal runs on ladder racks

3.8 Linear heat detecting cables

7.4.2 Straight vertical runs on cantilever arms

3.9 Developments in cable design

7.4.3 Horizontal runs in a vertical plane

3.10 Thermal ageing

7.5 Installation practices for cables installed other than

3.11 Mechanical performance

on support steelwork

3.12 Electrical tests

7.5.1 Direct in ground

4 Power cable system design

7.5.2 Installed in ducts

7.5.3 Routing in concrete troughs

4.1 Introduction

7.6 Cable pulling

4.2 Current rating for continuous operation

8 Cable performance under fire conditions

4.2,1 Maximum conductor temperature

8.1 Tests on a single cable or wire

4.2 ,2 Ambient temperature

4.2.3 Conductor temperature rise

8.2 Cable installations having reduced fire propagation

4.2.4 Permissible current ratings

8.3 Oxygen index tests

4.2.5 Rating factors

8.4 Smoke tests

4 2.6 Single-core cables in parallel

8.4.1 Test methods

4.3 Fault current and duration

8.4.2 Use of test information

4.3.1

Short-circuit faults

8.5 Corrosive gas emissions

4.3.2 Earth faults

8.6 Toxic gas emissions

4.3.3 Overload current

9 Cable accessories

4.4 Motor starting

 

4.4.1 Motor starting current

9.1 Cable glands

4.4.2 Motor starting times

9.1.1 Background to gland design

4.5 Cable voltage regulation

9.1.2 Gland construction

4.6 Cable system design

9.1,3 Gland sizing

4.6.1 Feeder circuits

9.1.4 Installation

4.6.2 Motor circuits

9.2 Power cable conductor terminations

4.7 Practical examples

9.2.1 Fittings for aluminium conductors

4.7.1 Feeder circuits

9.2.2 Fittings for copper conductors

4.7.2 Motor circuits

9.2.3 Formed terminations

5 Control and instrumentation cable systems

9.2.4 Bolting terminations to equipment

9,3 Conductor terminations for control cables

 

 

5.1

Signal levels

9.3.1 Crimped conductor terminations

5.2 Cable types

9.3.2 Wire wrapped terminations

5.3 Cable interference

9.4 11 kV terminations

5.3.1 Interference in multipair cables

1 0 Fire barriers

5.3 .2 Interference in multicore cables

10.1 Introduction

53.3 Circuit considerations

5.4 Control and instrumentation cable system design

10.2 Performance requirements

5.5 Cable network system using jumpering

10.2.1 Magnitude and type of fire

5.5.1 Basic principles of cable network

10.2.2 Proximity of the fire to the barrier

5.5.2 Switchgear and interlocking equipment

10.3 Fire test requirements

5.5.3 Design of cable network systems

10.4 Additional performance criteria

5.5.4 Application of cable network systems

10.5 Fire doors

5.5.5 Testing and commissioning of a control network system

10.6 Penetrations

427

Cabling

Chapter 6

 

11 Earthing systems

11_1 Introduction

11.2 Differences in earth potential

11.2,1 Definiti ons

11.2.2 Acceptance criteria 11,3 Earthing systems design

11.3.1Systems having remote neutrals

11.3.2Faults on internal systems

11_3 3 Lightning protection

11.3.4Additional considerations

11.4Earth electrodes

11.4.1Sheet steel piles

11.4.2Cylindrical steel piles

11_4.3 Earth rods

11.4.4Earth strip

11.5Earth network construction and plant bonding

11.5.1Main earth network

11.5.2Instrument earth network

11.5.3Earth bond cable sizes

11.5.4Plant bonding arrangements

11.6Testing

11.6.1Earth resistivity measurement

11.6.2Earth electrode resistance measurement

11.6.3Commissioning tests

11.6.4Routine tests

12Lightning protection

12.1General requirements

12.2Lightning magnitudes and risks

12.3Application of requirements to power stations

12,4 Protection system design

12.4.1 Main and gas turbine chimneys 12,4,2 Main buildings

12.4.3Other buildings

12.4.4Buildings requiring special considerations 12,4.5 Fuel oil storage tanks

12.4.6Flammable gas production and storage plant

12.5Assessment of risks of sideflashing and interference

12.6Inspection, testing and records

13Lighting, heating and small power systems

13.1Introduction

13.2Lighting system design

13.2.1Objectives

13.2.2Specification

13.2.3General planning

13.2.4Detailed planning

13.2.5Appraisal

13.3Emergency lighting systems

13.4Lighting of special areas

13.4.1Battery rooms and chlorination plant rooms

13.4.2Hydrogen plant (Division 1 and Division 2 areas)

13.4.3Central control rooms

13.4.4Hazard warning lights

13.5Supplementary heating and minor power systems

13.6Distribution system

13.6.1General

13,6.2 Isolation and switching of individual fittings

13.6.3AC supplies

13.6.4DC supplies

13.6,5 Cabling

14Design and management techniques

14.1Introduction

14.2Planning

14.3Design

14.3.1Layout

14.3.2Cable support systems

14.3.3Information from plant contractors

14.3.4Cable systems and electrical circuit design

14.4Installation and contract management information

14.4.1Introduction

14.4.2The aims and functions of TPI cabling

14.4.3Designing

15References

Appendices

AValues of resistance and reactance for single-core elastomericinsulated cables I90° C maximum conductor temperature)

BValues of resistance and reactance for multicore PVC-insulated cables (70° C maximum conductor temperature)

CCurrent ratings for elastomeric-insulated cables

D Current ratings for PVC-insulated cables

ERating factors for variations in thermal parameters

FCross-sectional area of armour wire

G415 V motor parameters and selected fuse sizes

HMaximum cable route lengths

IMain protection for feeder and motor circuits

JAdvantages and disadvantages of various lamps used for lighting power station interiors

1 Introduction

The cabling system within a power station performs the essential function of connecting mechanical, electrical and control equipment together to form a total working entity. Cabling systems therefore form an interface between a variety of plant supplied under a large number of electrical and mechanical contracts, and information has to be drawn from each of these to complete the cable system design. During the power station construction period cabling systems are dependent on plant having been installed so that connections can be completed. It can therefore be seen that cabling is an important item in the organising and planning of design functions and site activities.

Furthermore, the number of cables has steadily increased with the size of boiler/turbine units, mainly due to the growth of control and instrumentation func-

tions. The number of cables installed on a power station varies with the type of plant, i.e., hydro, coal, oil or nuclear. Considering 660 MW units, the quantities of cables involved at the time of writing for recent projects are

 

 

Cables

Cables for

Total

 

 

per unit

station services

 

Littlebrook D

6630

6890

26 780

(3 units, oil-fired)

 

 

 

Drax Completion

7170

8850

30 360

(3 units, coal-fired)

 

 

 

Heysham

2

16 870

17 570

51 310

(2 units, nuclear AGR)

The average cable route lengths for these projects varies from 51 m on Littlebrook D to 59 in on Heysham 2 and 74 m on Drax Completion. This means that

428

 

 

 

Cable systems and layout

 

 

 

some 3030 km of cable will be installed on the Hey-

The criteria applied to conventional stations is that

sham

2 project. Considering Heysham 2 further, it is

the output of not more than one unit should be lost in

worthy of note that approximately 70% of the cables

a single cable fire. To segregate the equipment of one

re associated with control and instrumentation.

unit from another alone is not adequate, since units

a The types of cables used in power stations range

are normally dependent on common station services

from control and instrumentation multipair armoured

which must also be secure. It should also be realised that

a bi es having_ 0.5 mmconductors, up to 11 kV power

although a fire may be contained to involve only the

cables having a maximum conductor size of 500 mm 2 .

equipment of one unit, the smoke and fumes of the

In addition there are requirements for special cables

fire may cause further loss of generation due to the

suc h as linear heat detectors to sense fires and short-

evacuation of operations staff and as a result of dam-

ti me

cables which are designed to keep their

age to light current equipment from corrosive fumes.

 

In achieving the segregation necessary to prevent

integrity for a specified period under fire conditions.

The cable system also includes accessories such as

the loss of more than one unit it is also often possible

cable supporting steelwork, cable glands and conductor

to achieve a degree of segregation within a unit without

terminations. Power stations tend to have requirements

additional cost. This can be usefully applied to dupli-

which differ from normal industrial standards because

cated auxiliaries where the loss of one may cause a

of their size, complexity and the security needs of

reduction in output, but not necessarily a unit loss,

such high investment plant. Therefore very often na-

and can improve the security of duplicated services

ti onal and international standards are not appropriate

and hence reduce the risk of plant damage and pro-

and in house' standards have to be prepared. To ensure

longed outage.

that only approved equipment of the required standard

A basic summary of the requirements for segrega-

is installed in a power station, the CEGB operates a

tion is given in Table 6.1. It is important to note the

type approval system.

differences between basic requirements and optional

This chapter is designed to give a comprehensive

i mprovements to the security of the system that can

insight into cable system requirements including hard-

be made at no additional cost.

ware, layout, design and installation. It also covers

In conventional stations, all barriers provided for

items closely related to cabling such as earthing, light-

segregation requirements should have a minimum of

ing, heating and small power systems.

one hour fire rating. Where cables are installed direct

 

 

 

in the ground, a separation distance between segrega-

 

 

 

tion groups of one metre is considered adequate.

2 Cable systems and layout

2.1Segregation requirements

Before discussing layout in general, it is necessary to understand the segregation and separation requirements for various station types. The station layout, from the very beginning, has to take into account the disposition of ancillary plant and interconnecting cables to ensure that segregation requirements can be achieved. Segregation is provided to limit damage under accident conditions such as fire.

Segregation is defined as the physical division or isolation of one group of cables or plant from another by an enclosure or barrier of a certain specified fire rating. The barrier may be brick, concrete or special fireproof partitioning as described in Section 10 of this chapter, Separation is defined as the division of groups of cables by distance alone.

Segregation in fossil-fired and hydro plant is primarily provided to limit economic loss. However, in nuclear power stations it is provided for nuclear safety as well as economic reasons.

2.1.1 Segregation requirements for fossil-fired and hydro power stations

Segregation in fossil-fired and hydro power stations is provided to limit economic loss in the event of fire.

TABLE 6.1

Basic segregation requirements for conventional plant

Plant

Segregation requirement

 

 

Unit — Unit

Mandatory

Station A — Station B

Mandatory

Unit — Station

None

Main plant — Standby plant

Yes if no cost penalty

Main plant — Emergency DC or

Mandatory

guaranteed AC

 

Alternative DC tripping supplies

Mandatory

 

 

It is a basic requirement that cabling of one unit be segregated from the cabling of all other units. This must be achieved on all major cable routes by the provision of suitable fireproof enclosures and barriers to prevent spread of fire from one unit's cabling to another, and also to contain combustion products. In the case of turbine halls and common boiler houses, clearly it is not practical to enclose all minor cable routes to achieve segregation and, because of the limited amount of cables, there is no need to contain the combustion products. Therefore in the case of these minor cable routes, segregation is achieved by isolating one from the other by distance.

429

one-

Cabling

Chapter 6

 

 

Segregation requirements for station cables and plant will depend on the system design. When one station transformer is provided for each unit, electrical station services are provided on a unit basis. In this case, cables for these services will be segregated by fire barriers from the station services cables associated with other units. If, however, two station transformers are used to provide station services for the whole station, then a different solution is required. In this case, duplicated plant necessary for the operation of the station may be designated 'Station A' and 'Station B', and full segregation by fire barrier applied between the two designations. There is no need to segregate station cables from unit cables providing that in any one incident the total loss is not greater than one unit and/or half the station services. Main CW pumps are normally fed from a station system since these are installed hydraulically on a shared station basis. For CW pumps, cabling should be provided on a sufficient number of segregated routes such that no more than the output of one unit will be lost in a single incident. Where gas turbines are installed, these are normally on a unit basis and segregation should be provided such that the output of only one gas turbine is lost in a single incident. Another area where it is considered essential to provide segregation is where an emergency DC or guaranteed AC drive is provided for plant safety, as for example, the turbine lubricating oil supply. In these cases, full segregation by fire barrier should be provided between the main drive and the emergency drive. Where duplicate DC supplies for switchgear tripping are provided, these should be segregated from each other over their entire lengths. This requirement stems from instances where, under fire conditions, switchgear tripping supplies have been lost before main circuits have been tripped. Where segregation is not possible, it is permissible for one of the DC supplies to be cabled in short-time fireproof cable of the type described in Section 3.7 of this chapter.

We can now consider areas where segregation is not mandatory but which will result in better availability and security and will be employed if it can be incorporated without additional cost. The first area to consider is the II kV supplies to the unit which are derived from the unit transformer, station transformer or via interconnectors (see Chapter 1 System design).

Often segregation can be readily achieved between the interconnectors and the unit/station transformer feeds over the majority of their routes up to the cable race immediately below the switchgear. Similarly, where auxiliary transformers and feeders are duplicated within a unit, segregation can often be achieved for the majority of the cable routes without additional cost. Other circumstances where segregation should be applied if there is no cost penalty are main and standby plant, and also between boiler feed pumps where more than one is provided per unit.

Separation should be provided between control cables (containing analogue signals, digital signals or

plant protection signals) and power cables to minimise the effects of electrical interference. Control cables should be separated from single-core power cables by at least 600 mm and from muiticore power cables by at least 300 mm. This requirement does not apply to tail ends of routes where power and control cables are terminated in the same equipment, providing the length of run where separation distances are not met does not exceed 5 m. The basis for these electrical separation distances is discussed in Section 5 of this chapter.

2.1.2 Segregation requirements for nuclear power stations

The segregation requirements for conventional power stations to protect availability of plant are equally applicable to nuclear power stations.

However, in nuclear power stations additional segregation is necessary for the safety of personnel, the general public and plant. For these additional segregation requirements the occurrences considered are minor fire, safe shutdown earthquake (SSE), local flooding and a major incident within the station, i.e., turbine disintegration, major fire or hot gas release. The safety criterion normally applied is that any one of these incidents and its consequential effects shall not damage sufficient safety related cables to render the reactor trip and post-trip functions ineffective to a degree where an unacceptable probability of a district hazard would arise. In practice, this means that:

The reactor must retain its ability to trip.

A specified proportion of the post-trip cooling, monitoring and control systems must remain effective.

Consequential faults must not degrade the effectiveness of the reactor trip system or post-trip cooling systems, e.g., gas circulator run-on.

The method of applying these criteria will depend on the type of reactor involved. However, to illustrate the principles, an advanced gas-cooled reactor (AGR) will be considered.

Firstly we must elaborate on the meaning of segregation and for this it is convenient to define two segregation classes. Segregation Class I is defined as 'cables, plant or equipment of different groups that must be separated by a barrier or enclosure having a minimum of four-hour fire rating and also be crash proof to the required standard for the safety hazard at the barrier/enclosure location'. Segregation Class II is defined as 'cables, plant or equipment of different groups that must be separated by a minimum of hour fire barrier or enclosure'. For cables installed direct-in-ground, cable groups should be separated by at least four metres for Class I and by at least one metre for Class II. The larger separation distance in-ground for Class I is in order to avoid accidental

430

is required between quadrant pairs

 

 

 

Cable systems arid layout

 

 

 

damage to both groups by mechanical excavations.

In the case of more probable incidents, such as

for segregation Classes I and II where cables are laid

a small fire, segregation must be employed to ensure

in troughs, the routes for cable groups should be

that no more than the X and Y supplies of one

,eparated by at least six metres to protect against oil

quadrant become unavailable. Another option is

 

 

or mechanical damage.

that not more than half the total X system or, alter-

 

The additional segregation in an AGR is associated

natively, half the total Y system supplies become

„iih safety related cables. Safety related cables are

unavailable. To meet this rule, Class II segregation

:hose which contain cores/pairs which can effect the

is required between quadrants or between halves

init i a tion, operation or termination of:

of systems.

 

s a fety related fault prevention actions (e.g., control

In the case of less probable incidents, which are

those liable to cause most damage such as turbine

 

rod interlocks).

disintegration or a major fire, a different set of

Reactor trip and shutdown actions.

segregation rules must be applied. It is required

that no single incident of this type causes damage

 

 

 

Post-trip actions.

to such an extent that both the X and Y cooling

 

 

 

systems become unavailable to more than two re-

Cables associated with plant protection, indication or alarms which in the event of a fire are essential to a n operator in the central control room, emergency indication centre or local control position are also Liesignated safety related. This includes fire fighting ,ervices and essential station communications. A fur- :her special function is heating and ventilation services

for contaminated areas.

The segregation of safety related cables is considered in the following section. However, the following rules are only written for areas outside the confines of the safety room. Cabling, conduits and trunking within the confines of the safety room are subject to special requirements, and these are considered too specialised o include in this volume.

Solely related cables excluding reactor safety trip s%cterns

This section deals with the segregation of safety re- laR;(1 cables with the exception of reactor safety trip

.stems which are a special case. Safety related cables

■■[II be discussed under three broad headings:

Power cables The Heysham 2 power system ar-

rangement for one reactor is described in Chapter 1 and shown in Fig 6.1. The electrical trains forming the essential electrical system are broadly associated with the boiler circulator quadrants (A to D) of the reactor, and provide power supplies for two post-trip cooling systems. These two post-trip cooling systems are designated X and Y. Essential cooling system X is associated with forced gas circulation, e.g., gas circulators and forced-feed decay heat boilers. Essential cooling system Y is associated with natural

gas circulation and emergency feed to the main boilers.

Segregation must be employed to limit damage to the cables providing supplies to the plant and auxiliaries associated with the X and Y cooling systems. Two rules have been formulated to define the segregation to be employed, depending upon the type of incident to be protected against.

actor quadrants. Another option for this type of incident is that not more than all the X system supplies or, alternatively, all the Y system supplies fail. Thus, for a major incident, Class I segregation

A B and C D and their associated trains, or Class I segregation is required between complete sections of the X and Y systems.

In addition, separation shall be provided between the X system and Y system power cables associated with the same quadrant, and between power cables associated with different quadrants routed to and within system plant areas segregated on a half system basis. It is not mandatory to separate safety related power cables from other power cables except to ensure that the segregation principles have been maintained.

• Control cables The segregation specified for safety related power cables is also applied to the associated control cables where these are required in the performance of the safety related function. This applies to post-trip sequence control signals to essential plant.

There is no need to segregate control cables from associated power cables to the same equipment. However, it is prudent to separate them to reduce electromagnetic interference as defined for conventional plant. There is no special requirement to separate safety related control cables from other control cables associated with the same train. Typical post-trip cooling system and safety trip system cabling is shown in Fig 6.2.

• Cables for remote control and indications associated with safety related plant and equipment In the central control room (CCR), area segregation of control and indication cabling between trains/ quadrants is provided to Class II. This segregation is provided to limit economic damage and is not necessary for reactor safety for the following reasons:

(a)While the reactor is at power it is protected against rapidly developing faults by safety cir-

431

l ov s I A DON St/AHD%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

111. 514111 St

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A oX 130A111.,

 

 

 

1

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

.4 31071ShEN1IA1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUXIL4AllY BOATIL,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[T i 4155 ITS /1

415V ASSANTEAL

 

 

 

 

 

 

 

'SEA EIL)

 

 

SERVICES UOLAHOh

2.

 

 

 

 

 

 

1

 

4

4

 

 

 

 

 

 

 

 

 

 

 

; 4151/ DIESEL 4

41SV OA St 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

St HVICTS 90AHI,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.1, 7 C111111-1INA HON 1

 

 

 

 

 

 

 

 

 

 

 

 

PIANI AUX BD 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

!'''

 

t I!I '

. 'J

 

 

 

 

 

 

 

 

'

'11.

I1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 --

 

 

 

 

 

 

 

 

 

 

 

 

 

4155 CHLOHINAT1ON

 

 

 

 

 

 

 

(15)

 

 

 

 

 

 

 

 

 

7

 

 

PLANE SE TIViCES

14174

 

 

49114-4

 

BOARD 7

 

 

rf

 

 

 

 

 

41SV

 

P/N

 

 

l

 

 

 

 

 

 

 

 

SERVICES_BOATIO L 1

 

 

 

 

 

 

 

 

 

.

 

 

4151'

 

 

 

 

1

4151'

 

J

 

17, T FT El 0 I

 

E SU

Op

 

 

 

 

 

 

 

 

 

 

 

TAY

.1.

 

 

 

 

 

 

 

 

 

 

4,

 

 

 

 

 

415,,

 

 

 

 

415 V

9155

 

 

 

 

E SB

 

 

 

 

E513

 

E s

 

 

 

 

LH v

 

1-1 94 5

H//5

 

 

t5S BU 15$ 80 E4S BD

 

 

 

LAX

 

 

 

 

7.4441!

7AY

 

HT Y551/AM13245 AND

_ 1321. V

444945 SOLITTAI/ON

• •131,114.villxvslA1105 -MANSE OI/M1 ri

 

 

 

 

..", luoesi

 

 

 

 

111,5 51 ..

 

 

 

 

 

 

 

 

..__ _

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.

1

HI.) IA

 

 

 

 

HO 01

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i',1

 

 

 

 

 

 

 

 

 

 

;:h .1

1:,r

1 ,1

 

 

 

 

 

 

 

X4'7!

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 ,

1

 

 

 

 

 

 

 

 

 

 

 

 

=*-

 

 

 

-'''====

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ri'

li

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ti.-Ar t-748

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

__I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L.,

33 14 5 EST

 

 

 

 

 

 

 

 

 

 

 

I

1

 

_i

t

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C']

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 .34

,

v ESS

el

I .,

 

 

 

 

 

 

 

 

 

 

 

 

l

 

 

1313 TAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

i

AU%

 

 

 

Aux HO TRY i 1.

 

(-:; DE 7194

.;

 

 

 

 

 

 

 

 

 

A

 

X

 

 

 

 

 

A

 

7 A

7

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

111

 

1

1

1

 

A

 

0

 

 

 

 

 

 

 

 

1'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 ,1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

,

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

..--; ..-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

. .1-1'j 4115 155

 

1

 

 

 

 

 

 

..., 4155 EhS /1

a 4155 ESh II,

 

 

 

 

 

 

 

 

 

 

 

 

SET/ 80 7AY :

.1.L. STI-

 

 

 

..

 

 

 

 

' 5111 RD hex ;

 

 

 

 

 

 

 

f. (

r

 

 

 

i r

 

 

 

 

 

 

 

 

i

i

r

 

 

 

 

 

 

-

 

 

r

 

. -

 

 

 

 

 

 

 

 

 

 

r

r

 

 

 

1-

 

 

 

 

 

 

 

 

1.14Ev DIESEL;..

-

 

 

;4155 DIESEL I

,

 

.,

 

I

 

 

 

 

i.

 

 

,

EH HD BY? 44..

 

 

 

 

4SER

80 95 /4:

_

 

 

L4/.........,

G'i _

.,S

 

 

 

 

 

 

41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41. 11 II

 

 

 

 

 

734, 5 STATION A...1%111.4NY BOARD /

 

 

 

 

 

n ...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C' 1

A

11?

 

i !)

0

 

L7,I

 

 

il:i

 

 

i

 

III

 

11

 

 

 

I f

I 1

 

 

 

 

 

 

 

 

 

 

 

 

 

:

4 1 ID. V ON/

 

 

I tit/ARO rri'

LI 4 .1,

7

I,1

 

I:I

1 . 1

L

L.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

-,-;-,171c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

':".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C i

, I

 

Y 90 715 '

 

'

 

 

Alx 13I .

 

1'15

 

 

$

 

 

1

 

 

'

 

 

 

 

 

 

 

 

 

 

 

 

j

315K

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

T

 

..1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T

T

1,

 

C

 

'.

;

 

111

 

t

 

I .

T.

 

 

 

1

 

L 1. 1

 

 

 

 

 

 

 

 

 

 

 

 

I41-•

' I

l' 1 4155

: SS

 

,,! '

1 ; S1A-1

I1

H /115

4

‘.

{ 14154111ES11(

.

4 TT

,SEI:ID 1:2. .. 4/

--.TA ,

 

..,82. 2....._

3 :4141! UNIT AUX 901115o 7

L!, ,

A

I i

„. __L

i'

41S111h1

T1 ,

 

' T114

ALL /1/11/.

 

1

4 it•V 4715511.

; -

,i[22.

-.).

,.

 

..i.

 

.. .....

 

 

 

1) 51404,0., 1,11,4 IIA

 

 

 

 

 

 

 

 

 

 

 

. 1.

 

 

 

 

F RANS. OHME IA 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

114V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

111/4110 !I ,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I T1

iiI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i

 

 

4—'

 

 

 

 

 

 

 

,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

. 1

1

 

 

 

•--T0'

 

 

 

 

 

..,-,.‘

 

 

 

 

 

I

 

 

 

 

 

1

I

 

 

 

 

 

 

 

 

 

I

 

 

7

,111i

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

../

 

 

 

 

 

 

 

1-

 

 

 

 

 

 

 

 

 

 

 

 

 

:KV ASS

 

11. 1

 

l'I

 

'‘I

 

 

 

 

 

 

 

A LIA

AD 11D,

'

 

 

'

7

'

AD

//l

 

 

 

 

 

 

 

i

 

 

 

 

 

 

L■

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YI

 

 

 

 

 

(

 

 

 

 

 

 

 

 

 

 

 

 

 

r

 

,'

 

-

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

4155 LT5

' L

 

 

 

t,

414V I S h

'

 

T.

TEN EIL

N.". 1

 

 

 

 

 

 

: 1 111 911 7 DA '

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.7

1.,risv

1111511

; -

 

 

rf '(

 

 

_

 

,,

Skil

 

..,

 

...

 

 

 

 

. ..--....a.

 

 

 

_

 

 

 

1B:,O

DV. 7..

 

 

I

 

 

L.•

r

'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

..c

 

 

E D

 

:.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

I/10., UN! 11 LINLAHLTS

13.5 0115A L

Ault 80114115

1 0., ASSES 11.41.

AHAILIAITY BOARDS

4155 I SST NTiAl.

SERVICES. . ,,, b,•1:713S

L

hi 1- 5 511 th 110ATIOS

4151 ALIX11 LAT7 1

80111H filJA1-111h

 

 

 

 

 

 

 

T

 

*

 

 

4.T'

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

I

 

I

 

, .11.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

415VSTAllUN

 

 

 

 

41-51! UNIT

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

44.

 

 

 

 

 

 

 

 

 

 

 

r-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REACTOH SOUTH 1.

..11.1EACTOR S. 0411 H

4

 

4 5 V 1-

1

1.

- -- .7.

41

5

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[ cy, Et

AsCiTHA,U 1,0;N,01,:l'i

 

 

 

 

 

 

 

 

 

 

 

415 V 10149151

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

al,

 

 

SE 1510Es

,,, ,

 

c i

 

SERV/LES

i d

 

 

 

 

 

 

 

 

 

1 1j

NOHTH , 1 , SERV, , L. ,;. ,

,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r.

 

 

EIDA1-10 7

 

 

 

V.

 

;

 

 

 

Elt.O. .A,441.7 I

 

-

 

 

,

 

 

 

 

 

 

 

 

I

ITTA L104 1:

B O

 

 

 

 

 

 

HOAR D /

 

 

 

I.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

II

i

 

 

 

 

..... 1,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

4 • 4

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4155

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

f...t;__8,

„:„ _...4J

r ry

 

 

 

 

 

 

 

 

 

fr/ BD IC

 

ir(LHIN'EF1PCn

1:'

 

 

 

4,./E55N ,A,c_cc:; 111.11../ C,,

-

 

 

 

 

 

 

 

 

 

 

 

 

,. AC/MILL

 

_

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

n

 

 

 

f

f

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1 , „ i„, ,,,.., ,, ,'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AM:1W, A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4,5„, GAS CifiC ;

4155 D /4 L fC AC S

 

 

 

 

 

415V .1•F,S•CiHi2. 1

"

R P 50 1

 

 

!

4 ,v 1,

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

91/

 

 

 

e,)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

'.1-151 RH BO 78 ,

/OSINC4 PLANT..T:l1 . 7

 

 

 

 

 

 

 

 

 

J0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tj

 

 

'' SET I 415V Li & 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

__

..........-

.,

 

_ya

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ILK ACTOH

[.•

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r

 

 

 

4s y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41

 

H & V

 

 

 

 

.0 811

 

 

1 .

 

 

 

 

 

BLI IA

'

 

 

 

4155 CA NEHAL htH BD

/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

!•L—...-,:k.■.■ HE ACTON SE115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.4 . SV WiS ST)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ANNE X EID IA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41145 A T

 

 

I 1 A L., 1.1701

1.1?"11,,.: VI.cA

 

 

?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

v & V F uE

 

 

 

 

 

 

 

 

 

 

 

 

' tHISA Il//AIAI AND

 

 

 

 

PLAN I 110

 

ITTANSF

 

 

 

s, NCI

 

 

 

 

 

Il.:A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EROCK tiUAR0 7

 

 

 

 

 

 

 

 

 

 

 

 

 

1' 71A MAIN1 BD A

 

 

 

 

 

 

 

 

 

 

_IF, 1/11 SE L:f1 '

. 1 :

7iO4,

LT1151 L

 

 

I J

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

'/

..,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

..7;1 .

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

. 115%. FUEL BLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tl & 1/ 1051 ?MELT.

 

 

 

 

 

 

 

 

7

I.; TURBINE

 

 

 

 

 

 

HISS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SERVICES LIOA140 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

;

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ANNE X BOAHO 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEACToH

 

 

 

 

 

 

 

I -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 I51! Rb V ACTIVE

 

 

 

 

 

 

 

 

 

 

 

 

4155 II & VI/AS CTHC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

LIG

5" ( J

 

 

 

e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WASTE BIJILDINO LID/

 

 

 

 

 

 

 

 

 

WORKSHOP ROALIII

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ii

I. 4155

 

 

9.o

 

 

:

 

 

 

 

d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L::111:A

'1 ! 1

11 °. :

 

 

 

TUR13

 

,

-

 

 

Y

 

'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

;155 1: 02STORAL4

 

 

 

 

 

 

 

 

 

 

 

 

4-1 5 5 &FAS 1111

 

 

 

 

 

 

 

 

 

 

 

141 5114 1 5

 

 

 

7377: 771::

6 LTG SEFiv ,1',.,

4115 TURBINE HOUSL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLANT BOARD

 

 

 

 

 

 

 

 

 

 

 

 

WOHKhoi111 1

S1 II BD

 

 

 

 

 

 

 

 

 

 

Si

I

A 51.1414074

4.fE11:.........

 

 

 

 

 

H & 5 SEH 9113 7

 

 

 

 

 

 

 

 

 

 

 

4 4 l' SV POND WA TE- 14 AND LASK

 

 

 

 

 

 

 

 

4155 PIA

 

c

 

 

 

 

 

 

 

 

 

 

 

 

 

1 H ANSI 'S

14: 7

yr.

11-/ANSI.15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lAIll hi

 

Oit SI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LACONTAmINA DON 811//HO

 

 

 

 

 

 

 

511151115

 

 

 

'

 

 

 

 

 

 

 

 

 

 

 

 

lit

NI HA 10145 LA NLITAT OHS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4155 ELECTROL AND147

 

I" At

 

-4114‘,

ATIVEC

EFELLANI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FSSI NTIA4

 

 

 

 

METH FLT 90 7

 

 

 

 

 

 

 

THEAlmENT AN1 dl?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

h1641CH-Lik AN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4155 CONIPHESSO; t

 

 

 

 

 

 

 

 

 

 

 

 

;155 SUL IL) WASTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLANT BOARD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FACILITY 190A911.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fi(i. 6.1 Heysham 2 — power sysieni for unit 7 and common services