- •Iaea safety standards
- •Objective
- •Structure
- •Relationship to other standards
- •2. Management systems for I&c design
- •2.8. The management systems for development of I&c systems should comply with the recommendations of Safety Guides gs-g-3.1, Ref. [5] and gs-g-3.5, Ref. [6].
- •Generic management system processes
- •Configuration management
- •2.15. All I&c configuration items and their associated configuration documents should be designated, given a unique identification, and placed under configuration control.
- •2.31. Insights gained from probabilistic safety assessments (psAs) should be considered in the design of I&c systems.
- •Documentation
- •2.33. Before I&c systems are declared operable their documentation should be complete and should reflect the as-built configuration.
- •2.34. I&c documentation should:
- •2.36. I&c documents should be grouped according to their primary or secondary role in the design process.
- •2.38. Documentation for I&c systems and components should, as a minimum, cover the following topics:
- •3. Design bases
- •Inputs to I&c design bases
- •Identification of I&c functions
- •3.4. The required functions of the I&c systems should be determined as part of the nuclear power plant design process.
- •Content of I&c design bases
- •3.7. The overall I&c system architecture and each I&c system should have a design basis.
- •3.9. The I&c systems required for the safety of the plant should be identified systematically.
- •3.10. I&c system design bases should specify the following:
- •3.12. In addition to the above the design basis for the reactor protection system should specify the following:
- •Variables and states that must be displayed so that the operators can confirm the operation of protective system functions;
- •4. Guidance for overall I&c system architecture architectural design
- •4.3. The overall I&c architecture should:
- •4.4. The inputs to the overall I&c architecture design process should refer to the plant safety design basis documents, which should provide the following information:
- •Defence in depth
- •4.28. When diverse I&c systems are provided to meet requirements for defence-in-depth, the diverse systems should not both be subject to the same errors in design or fabrication.
- •5. Safety classification of I&c functions, systems, and equipment
- •6. Life cycle activities
- •Process implementation
- •Verification that the effects of automatic control system failures will not exceed the acceptance criteria established for anticipated operational occurrences.
- •6.58. The I&c architecture should be designed to fully satisfy the system requirements, including system interfaces and non-functional requirements (e.G., performance and reliability).
- •6.109. The benefits of changes should be weighed against potential negative safety consequences and this assessment documented as part of the justification for the changes.
- •Design for reliability
- •Single failure criterion
- •7.10. Each safety group should perform all actions required to respond to a pie in the presence of:
- •7.15. Non-compliance with the single failure criterion should be exceptional and clearly justified in the safety analysis.
- •7.19. I&c systems should be redundant to the degree needed to meet design basis reliability requirements.
- •Independence
- •7.27. When isolation devices are used between systems of different safety importance, they should be a part of the system of higher importance.
- •7.29. The adequacy of design features provided to meet the independence recommendations should be justified. Physical separation
- •7.31. Items that are part of safety systems should be physically separated from items of lower safety classification.
- •7.32. Redundant items of safety systems should be physically separated from each other.
- •Electrical isolation
- •Diversity
- •7.49. The decision to use diversity or not use diversity should be justified.
- •7.50. Where diversity is provided to cope with ccf several types of diversity should be used.
- •7.51. Where diversity is provided the choice of the types of diversity used should be justified.
- •Failure modes
- •7.57. The failure modes of I&c components should be known and documented.
- •7.60. Failures of I&c components should be detectable by periodic testing or self-revealed by alarm or anomalous indication.
- •7.73. Analysis that is part of the evidence of equipment qualification should include a justification of the methods, theories and assumptions used.
- •7.75. Traceability should be established between each installed system and component important to safety and the applicable evidence of qualification.
- •Suitability and correctness
- •7.81. The equipment qualification program should demonstrate that the as-built I&c systems and installed components correctly implement the qualified design.
- •7.90. Environmental qualification of safety components that must operate in harsh environments should include type testing.
- •7.102. Detailed emc requirements should be determined for safety systems and components and their compliance with the requirements demonstrated.
- •7.105. Equipment and systems, including associated cables, should be designed and installed to withstand the electromagnetic environment in which they are located.
- •7.109. Limits on radiated and conducted electromagnetic emissions should be established for all plant equipment.
- •7.112. The equipment qualification program should show that electromagnetic emissions of plant equipment are within the defined limits.
- •7.114. Instrumentation cables should have twisting and shielding sufficient to minimize interference from electromagnetic and electrostatic interference.
- •Design to cope with ageing
- •7.119. Ageing mechanisms that could significantly affect I&c components and means for following the effects of these mechanisms should be identified during design.
- •7.122. Maintenance programs should include activities to identify any trend towards degradation (ageing) that could result in the loss of operability of equipment.
- •Control of access to systems important to safety
- •7.130. Access to equipment in I&c systems should be limited to prevent unauthorized access and to reduce the possibility of error.
- •Testing and testability during operation
- •Test provisions
- •7.150. Arrangements for testing should neither compromise the independence of safety systems nor introduce the potential for common cause failures.
- •Test interfaces
- •7.153. Provisions for testing I&c systems and components should:
- •7.154. Where equipment to be tested is located in hazardous areas, facilities should be provided to allow testing from outside the hazardous area.
- •7.164. The test program should define processes for periodic tests and calibration of systems that:
- •Individually test each sensor, to the extent practicable.
- •7.165. In addition to the recommendations of paragraph 7.164, the processes defined for periodic tests and calibration of safety systems should:
- •Independently confirm the functional and performance requirements of each channel of sense, command, execute, and support functions;
- •Include as much of the function under test as practical (including sensors and actuators) without jeopardizing continued normal plant operation;
- •Maintainability
- •7.169. The design of I&c systems should include maintenance plans for all systems and components.
- •Setpoints
- •7.185. Trip setpoints used to initiate safety actions should be selected to ensure that required mitigating actions occur before the monitored variable reaches the analytical limit.
- •Operational identification of items important to safety
- •7.186. A consistent and coherent method of naming and identifying all I&c components should be determined and followed throughout the design, installation and, operation phases of the plant.
- •7.190. I&c components in the plant should be marked with their identifying information.
- •8.4. To the extent practicable, the plant conditions of concern should be monitored by direct measurement rather than being inferred from indirect measurements.
- •8.17. Means should also be provided to manually initiate the mechanical safety systems and the individual components necessary to initiate and control performance of their safety functions.
- •Digital computer systems and digital equipment
- •8.68. Specific skilled staff should be available during operation to allow controlled software and configuration data changes to be made when necessary to computer based systems.
- •8.91. Data received and data transmitted should be stored in separate, pre-determined memory locations.
- •8.154. Tools should be used to support all aspects of the I&c life cycle where benefits result through their use and where tools are available.
- •8.173. Confirmation of the suitability and correctness of industrial digital devices for their intended functions should produce evidence:
- •V&V at each stage of development for the final product;
- •9.4. The I&c system should allow the operator in the control room to initiate or take manual control of each function necessary to control the plant and maintain safety.
- •9.21. Instrumentation performing the functions given in 9.20 items a, b, and c should be classified as safety systems.
- •9.32. The main control room, the supplementary control room, and the Emergency Control Centre should have at least two diverse communications links with:
- •9.42. The Human System Interface (hmi) design should retain positive features and avoid hfe issues and problems of previous designs.
- •9.57. Where hmi stations are distributed, plant staff should have means to access these different locations in a safe and timely manner.
- •10.4. Development of software for systems should follow a previously defined life cycle, be duly documented and include thorough verification and validation. (See Chapter 6.)
- •10.49. Coding rules should be prescribed and adherence verified.
- •10.72. Verification should include the following techniques:
- •Software tools
- •Glossary
- •Annex I defense in depth in I&c systems
- •Annex II traceability to previouse I&c safety guides
- •Annex III bibliography of supporting international standards
8.154. Tools should be used to support all aspects of the I&c life cycle where benefits result through their use and where tools are available.
8.155. A key element of integrated project support environments is to ensure proper control and consistency. If tools are not available, the development of new tools might need to be considered.
8.156. The benefits and risk of using a tool should be balanced against the benefits and risk of not using a tool.
8.157. The important principle is to choose tools that limit the opportunity for making errors and introducing faults, but maximize the opportunity for avoiding or detecting faults. System development might be adversely affected by the use of tools in several ways. For example, design tools might introduce faults by producing corrupted outputs; and verification tools might fail to reveal certain faults or types of faults.
8.158. Tools should be selected to remain available throughout the system lifetime and be compatible with tools used in other development phases.
8.159. The functionality and limits of applicability of all tools should be identified and documented.
8.160. The tools and their output should not be used outside their declared functionality or limits of application without prior justification.
8.161. For example, tools cannot replace humans when judgment is involved. In some cases, tool support is more appropriate than complete automation of the process.
8.162. Tools should be verified and assessed consistent with the tool reliability requirements, the type of tool, and the potential of the tool to introduce faults.
8.163. For example:
Verification is not necessary for tools that cannot introduce or fail to detect faults;
Less rigour in tool verification may be accepted if there is mitigation of any potential tool faults (e.g. by process diversity or system design);
Verification is not necessary for tool outputs that are systematically verified independently of the tool.
8.164. The verification and assessment of software tools should take into account experience from prior use, including experience of the developers and experience gained from the processes in which the tools are used.
8.165. The choice and qualification of tools should be justified and documented.
8.166. All tools should be under appropriate configuration management.
8.167. Tool parameters used during the development, verification, or validation of baseline equipment or software should be recorded in the development records.
8.168. This is useful not only for the final software consistency; it also helps in assessing the origin of a fault, which might lie in the source code, in the tool, or in the tool parameters. It might also be necessary in the assessment of the potential for common cause failures due to software tools.
QUALIFICATION OF INDUSTRIAL DIGITAL DEVICES FOR SAFETY APPLICATIONS
8.169. This section provides guidance on the qualification of industrial digital devices of limited functionality that are to be used in nuclear power plant safety systems, but that have not been developed specifically for use in such applications.
8.170. Devices of limited functionality are devices that perform only one function or a very narrow range of functions. Examples include: smart sensors, valve positioners, power meters, soft-starters, inverters, dedicated display units, or dedicated communications interfaces that contain or might contain software or complex electronic components.
8.171. This guidance does not apply to devices that can be programmed to perform functions other than the specified function. For example, general-purpose devices for which the functionality can be defined using a programming language.
8.172. This guidance supplements the general equipment qualification recommendations of paragraphs 7.67-7.127 for devices in this category.