- •Theoretical data
- •Setting of protection functions of mp3c-05
- •General guidance
- •Work order
- •Measured indications and their measuring accuracy
- •Checking of maximal current protection (mcp)
- •Checking of maximal current protection (mcp) attention!
- •It’s not allowed to set parameters of mt3 less than 2.7 a.
- •Change of drawdown parameters of current protections of mp3c-
- •Check of maximal voltage protection (зНмах).
- •Parameters set of maximal voltage protection (зНмах).
- •Measuring of parameters of maximal voltage protection actuation (зНмах)
- •Checking of minimal voltage protection (3Hmin)
- •Setting of protection parameters of minimal voltage (3Hmin)
- •Changing of minimal voltage protection parameters actuation (3Hmin)
- •5. Contents of report
- •Laboratory work # 5
- •Laboratory work # 5
- •Theoretical information
- •AIlBointment of automated functions mp3c-5
- •General instructions
- •Work and functional block scheme аг1в, уров
- •Automatic reclosing of апв
- •Breaker failure protection device (уров)
- •Work order
- •The parameters and the accuracy of their measurement
- •Checking of апв.
- •Setting of parameters апв mp3c-05
Aim of the work: to get acquaintance with a work of protection functions of microprocessor-based relay protection device “MP3C-05”.
Tasks:
To get acquainted with a description, settings, logical schemes and a work of protection functions: maximal current protection (MT3), shortening protection (33), voltage protection (311), automatic frequency discharge (АЧР) of microprocessor-based relay protection device “MP3C-05” accordingly to exploitation manual РСГИ.466452.007 РЭ.
To get acquainted with Instruction of the operator of service program SizifJL, which is dedicated for a work with “MP3C-05” device.
To perform practical check of working accuracy of protection functions: maximal current protection (MT3), shortening protection (33), voltage protection (3H), automatic frequency discharge (АЧР) of microprocessor- based relay protection device “MP3C-05” using Sizif_L service program for parameter set.
To prepare a report with obtained results.
Theoretical data
Setting of protection functions of mp3c-05
Protection functions of MP3C-05 are aimed for protection of air and cable voltage lines of 6 - 35 kV, which works with isolated or compensated neutral terminal:
from phase shortening (MT3);
from ground shortening (33);
via minimal voltage (3H) ( with ability of current blocking selection and without blocking);
via maximal voltage (311);
from decrease of network frequency below desired (АЧР).
General guidance
MP3C device is produced by producer-plant fully adjusted and checked without protection functions, and with minimal values of settings, which values are presented in table 1.
Simplified scheme of connections
Simplified scheme of connections of MP3C-05 is described on fig. 1.
Work order
Performing of practical check of protection functions MT3, 33, ЗН, АЧР of MP3C-05 device include the stage of parameter set for protection work of MP3C-05, sending of output voltage & current values in specified ranges, with the help of console panel, to input of MP3C-05 and also control of an accuracy of definite protection parameter measuring.
Measured indications and their measuring accuracy
Measured indications and their accuracy is shown in table 1.
Table 1.
Measured parameter |
Nominal value or measuring boundaries |
Maximal deviation |
Current of maximal current protection actuation (MT3), |
|
|
A |
0,50 - 20,00 |
±5% |
Coefficient of a return (KB) of starting organs MT3 |
0,95-0,98 |
- |
Restraint time of protection activation , s: |
|
|
- 1 range |
0,00-5,00 |
±0,01 |
- 2 range |
5,00- 32,00 |
±0,05 |
Current of ground shortening protection actuation (33), |
|
|
mA |
5,00 - 300,00 |
±10% |
Voltage of minimal voltage protection actuation |
14,40 - 100,00 |
±5% |
(Umhh), V |
|
|
Voltage of maximal voltage protection activation |
23,20 - 110,00 |
±5% |
(Umakc), V |
|
|
Coefficient of a return of voltage protection: |
|
|
- Umhh |
1,01 - 1,05 |
- |
- UMakc, not less |
0,9 |
- |
Frequency of actuation and return of automatic |
|
|
frequency discharge (АЧР), GHz |
45,00 -50,00 |
0,05 |
Coefficient of a return of АЧР |
1,01 |
±1% |
During practical check of protection functions work (защит MT3, 33, 3H, АЧ) we calculate coefficients of the return, diagnostics tolerance of separate parameters by means of next formulas:
coefficient of return of protection according to a current
Where I, - current of return of a protection to initial value;
And Ipra - current of protection actuation;
-coefficient of return of protection according to a voltage
Where Ur-voltage of return of protection to initial state;
And Upra -voltage of protection actuation;
Coefficient of return of a protection according to a frequency
Where fr- frequency of return of protection to initial state; And fpra- frequency of protection actuation;
- accuracy of actuation of voltage protection
Where Upra- voltage of protection actuation;
And Us — setting of a voltage of protection actuation;
- coefficient of frequency protection actuation
Accuracy of actuation of current protection
Where
Ipra-
current of protection actuation;
And
Is-
setting of a current of protection actuation;
Where fpra- frequency of protection actuation;
And fs- setting of a frequency of protection actuation