- •Related Catalogs
- •1 Introduction
- •The SINAMICS drive family
- •The members of the SINAMICS drive family
- •SINAMICS DCM Cabinet drive converter units
- •The system components of a DC drive
- •2 Highlights
- •Ready to connect up and switch on
- •Supply for motor fan
- •Flexibility for the auxiliary power supply
- •EMC zone concept
- •Monitoring the temperature inside the drive cabinet
- •Individual components and customer interfaces that are easy to access
- •Type tested
- •Documentation
- •Special project-specific solutions
- •3 SINAMICS DCM Cabinet
- •General information
- •Overview
- •Benefits
- •Application
- •Design
- •More information
- •Ordering and technology
- •Selection and ordering data
- •Function
- •Technical specifications
- •General technical data
- •Coolant temperature and installation altitude
- •Installation location
- •Relevant standards
- •Electrical data
- •Mechanical data
- •Environmental conditions
- •Mechanical stability
- •Approvals
- •Schematics
- •Block diagrams
- •Assignment of terminals and connectors
- •The Terminal Module Cabinet (TMC -X71, -X72)
- •Documentation
- •4 Options
- •Available options
- •Overview
- •Ordering examples
- •Description of the options
- •DC Converter
- •Other voltages, frequencies
- •OFF functions
- •Display instruments
- •Supplementary circuits
- •Motor-relevant options
- •Monitoring functions
- •Supplementary modules
- •Mechanical options
- •Other options
- •Documentation
- •Packing
- •5 Engineering information
- •Dynamic overload capability
- •Parallel connection and 12-pulse applications of SINAMICS DC MASTER integrated in the drive cabinet
- •SINAMICS DC MASTER to feed high inductances
- •Characteristic values of the pulse tachometer evaluation electronics
- •Notes for EMC-compliant drive installation
- •Harmonics
- •6 Tools and engineering
- •SIZER WEB ENGINEERING
- •STARTER commissioning tool
- •Drive Control Chart (DCC)
- •Drive ES engineering software
- •7 Services
- •SINAMICS DCM demonstration case
- •Service & Support
- •Overview
- •Commissioning drive systems
- •Customer-specific drive training
- •Maintenance and inspection of drives
- •Spare parts for drives
- •Remote maintenance – expert knowledge available close at hand
- •Energy saving in drive technology
- •Modernization of drives
- •Service portfolio
- •Extension of the liability for defects
- •Training
- •Product information SINAMICS DCM Cabinet
- •SINAMICS DCM Service and commissioning
- •SINAMICS DCM Upgrade for SIMOREG experts
- •Commissioning SIMOREG DC-MASTER
- •8 Appendix
- •Subject index
- •Order No. index
- •List of abreviations
- •Conditions of sale and delivery
- •Catalogs
© Siemens AG 2012
SINAMICS DCM Cabinet
Options
Description of the options
■Overview (continued)
M66
Marine version
Corresponding to the requirements of the marine classification societies Lloyds Register, American Bureau of Shipping, Germanischer Lloyd or Det Norske Veritas, individual acceptance tests are carried out in the factory.
M90
Crane transport aid (mounted at the top)
A top-mounted crane transport assembly can be ordered as an option for SINAMICS DC MASTER Cabinet. Depending on the
width of the cabinet, it consists of either transport eyebolts (width ≤ 1 600 mm) or transport rails (width > 1 600 mm).
Other options
F03
Equipment acceptance with customer present: visual acceptance
The acceptance scope includes:
•The degree of protection is checked
•The integrated components are checked to ensure that they are complete (checked against the parts list)
•The equipment codes are checked
•The clearance and creepage distances are checked
•The cable tags are checked
•Customer documentation is checked
•Acceptance report is handed over
All the above checks are performed with the equipment in a no-voltage condition.
F97
Equipment acceptance with customer present: customer-spe- cific acceptance
Q80 to Q85
Extension of the liability for defects
A detailed description of the options is provided in the catalog section, Services, Section Service & Support under Liability for defects.
U09
Version according to UL Listing
The converter cabinet is designed and built corresponding to UL specifications. The option does not include any certification. Individual certification can be performed in the factory after prior agreement.
X30
Customer-specific requirement
If options are requested, which are not covered by the catalog, customer-specific requirements can be ordered specifying order code X30 on request and following technical clarification.
Y09
Special cabinet paint finish
As standard, the drive cabinets are delivered in RAL 7035. The special paint finish must be specified in plain text when ordering.
All RAL colors which are available as powder coatings can be 4 selected. If roof sections or canopies (order code M21), top cov-
ers (codes M23/M43/M54 ) are required for the drive cabinets, these will also be painted the same color as the cabinet. The molded plastic parts (e.g. ventilation grilles) as well as options such as cable marshaling space (order code M07) are finished in RAL 7035, and cannot be painted. A special paint finish is also not available for the optional socket (option M06).
Y32
Labeling plate to identify the system, two lines, 40 × 180 mm
If acceptance tests are requested, which are not covered by option F03, customized acceptance tests/supplementary tests can be ordered using order code F97 on request and following technical clarification.
K07
Without Advanced Operator Panel AOP30
The Advanced Operator Panel AOP30 is not provided. The AOP30 is not installed in the cabinet door and is not supplied the equipment.
90
Field+D4Z01R041 |
|
Field 2-31FA011 |
|
|
|||||
|
|
|
|||||||
|
40 |
||||||||
Field 3 |
infeed roller FS |
||||||||
|
|
||||||||
|
|
||||||||
|
|
||||||||
|
|
|
180 |
|
|
|
|
||
|
|
|
|
|
|
|
|||
|
|
|
G_D023_EN_00087 |
||||||
|
|
|
|
|
|||||
L91
Commissioning interface (PROFIBUS) brought out
The commissioning interface (PROFIBUS) is brought through the cabinet door of the control cabinet. This interface is intended for commissioning purposes only and cannot be used to continually control the drive. The cable entry in the cabinet is equipped with a protective cover.
Plastic labels (white with black engraving) are available to mark the drive cabinets. The labels are glued to the cabinet door.
Dimensions H × W: 40 × 180 mm.
The text must be specified in plain text when ordering. Field 1: Max. 9 characters, font size 10 mm
Field 2: Max. 9 characters, font size 10 mm Field 3: Max. 20 characters, font size 10 mm.
Siemens D 23.2 · 2012 |
|
4/21 |
|
|
|
© Siemens AG 2012
SINAMICS DCM Cabinet
Options
Description of the options
■Overview (continued)
Documentation
D02
Customer documentation (circuit diagram, terminal diagram, layout diagram) in the DXF format
Option D02 can be used to order documents such as circuit diagrams, terminal diagrams, layout diagrams, and dimension drawings in the DXF format, e.g. for further processing in AutoCAD systems.
D04
Customer documentation, paper
Equipment documentation is supplied electronically on DVD as standard. If the customer also requires a hard copy of the documentation and selects option D04, the following documents will be included in a document folder with the converter cabinet:
•Operating instructions
•Circuit diagram
•Terminal diagram
•Layout diagram
•Dimension drawing
Independent of selecting option D04, safety and transport 4 instructions, the circuit manual with circuit diagram, terminal
diagram, single-line block diagram and layout diagram as well as the dimension drawing are always provided as hard copy in the drive cabinet.
Note:
The documentation language is selected using options D58 to D80 (standard, German and English).
D14
Preliminary customer documentation
If documents such as circuit diagrams, terminal diagrams, layout diagrams and dimension drawings are required in advance for the purpose of system engineering (integration of drive into higher-level systems, interface definition, installation, building planning, etc.), it is possible to order a draft copy of the documentation when ordering. These documents are then supplied electronically a few working days after the order has been clarified. For project-specific, special solutions, option D14 is only available on request.
D19
Circuit diagram prepared for motor overtemperature monitoring using a limit value transmitter
The evaluation is realized using an isolated signaling contact in the motor (order code A31 according to Catalog DA 12 · 2008, Protection and monitoring).
D20
Circuit diagram prepared for motor temperature monitoring
PT100, PT1000, KTY84-130, PTC or NTC motor temperature monitoring devices can be directly evaluated in the SINAMICS DC MASTER. When specifying the option, for the corresponding temperature input, this is documented in the circuit diagram. The customer connection is realized at the TMC terminal adapter.
D21
Circuit diagram prepared for speed actual value sensing (pulse encoder)
The connection of the speed actual value sensing using a pulse encoder is shown in the circuit diagram. The customer connection is realized at the TMC terminal adapter.
D22
Circuit diagram prepared for speed actual value sensing (analog tachometer)
The connection of the speed actual value sensing using an analog tachometer is shown in the circuit diagram. The customer connection is established at the power interface of the SINAMICS DC MASTER.
D58 to D80
Documentation language
The following options refer to the operating instructions and the List Manual for SINAMICS DC MASTER DC Converter as well as the standard information texts in the circuit diagram. Parts lists are in English/German.
Order code |
Languages |
D58 |
English/French |
|
|
D60 |
English/Spanish |
|
|
D61 |
English/Russian |
|
|
D80 |
English/Italian |
|
|
Packing
M91
Packaging type: wooden crate
Cabinet bolted to a pallet, air cushion + shrink foil + additional air cushion at the top. Wooden frame with approximate 100 mm clearance to the cabinet, nailed with wooden strips with approximately 200 mm space between them (low level of protection against mechanical damage).
M92
Packaging type: crate, packed for air freight
Cabinet bolted to a pallet, air cushion + shrink foil + additional air cushion at the top. Packed in a wooden crate.
M93
Packaging type: crate, seaworthy packaging
Cabinet bolted to a pallet, air cushion + aluminum foil + air cushion at the top, desiccant added, and welded, vacuum sealed and packed in a wooden crate.
M94
Packaging type: additional packaging data IPPC ISPM15 (according to country-specific regulations)
Protection against insects that can cause damage, all of the wooden parts manufactured out of plywood. The factory is certified for packing according to ISPM15.
4/22 |
|
Siemens D 23.2 · 2012 |
|
|
|