Добавил:
Опубликованный материал нарушает ваши авторские права? Сообщите нам.
Вуз: Предмет: Файл:
01 POWER ISLAND / Overview of Light Water.docx
Скачиваний:
0
Добавлен:
01.04.2025
Размер:
8.88 Mб
Скачать

Chapter 3 Systems of PWR Nuclear Power Plants

  1. Dc power supply systems

The DC power supply systems consist of two safety systems and one or more non-safety- related systems. The number of non-safety-related systems is determined based on their loads, which are dependent on the plant design. All systems are independent and physically separated from each other. Each system has its its own battery, two battery chargers, two voltage compensators and a distribution panel. The two safety DC power systems supply power to redundant plant equipment including relays, breakers, solenoid valves, and inverters of safety systems, including the engineered safeguard systems, essential for the plant safety. The non-safety DC power system(s) supplies power to the turbine-generator auxiliary system equipment and to non-safety equipment including relays, breakers, solenoid valves, and inverters of the systems which are not essential for the plant safety.

The one-line diagram of one of the two safety DC power systems is shown in Figure 3.10.6. Hie non- safety DC power system(s) has the same structure with the safety DC power systems.

  1. Instrument power systems

Instrument power systems include four safety systems and a few non-safety systems. The one-line diagram of two of the four safety instrument power systems is given in Figure 3.10.7. The number of non-safety-related systems is determined based on their loads which are dependent on the plant design.

Each safety system is supplied power by an uninterruptible power supply unit (inverter). Each non-safety instrument power system is conventionally fed from an AC

bus either through constant-voltage regulators or a transformer. However, in the latest plants, in which reactor and turbine control systems are computerized, each non-safety instrument power system is supplied power by an uninterruptible power supply and by a backup AC bus through constant-voltage regulators or a transformer. Power is independently supplied to each instrument power system from the main power source (inverter) and the backup power source (constant-voltage regulator).

Reactor control center

Safety protection systems

Important safely systems

including engineered safety feature

(Notel With mechanical interlock

Figure 3.10.6 Direct current power supply system (one of safety system)

Reactor control center

Board feu | 4 c Icard for j I c

Al Cl

(Note)Wllh mechanical Interlock

Figure 3.10.7 I & C power supply system (two of safety systems)

3 119

NSRA, Japan

  1. Plant Auxiliary Systems

A water supply and treatment system, an auxiliary steam system, compressed air systems, heating, ventilating and air conditioning systems, and a fire protection system are collectively called plant auxiliary systems. These systems support the plant operation, as well as provide the plant with services, such as ensuring the plant habitability, supplying drinking water, and so on.

  1. Water Supply and Treatment System

Either filtrated river water or sea water processed in a desalination unit are used as raw water supply sources for NPPs. The capacity of the water supply and treatment system is determined based on a water supply plan with a scale commensurate to the plant size. In multi-unit plants, approximately

    1. ton/d ■ MWe (approximately 1,400 ton/d • unit for 4-loop units) is an adequate capacity for its water supply and treatment system. Raw water is stored in raw water storage tanks and sent to primary and secondary system make-up water storage tanks after treatment by a water treatment unit. Water treatment units usually use mixed-bed demineralizers to produce high quality pure water.

Typical quality standards for make-up water at the outlet of a water treatment unit are given in Table 3.11.1. The schematic flow diagram of the water supply and treatment system for a typical NPP is shown in Figure 3.11.1.

  1. Auxiliary Steam System

As shown in Figure 3.11.2, a typical auxiliary steam system consists of a steam converter, auxiliary boilers, an auxiliary steam drain tank, and auxiliary steam drain pumps. The auxiliary steam

Table 3.11.1 Demineralized water quality specification (Typical at outlet of demineralizer)

Item

Threshold (concentrations)

pH(25°C)

6-8

Conductivity (25 °C)

1.0 pfl/cm

Resolved Oxygen (DO2)

< 0.1 ppm

Silica (S1O2)

< 0.02 ppm

Chlorine (Cl)

0.1 ppm

Total Iron(Fe)

< 0.01 ppm

system supplies heating steam for components such as a boric acid evaporator, a liquid waste evaporator, heating, ventilating and air conditioning system heaters, and freeze-proof tank heaters. It also supplies steam to the turbine glands for sealing, and to the deaerator for heating, when steam generators cannot supply steam to fulfill these purposes during the plant start-up or shutdown operations.

The steam converter is heated with turbine- extracted steam during the plant normal operation, and it is heated with main steam from the steam generators during the plant low power operation. Auxiliary boilers are used to supply steam when the main steam and the steam converter steam are not available. The capacities of the steam converter and the auxiliary boilers are determined based on requirements to supply the necessary amount of steam for the above mentioned components during the plant normal, start-up and shutdown operations.

Based on the requirements, auxiliary boilers and steam converters in a multi-unit plant usually have capacities of 0.02 ton/h* MWe and 0.03 ton/h • MWe, respectively; for a 4-loop unit this means approximately 20 ton/h-unit and 30 ton/h ■ unit, respectively. The auxiliary steam condenses in various components and flows down to and is stored in an auxiliary steam condensate tank. The condensate tank water is returned to the steam converter or the auxiliary boiler by auxiliary steam condensate pumps. Since such components as the boric acid evaporator and the liquid waste evaporator, carrying radioactive or potentially radioactive fluids are included in the load group heated by auxiliary steam, a radiation monitor is installed on the drain header from these components to detect any leakage of radioactive materials into the auxiliary steam system.

The components heated by the auxiliary steam are classified into two categories:

•Those components including the boric acid evaporator and the liquid waste evaporator, which carry radioactive or potentially radioactive fluids and therefore potentially can contaminate the auxiliary steam system; and

•Those components including the components of the heating, ventilating and air conditioning systems, which carry non-radioactive fluids and therefore have no possibility of contaminating

NSRA, Japan

3-120