Добавил:
Опубликованный материал нарушает ваши авторские права? Сообщите нам.
Вуз: Предмет: Файл:
01 POWER ISLAND / Overview of Light Water.docx
Скачиваний:
0
Добавлен:
01.04.2025
Размер:
8.88 Mб
Скачать

High Neutron Flux {Power Range High Selling)

High Neutron Flur Rate (Power Range High Selling)

High Reactor Pressure

Emergency Core Cooling Sywtem (ECCS) Actuation

Steam Generator Waler Level *1

Sleam Generator Feedaler Flow Level tl *

High Seismic Acceleration

Manual

High Neutron Flux (Power Range Low Setting)

High Neutron Flux

(Neutron Source Range and Intermediate Range)-, •

Low Reactor Pressure

High Pressurizer Waler Level

Low Reactor Coolant Flow Rate

Low Reactor Coolant Pump Power Voltage *2

Low Reactor Coolant Pump Frequency

Turbine Trip

Interlock

Losie Circuit

Reactor

Trip

Turbine Load Neutron Flux Level

Reactor Coolant Teiperature Difference AT

Reactor Coolant Average Teiperature T avg

Upper and LowerNcutron Flux Devialion Penalty Function f(Aq)—•

Over Poser AT High

Reactor Coolant Teiperature Difference AT

Seactor Coolant Average Teiperature T avg •

Pressurizer Pressure P

Over Teiperature AT High

1: Recent plants are slandardized to have a low sleam generator waler level.

2: Some plants use low reactor coolant pump speed

Figure 3.6.4 Reactor protection system block diagram

High Head Safety

Injection Pump Actuation

RHR Pump Actuation

Containment Isolation Annulus Air Cleanup Fan Actuation Containment Ventilation Isolation Auxiliary Feedwater Pump Actuation Feedwater isolation ( Reactor Trip ) (Emergency Diesel Generator Startup)

Steam Line Isolation

High-high Containment Pressure

.Manual Containment Spray Actuation

Containment Spray Actuation

Containment Isolation

Figure 3.6.5 Block diagram Illustrating engineered safety feature actuation

NSRA, Japan

3 ' 66

Chapter 3 Systems of PWR Nuclear Power Plants

Table 3.6.3 Function of reactor trip signals

Reactor Trip Signal

Function

(1) High Neutron Source Range Neutron Flux

To protect reactor against rapid increase of neutron flux at reactor start-mp and shutdown.

To trip reactor when measured value of ex core source range proportional counter exceeds the set value.

( 2) High Intermediate Range Neutron Flux

To trip reactor when measured point of ex-core ionization box exceeds the set value.

(3) High Power Range Neutron Flux

To trip reactor at high setting neutron flux during high power operation and at low setting neutron flux value during low power operation in order to assure integrity of fuel.

(4) High Power Range Neutron Flux Change Rate

Core flux distribution could be distorted beyond design value in case of rod ejection and drop of control rod clusters.

Power range neutron flux detectors detect such sudden change of neutron flux and trip reactor to prevent fuel damage.

(5) Over Temperature A|THigh

This signal protect fuel cladding from PNB by tripping reactor when the minimum DNBR in the core approches the design minimum low limit. (The minimum DNBR is not directly measured, but can be protected using Tavg, AT and P)

(6) Over Power AT High

This signal protects fuel from exceeding the maximum linear power by tripping reactor when measured AT corresponding to core power exceeds the permitted value.

AT corresponding to core poweri s corrected

with Tavg signal compensating for the dependecy on low coolant temperature.

(7) Low Reactor Pressure

To trip reactor when pressurizer pressure drops below the low pressure range of DNBR correlation of ''over temperature A T High” and also prevent excess boiling of primary coolant

( 8) HighReatctor Pressure

To trip reactor when pressurizer pressure exceeds the set value in order to limit the protection range of DNB by “over temperature AT high” and also prevent over pressurization of the reactor system before safety valves are opened.

( 9) Pressurizer later Level High

To prevent pressurizer from being filled with water and discharging liquid phase water through either safety valve or relief valve, although any direct damage is not expected by high level water.

(10) Reactor Coolent Flow Rate Low

To trip reactor during high power operation to prevent fuel damage, since low flow rate lowers heat removal capacity and causes DNB.

(11) Reactor Coolant Pump Power Voltge Low

Drop of power voltage to reactor coolant pump causes similar phenomena as low flow rate as described in item (10) abeve.

(12) Reactor Coolant Pump Power Frequency Low

Drop of power frequency causes low flow rate of reactor coolant pump and invite the similar phenomena as described in item (10) abeve.

(13) Actuation of Emergency Core Cooling System

To trip reactor by the actuation signal of emergency core cooling systme to be described later.

(14) Steam Generator rater Level Low (Note)

Drop of water level in steam generator may decrease heat removal capacity of primary coolant system.

(15) Steam Generator Feedwater Flow Rate Low (Note)

To trip reactor since low feedwater flow rate invite drop of water level in steam generator and may decrease heat removal capacity of primary coolant system.

(16) Turbine Trip

To trip reactor to prevent excess temperature rise and over pressurization of primary coolant system due to turbine trip.

(17) Seismic

Acceleration High

To trip reactor when either horizontal or vertical seismic acceleration exceeds the set points.

(18) Manual

To trip reactor by manual operation at the central control beard when operator needs emergency shutdown of reator.

[Note] Both are combined into "Steam Generator rater Level Low” signal in the recent plants.

3-67

NSRA, Japan

Table 3.6.4 List of engineering safety feature (ESF) actuation signals

Engineering Safety Feature Actuation Signal

Detector

Functional Logic

Interlock

Emegency Core Cooling System (ECCS) Actuation Signal

a. Low Reactor Pressure abnormally

Pressurizer Pressure Detector

2/4

Manual Block below (P-11)

b. Low Main Steam Line. Pressure

Main Steam Pressure Detector

1/4 of Low Main Steam Line Pressure

(2/4 for Each Line)

Manual Block below (P-11)

c. High Containment Vessel Pressure

Containment Pressure Detector

2/4

d. Manual

1/2

Main Steam Line Isoration Signal

a. High-high Containment Vessel Pressure abnormally

Containment Pressure Detector

2/4

b. Low Main Steam Line Pressure

Same as Emergency Core Cooling System (ECCS) Actuation Signal b.

Same as Emergency Core Cooling System (ECCS) Actuation Signal b.

Same as Emergency Core Cooling System (ECCS) Actuation Signal b.

c. High Main Steam Line Pressure Negative Rate

Main Steam Pressure Detector

1/4 of High Main Steam Line Pressure Negative Rate (2/4 for Each line)

Automatic Block above (P-11)

d. Manual

1/2

Containment Spray Actuation Signal

a. High-high Containment Pressure

Containment Pressure Detector

2/4

b. Manual

(2/2) xl/2

Containment Isolation Signal

a. Emergency Core Cooling System (ECCS) Actuation Signal

Same as Emergency Core Cooling System (ECCS) Actuation Signal

Same as Emergency Core Cooling System (ECCS) Actuation Signal

b. Containment Spray Actuation Signal

Same as Containment Spray Actuation Signal

Same as Contaminant Spray Actuation Signal

c. Manual

1/2

each train are capable to operate the associated equipment, so that a single component failure will not compromise the safety protection system function.

The conventional analog and logic circuits of the ESFs actuation system are nowadays being replaced by a digital control system using micro­processors for new plants and the conventional systems for operating plants are being replaced step-by-step.

  1. ESFs actuation signals and their functions

The ESFs actuation signals of a typical PWR plant are given in Table 3.6.4. Also, permissive

logic circuits are provided to allow startup and shutdown operation conditions without defeating the safety functions of the reactor system. The permissive signals associated with the ESFs actuation system are listed in Table 3.6.5.

Primary coolant discharge in an unlikely event of primary coolant system rupture, also known as the LOCA, results in a decrease in both pressurizer pressure and the pressurizer level as well as an increase in containment pressure. At this condition, a reactor pressure abnormally- low-signal, or a containment pressure-high signal causes the ECCS actuation signals.

NSRA, Japan

3-68

Chapter 3 Systems of PWR Nuclear Power Plants

Table 3.6.5 List of permissive signals of engineering safety feature (ESF) actuation signals

Symbols of Permissive Signals

Function

Input Signals

P-11

a.Permission for manual block of emergency core cooling system (ECCS) actuation signal due to abnormally low reactor pressure and low main steam line pressure

(Note)

2/3 of low pressurizer pressure

b.Permission for manual block of main steam line isolation signal due to low main steam line pressure

(Note)

2/3 of low pressurizer pressure

c.Automatic block of main steam line isolation signal due to high main steam line pressure decreesing rate

(Note)

2/3 of high pressurizer pressur

[Note] 2/4 instead of 2/3 in the recent

Uncontrolled steam discharge in an event of a steam line rupture, will result in steam pressure drop. At this condition, pressure-low signals from each steam line actuate the ECCS and close all steam line isolation valves to prevent blowdown flow of more than two steam-generators and maintain the reactor residual heat removal capability of the secondary system.

Also, either a primary or secondary system component rupture accident inside the containment structure, will increase the containment pressure which in turn, provides actuation signals for the ECCS, the main steam line isolation and the containment spray system which is provided for removal of iodine and containment depressurization.

The ECCS and containment spray system actuation signals provide signals for the containment isolation valves to isolate all systems other than those important for accident suppression. Further, each of the above mentioned actuation signals can be manually caused by the operators from the main control panel.

The reactor pressure abnormally-low-signal or the steam line pressure-low signal can be manually blocked by the pressurizer pressure- low input signal (permissive function P-11) to prevent unnecessary actuation of the ECCS during the plant cool down and heat up processes. Further, if the main steam line pressure-low signal is blocked, isolation of the main steam line is actuated by the main steam line pressure drop­rate-high signal.

c. Design philosophy of the safety protection system

High quality and high reliability are necessary

for the safety protection system to meet its performance requirements. Descriptions of the main design philosophies and design precedents of the safety protection system are given below.

  1. Redundancy

The safety protection system is designed with sufficient redundancy so that a single component failure will not compromise the system function.

  1. Independence

The redundant components of the safety protection system are designed and arranged to be electrically isolated and physically separated to achieve maximum independence and separation between them. Analog channels and logic trains (shown in Figure 3.6.3), as well as their electrical sources and cable trays, are all independent and physically separated from each other.

  1. Separation / interference of safety protection system from the control system

In PWR NPPs, the safety protection system is separated from the normal control system to the maximum practical extent possible to increase reliability of the safety protection system. However, if the control system signals are derived from a part of the safety system, they are sent through isolation amplifiers installed at signal branching points (Figure 3.6.6).

  1. Testing and calibrating

The safety protection system is designed to permit routine testing and calibrating during power operation without system trip, in order to demonstrate soundness of its functioning. Since its design provides sufficient redundancy and independence, the instrumentation channels and logic circuit trains can be tested separately, while the remaining parts of the system during the testing operation continue to meet the safety

3 ~ 69

NSRA, Japan