b)Axial wall-mount exhaust fans with hoods

c)Electric Unit Heaters (EUH)

d)Makeup Air Unit (MAU).

HVAC Controls:

a)HVAC controls shall be provided from a centrally located control panel and alarm to the central Control Room. DCS network wiring to the control room for all alarms shall be installed by plant contractor.

b)The HVAC controls shall include a graphical floor plan and Graphical User

c)Interface (GUI) touch screen panel for control

HVAC Design Standards / Reference

American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE)

ASHRAE Handbooks

ASHRAE 62.1

IMC

SMACNA HVAC Duct Construction Standards

NFPA 90A.

Site Security

The facility will use several measures to maintain security. A six-foot-high security fencing will be required as the entire work area is located outside the existing plant perimeter fencing. Fencing shall be grounded as required. A primary entrance to the facility will have manned guard. Throughout the facility will be cameras on a closed-circuit system will monitor the facility.

Plant Layout and Construction Access

The new carbon capture facility will consist of the equipment shown in the Plot Plan. A “mirrored” arrangement was selected to allow the construction site to be grouped into smaller unitized areas. Each unit area contains identical process equipment and components to its “mirrored” counterpart area. This