Добавил:
Опубликованный материал нарушает ваши авторские права? Сообщите нам.
Вуз: Предмет: Файл:
0 Standard / 02 JICA.2013 / Guide / Vol 4-Operation - Plants and Grid.pdf
Скачиваний:
1
Добавлен:
28.12.2023
Размер:
6.05 Mб
Скачать

(3)Transforming ratio test

By applying current to the primary circuit of CT, current and phase angle shall be measured at

CT test terminals in distribution boards that are connected to the secondary (tertiary) circuit of CT in order to check that transforming ratio and polarization as well as connection between the CT and distribution board are proper.

(4) Load measurement

With the subject CT being fully loaded, the secondary circuitof CT shall be applied with the rated current and comprehensive load including distribution board and control cable shall be measured in order to check that it is the same level as design value.

(5) Core check

While primary current is flowing through CT ina transformation ratio test, the secondary circuit of CT shall be suddenly short circuited at the terminal block, and it shall be checked that the

reading of ampere meter connected to distribution board drop to zero, thus the subject CT is connected to a proper destination.

Chapter 5 Completion Inspection

Section 1 General

Article 41. General provision

Completion inspection for facilities of overhead transmission lines, underground transmission lines and substations shall be carried out according to Chapter 5 in Part 2 in Technical Regulation Vol.5 and this Guideline.

Section 2

Overhead Transmission Line

Article 42.

Measurement of insulation resistance

Insulation resistance

of overheadtransmission lines shall satisfy inspection items in the following

table.

 

 

 

 

 

 

 

Table 42 Inspection of insulation of overhead transmission line

 

 

 

 

 

 

 

Items

 

 

Method

 

Acceptance criteria

 

 

 

 

 

 

 

 

 

 

 

- Insulation resistance measured by the megger

 

 

 

 

 

 

shall be more or equal to the following values.

 

 

 

 

 

- Between each phase and the ground : 4 ×106Ω

 

Insulation resistance

 

 

-

Between a phase and the other phases : 8 ×106 Ω

 

 

 

- The value measured at one minute after the

 

of overhead

 

Measurement

 

 

 

measurement was started shall basically be

 

transmission lines

 

 

 

 

 

 

 

adopted. In case that the value is not stable, it

 

 

 

 

 

 

should be measured after the value becomes

 

 

 

 

 

 

stable.

 

 

 

 

 

- Use 2,500V megger for testing.

 

 

 

 

 

 

 

 

61

Article 43. Phase test

Phase test of overhead transmission lines shall be complied with Article 19 in this Guideline.

Article 44. Power-frequency operating voltage test

Dielectric strength of overhead transmission lines shall satisfyinspection items of power frequency withstand voltage test in the following table.

Table 44 Inspection of power frequency withstand voltage test

Item

Method

Acceptance criteria

 

 

 

 

 

- Insulators shall be confirmed that they have

 

Document

prescribed dielectric strength by records of factory

 

 

test.

 

 

- Overhead transmission line shall be confirmed

Dielectric strength

 

that measured voltage between conductors

 

energized by power frequency voltage (voltage

 

 

 

Measurement

normally operated in the line) and the ground

 

 

which is recorded after one and ten minutes are

 

 

not significantly different from power frequency

 

 

voltage.

Section 3 Underground Transmission Lines

Article 45. Appearance inspection (Route exploration)

Appearance of cable lines shall satisfy inspection items in the following table.

Table 45 Inspection of appearance of cable

Items

Method

Acceptance criteria

 

 

 

 

 

- Kind, nominal cross sectional area and number of

 

 

cables shall be in accordance with the

 

 

specification.

 

 

- The position of connection boxes and terminal

 

 

boxes shall be in accordance with the

 

 

specification.

 

 

- Fixed condition of the cable, connection boxes,

 

 

terminal boxes and the grounding conductor shall

Appearance

Visual inspection

be in accordance with the specification.

- The steel cover of the cable well shall not be

 

 

 

 

damaged, and the installed condition of the cable

 

 

room shall be in accordance with the specification.

 

 

- Installed position and condition of the oil supply

 

 

system shall be in accordance with the

 

 

specification.

 

 

- Operating performance and installed condition of

 

 

alarm system shall be in accordance with the

 

 

specification.

62

Article 46. Measurement of insulation resistance

Insulation resistance of the cable shall be complied with Article 18 in this Guideline.

Article 47. Phase check

Phase test of underground transmission lines shall be complied with Article 19 in this Guideline.

Article 48. (moved to Article 26-a1)

Article 49. Clearance between live part and fence or wall

The clearance between live part exposed from cable lines and the fence or the wall shall be complied with Article 50 in this Guideline.

Section 4 Substation Equipment Article 50. Visual inspection

1. State of installation of equipment which generates arc

It shall be checked that the equipment which generates arc such as circuit breaker and disconnector is isolated from combustibles at a safe enough distanceThe. criteria of isolating distance between the equipment which generates arc and combustibles are shown in Table 50.

Table 50 Criteria of isolating distance between the equipment which generates arc and combustibles

Nominal voltage

Isolating distance *

 

 

7kV and less

1m and more

More than 7kV

2m and more

In case hat the direction and length of arc

are

restricted so that thereis no fear of fireand the

1m and more

nominal voltage is 35kV and less.

 

* Note: The abovedistance shall not be applied when fireproof materials are installed between the equipment which generates arc and combustibles.

2. State of installation of charged part

It shall be carried out according to the inspection items specified separately inArticle 335, 337, 338, and 343 of Volume 1.

3. Testing of installation of fence, wall

The height of fence and wall, and the various types of minimum clearance such as protective barrier clearance, boundary clearance, minimum height over accessible area and building clearanceshall be carried out according to the inspection items specified separately inArticle 335, 337, 338, 343 and 349 of Volume 1.

63

Article 51. Measurement of grounding resistance

Grounding resistance shall be measured to confirm that the measured value meets standards provided in Article 572 of the Volume 1.

Article 52. Supervisory and control test

1. Switching test

By operating circuit breaker, disconnector, etc. which are controlled from the control room or load dispatch center, it shall be checked that each equipment works properly and the indication in the control room or load dispatch center changes correspondingly. Inaddition, switching indicator of the controlled equipment shall also be checked to work properly.

2. On-load tap changer test

By giving tap-changing instruction from the control room or load dispatch center to the transformer, it shall be checked that the tap changes in accordance with the instructionIt shall. be carried out according to the inspection items specified separately in item 8. (1) of Article27.

3. Protective device test, Alarm indication test

By activating relay compulsorily for every protective device or alarm device, it shall be checked that the operation of the related equipment and the indication in the control room or load dispatch center correspond exactly to the design diagram.

4. Actual Loading Test for protective relay and control equipment

As a final check using voltage and current on actual power system, the following testsbeshall implemented.

(1)Voltage and phase check

It shall be confirmed that the phase arrangement meets the design diagram by measuring and comparing the voltage of testing line and another charged line.The voltage shall be measured at test terminals on distribution boards.

(2)Voltage, current and phase angle measurement

Voltage, current and phase shall be measured at test terminalson distribution boards. It shall be confirmed that the measured voltage and current are appropriate considering the PT and CT ratio and that the phase differences between measured values are appropriate considering the polarity and connection of PT and CT.

(3)Directional test

It shall be confirmed that the direction, polarity and phase difference of measured voltage and current are appropriate.

(4)Residual current and voltage measurement

Residual current and voltage shall be measured to confirm that the measured value corresponds to the imbalance if there is an imbalance among three phase current or voltage.

(5)Id (differential current) check

Differential current shall be measured to confirm that the measured value is nearly equal to 0 in a normal state.

64

Article 53. Interlock test

It shall be carried out according to the inspection items specified separately in Article 31.

Article 54.

(moved to Article 27-34, 36-38)

Article 55.

(deleted)

Article 56.

Measurement of noise and vibration

(1) Measurement of noise and vibration

Noise and vibration level shall be measured at the boundary of a substation yard. It shall be confirmed that the measured value is within the local regulation such as Table6-1 and5 562-. In case of measurement, the influence of sound sources besides the substation shall be excluded.

Table 56-1 Maximum permissible noise levels in public and residential areas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(dB)

Area

 

 

 

 

 

 

 

 

 

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

From 6am to

 

From 6pm to

 

From 10pm to

 

 

 

 

 

6pm

 

 

 

10pm

 

 

6am

 

1. The places requiring special silence:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

hospitals, schools, libraries, sanatorium,

 

 

 

 

50

 

 

 

 

45

 

 

40

 

churches, temples

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. Residential areas, hotels, resorts,

 

 

 

 

60

 

 

 

 

55

 

 

50

 

administrative offices

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Residential areas alternated with

 

 

 

 

75

 

 

 

 

70

 

 

50

 

commercial, service, productive areas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 56-2 Sound pressure levels at working places

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equivalent

Sound level at

octaves

of medium

frequencies (Hz)

 

sound

not exceeding (dB)

 

 

 

 

 

 

 

Working place

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

level

63

 

125

 

250

 

500

 

1000

 

2000

 

4000

 

8000

 

(dBA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

At working, production

85

99

 

92

 

86

 

83

 

80

 

78

 

76

 

74

places

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote control room,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

experimental rooms with

80

94

 

87

 

82

 

78

 

75

 

73

 

71

 

70

noise resources

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote control room,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

experimental rooms

70

87

 

79

 

72

 

68

 

65

 

63

 

61

 

59

without noise resources

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Functional rooms

65

83

 

74

 

68

 

63

 

60

 

57

 

55

 

54

(accounting, statistics etc.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Research, design,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

computer, experimental

55

75

 

66

 

59

 

54

 

50

 

47

 

45

 

43

and data treatment rooms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

Соседние файлы в папке Guide