Annex II.2.1 (I.3A)

Rated electricity currents and some technical parameters of XLPE and EPR kV,24 one phase and 3 phase cables

Technical parameters of XLPE 24kV 3 phase copper core cables

Cross

Resistance of core

Self

Capacita

Rated

 

Rated

Nominal

Test

section

 

 

induction

nce

current in

 

current in

short

voltage

DC

AC

area

coefficient

cable

earth

a

air

circuit

 

20oC

20oC

(kV/5

cable

(/km)

(/km)

(mH/km)

(µF/km)

20oC (A)

 

30oC (A)

current at

minutes)

(mm2)

 

 

 

 

 

 

 

1s (kA)

 

 

 

 

 

 

 

 

 

 

 

3x35

0.524

0.668

0.373

0.110

120

 

113

5.04

30

 

 

 

 

 

 

 

 

 

 

3x50

0.387

0.493

0.358

0.117

170

 

163

7.30

30

 

 

 

 

 

 

 

 

 

 

**

0.641

0.822

 

 

134

 

127

4.65

 

 

 

 

 

 

 

 

 

 

 

3x70

0.268

0.342

0.340

0.128

210

 

201

10.08

30

 

 

 

 

 

 

 

 

 

 

**

0.443

0.568

 

 

164

 

157

6.51

 

 

 

 

 

 

 

 

 

 

 

3x95

0.193

0.246

0.325

0.138

250

 

242

13.68

30

 

 

 

 

 

 

 

 

 

 

**

0.320

0.410

 

 

195

 

189

8.83

 

 

 

 

 

 

 

 

 

 

 

3x120

0.153

0.195

0.315

0.146

284

 

278

17.28

30

 

 

 

 

 

 

 

 

 

 

**

0.253

0.324

 

 

222

 

217

11.16

 

 

 

 

 

 

 

 

 

 

 

3x150

0.124

0.158

0.305

0.155

321

 

317

21.60

30

 

 

 

 

 

 

 

 

 

 

**

0.206

0.264

 

 

251

 

247

13.95

 

 

 

 

 

 

 

 

 

 

 

3x185

0.099

0.126

0.297

0.163

358

 

356

26.64

30

 

 

 

 

 

 

 

 

 

 

**

0.164

0.210

 

 

282

 

281

17.21

 

 

 

 

 

 

 

 

 

 

 

3x240

0.075

0.096

0.285

0.176

411

 

415

34.56

30

 

 

 

 

 

 

 

 

 

 

**

0.125

0.160

 

 

325

 

327

22.32

 

 

 

 

 

 

 

 

 

 

 

3x300

0.060

0.077

0.279

0.184

462

 

472

43.20

30

 

 

 

 

 

 

 

 

 

 

**

0.010

0.128

 

 

368

 

376

27.90

 

 

 

 

 

 

 

 

 

 

 

(**) Aluminum core

294

Technical parameters of cable Cu/Al - XLPE - 24kV - 3 phase

 

Cross

DC at 20oC (/km)

Self

 

Capacita

 

Rated

Rated

Nominal

 

 

Test

 

 

section

 

 

 

 

induction

 

nce

 

current

current

short

 

 

voltage

 

 

area

 

 

 

 

coefficie

 

cable

 

in

earth

in

o

air at

circuit

 

 

(kV/5

 

 

cable

 

 

 

 

nt

 

 

 

 

at

o

30

C (A)

current

 

 

 

 

 

 

 

 

 

(µF/km)

 

20C

 

 

 

minutes)

 

 

(mm2)

 

 

 

 

(mH/km)

 

 

(A)

 

 

 

 

 

at

1s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC

AC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20oC

90oC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(/km)

(/km)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x50

0.387

0.493

0.399

 

0.100

 

164

 

 

205

 

 

7.20

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

0.641

0.822

 

 

 

 

 

 

130

 

 

151

 

 

4.65

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x70

0.268

0.342

0.378

 

0.109

 

202

 

 

245

10.08

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

0.443

0.568

 

 

 

 

 

 

158

 

 

180

 

 

6.51

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x95

0.193

0.246

0.361

 

0.117

 

234

 

 

280

13.68

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

0.320

0.410

 

 

 

 

 

 

182

 

 

217

 

 

8.83

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x120

0.153

0.195

0.350

 

0.123

 

270

 

 

320

17.28

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

0.253

0.324

 

 

 

 

 

 

208

 

 

247

11.16

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x150

0.124

0.158

0.338

 

0.131

 

304

 

 

356

21.60

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

0.206

0.264

 

 

 

 

 

 

234

 

 

281

13.95

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x185

0.099

0.126

0.328

 

0.137

 

338

 

 

415

26.64

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

0.164

0.210

 

 

 

 

 

 

265

 

 

327

17.21

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x240

0.075

0.096

0.314

 

0.148

 

390

 

 

472

34.56

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

0.125

0.160

 

 

 

 

 

 

307

 

 

376

22.32

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(**) Aluminum core

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Technical parameters of cable Cu/Al - XLPE - 24kV - 3 phase

 

 

 

 

 

 

 

 

 

Cross

 

DC at 20oC (/km)

 

Self

 

Capacita

 

Rated

 

 

Rated

 

 

Nominal

 

Test

 

 

section

 

 

 

 

 

induction

 

nce

 

current

 

 

current

 

 

short

 

 

 

voltage

 

 

 

DC

 

atAC

 

 

 

 

 

 

 

 

 

area

o

 

 

coefficient

 

cable

 

in

air

at

 

in air

at

 

circuit

 

 

 

 

 

 

 

 

20oC

 

90oC

 

 

 

 

 

 

 

 

(kV/5

 

 

cable

 

(/km)

 

(/km)

 

(mH/km)

 

(µF/km)

 

30oC (A)

 

30oC (A)

 

current

 

minutes)

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at

1s

 

 

 

(mm )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x240

 

0.0754

 

0.098

 

0.287

 

 

0.176

 

 

 

411

 

 

 

415

 

 

33.80

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.125

 

0.162

 

0.287

 

 

0.284

 

 

 

325

 

 

 

327

 

 

22.2

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(**) Aluminum core

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

295

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Technical parameters of cable Cu/Al - XLPE - 24kV - 1 phase

Cross

 

DC at 20oC (/km)

Self

Capacita

Rated

Rated

Nominal

Test

section

 

induction

nce

current

current

short

 

voltage

 

 

 

 

 

 

 

 

area

o

 

 

 

 

 

 

coefficie

cable

in

earth

in air at

circuit

 

(kV/5

DC

AC

 

cable

 

nt

 

at

20 oC

30oC (A)

current

 

(µF/km)

minutes)

 

 

20

o

C

90

o

C

(mH/km)

(A)

 

at

1s

(mm2)

 

 

 

 

 

 

 

(/km)

(/km)

 

 

 

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1x35

 

0.514

0.655

0.541

0.142

 

154

136

5.04

 

30

 

 

 

 

 

 

 

 

 

 

 

 

1x50

 

0.379

0.483

0.523

0.155

 

180

279

7.2

 

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.628

0.805

 

 

 

141

217

4.65

 

 

 

 

 

 

 

 

 

 

 

 

 

1x70

 

0.262

0.334

0.500

0.174

 

219

347

10.08

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.435

0.558

 

 

 

171

270

6.51

 

 

 

 

 

 

 

 

 

 

 

 

 

1x95

 

0.189

0.241

0.482

0.193

 

2

420

13.68

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.313

0.401

 

 

 

203

328

8.83

 

 

 

 

 

 

 

 

 

 

 

 

 

1x120

 

0.150

0.191

0.471

0.207

 

293

483

17.28

30

 

 

 

 

 

 

 

 

 

 

 

**

 

0.248

0.318

 

 

 

230

378

11.16

 

 

 

 

 

 

 

 

 

 

 

 

1x150

 

0.122

0.156

0.459

0.225

 

320

540

21.60

30

 

 

 

 

 

 

 

 

 

 

 

**

 

0.202

0.259

 

 

 

254

425

13.95

 

 

 

 

 

 

 

 

 

 

 

 

1x185

 

0.097

0.124

0.450

0.242

 

359

614

26.64

30

 

 

 

 

 

 

 

 

 

 

 

**

 

0.161

0.206

 

 

 

285

485

17.21

 

 

 

 

 

 

 

 

 

 

 

 

1x240

 

0.074

0.094

0.436

0.271

 

410

718

34.56

30

 

 

 

 

 

 

 

 

 

 

 

**

 

0.122

0.156

 

 

 

329

573

22.32

 

 

 

 

 

 

 

 

 

 

 

 

1x300

 

0.059

0.075

0.429

0.290

 

455

813

43.20

30

 

 

 

 

 

 

 

 

 

 

 

**

 

0.098

0.125

 

 

 

368

652

27.90

 

 

 

 

 

 

 

 

 

 

 

 

1x400

 

0.046

0.059

0.418

0.325

 

494

904

57.60

30

 

 

 

 

 

 

 

 

 

 

 

**

 

0.076

0.098

 

 

 

408

740

37.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(**) Aluminum core

296

Technical parameters of cable Cu/Al - XLPE - 24kV - 3 phase

Cross

 

Core resistance

Self

Capacitanc

Rated

Rated

Nominal

Test

section

 

induction

e of cable

current

current

short

voltage

 

 

 

area

o

 

 

coefficien

(µF/km)

in

earth

in air at

circuit

(kV/5

DC

AC

 

 

t

 

o

 

o

 

current

cable

 

20oC

90oC

 

at

20C

30

 

C (A)

minutes)

(mm2)

 

(/km)

(/km)

(mH/km)

 

(A)

 

 

 

at

1

 

 

 

 

 

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x35

 

0.521

 

0.424

0.12

 

164

 

173

 

5.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.868

 

 

 

 

127

 

139

 

3.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x50

 

0.387

 

0.406

0.13

 

194

 

206

 

7.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.641

 

 

 

 

148

 

161

 

4.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x70

 

0.268

 

0.388

0.14

 

236

 

257

 

10.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.443

 

 

 

 

179

 

199

 

6.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x95

 

0.193

 

0.364

0.16

 

283

 

313

 

13.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.320

 

 

 

 

214

 

242

 

8.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x120

 

0.153

 

0.346

0.18

 

322

 

360

 

17.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.253

 

 

 

 

246

 

280

 

11.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x150

 

0.124

 

0.333

0.19

 

362

 

410

 

21.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.206

 

 

 

 

246

 

318

 

14.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x185

 

0.099

 

0.323

0.21

 

409

 

469

 

26.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.164

 

 

 

 

308

 

365

 

17.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x240

 

0.075

 

0.313

0.23

 

474

 

553

 

34.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.125

 

 

 

 

358

 

425

 

22.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x300

 

0.060

 

0.301

0.25

 

533

 

629

 

42.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.100

 

 

 

 

398

 

481

 

28.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x400

 

0.047

 

0.291

0.28

 

597

 

717

 

57.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.078

 

 

 

 

446

 

553

 

37.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(**) Aluminum core

297

Technical parameters of cable Cu/Al - XLPE - 24kV - 1 phase

Cross

 

DC at 20oC (/km)

Self

Capacitan

Rated

Rated

 

Nominal

Test

section

 

induction

ce

current

current

 

short

 

voltage

 

 

 

 

 

 

area

o

 

 

 

coefficient

cable

in earth

in

air

at

circuit

 

(kV/5

DC

 

AC

 

cable

 

20oC

 

90oC

(mH/km)

(µF/km)

at 20oC

30oC (A)

current

minutes)

(mm2)

 

 

 

(A)

 

 

 

at

1

 

(/km)

 

(/km)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1x240

 

0.074

 

0.094

0.436

0.271

490

 

 

 

34.56

30

 

 

 

 

 

 

 

 

 

 

 

 

 

1x300

 

0.059

 

0.075

0.429

0.290

 

 

 

 

43.20

30

 

 

 

 

 

 

 

 

 

 

 

 

 

1x400

 

0.046

 

0.059

0.418

0.325

 

 

 

 

57.60

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Technical parameters of cable Cu/Al - XLPE - 24kV - 3 phase

 

 

Cross

 

DC at 20oC (/km)

Self

Capacitan

Rated

Rated

 

Nominal

Test

section

 

 

 

 

induction

ce

current

current

 

short

 

voltage

area

o

DC

 

AC

coefficient

cable

in earth

in

air

at

circuit

 

(kV/5

cable

 

20oC

 

90oC

(mH/km)

 

at 20oC

30oC (A)

current

 

 

(µF/km)

minutes)

(mm2)

 

(/km)

 

(/km)

 

(A)

 

 

 

at

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x240

 

0.0754

 

0.0980

0.320

0.287

 

 

718

 

107.8

30

 

 

 

 

 

 

 

 

 

 

 

 

 

3x300

 

0.059

 

0.075

0.429

0.290

 

 

813

 

43.20

30

 

 

 

 

 

 

 

 

 

 

 

 

 

3x400

 

0.046

 

0.059

0.418

0.325

 

 

904

 

57.60

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Technical parameters of cable Cu/Al - XLPE - 24kV - 3 phase

Cross

 

Core resistance

Self

Capacitan

Rated

Rated

Nominal

Test

section

 

induction

ce

current

current

short

 

voltage

 

 

 

 

area

o

 

 

coefficient

cable

in earth

in air at

circuit

 

(kV/5

DC

AC

 

cable

 

(mH/km)

 

o

30

o

C (A)

current

 

 

 

 

20oC

90oC

(µF/km)

at 20 C

 

minutes)

(mm2)

 

 

(A)

 

 

 

at

1

 

(/km)

(/km)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x240

 

0.0754

0.0777

0.301

0.288

425

 

718

109.0

30

 

 

 

 

 

 

 

 

 

 

 

 

 

298

Underground cable Cu-EPR - 24kV - 3x24

(Protected with gas bag)

Cross

 

Core resistance

Self

Capacitan

Rated

Rated

Nominal

Test

section

 

induction

ce

current

current

short

 

voltage

 

 

 

 

area

o

DC

AC

coefficient

cable

in earth

in air at

circuit

 

(kV/5

cable

 

20oC

90oC

(mH/km)

 

at 20oC

30oC (A)

current

 

(µF/km)

minutes)

 

 

(/km)

(/km)

 

(A)

 

at

1

2

 

 

 

 

 

(mm )

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x240

 

0.0754

0.0981

0.306

0.325

569

718

108

30

 

 

 

 

 

 

 

 

 

 

 

Underground cable Cu-EPR - 24kV - 3 phase

(Protected with two steel layers)

Cross

 

Core resistance

Self

Capacitan

Rated

Rated

Nominal

Test

section

 

 

 

induction

ce

current

current

short

voltage

 

DC

AC

area

o

20oC

90oC

coefficient

cable

in earth

in air at

circuit

(kV/5

cable

 

(/km)

(/km)

(mH/km)

µ

at 20oC

30oC (A)

current

minutes)

2

 

 

( F/km)

(A)

 

at

1

 

(mm )

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x35

 

0.524

0.67

0.377

0.136

180

190

 

5

30

 

 

 

 

 

 

 

 

 

 

 

**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x50

 

0.387

0.49

0.362

0.149

210

225

 

7

30

 

 

 

 

 

 

 

 

 

 

 

**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x70

 

0.268

0.34

0.344

0.169

260

280

 

10

30

 

 

 

 

 

 

 

 

 

 

 

**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x95

 

0.193

0.25

0.328

0.190

310

330

 

13.5

30

 

 

 

 

 

 

 

 

 

 

 

**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x120

 

0.153

0.20

0.318

0.206

350

380

 

17

30

 

 

 

 

 

 

 

 

 

 

 

**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x150

 

0.124

0.16

0.310

0.220

390

430

 

21.5

30

 

 

 

 

 

 

 

 

 

 

 

**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x185

 

0.0991

0.13

0.300

0.243

440

485

 

26.5

30

 

 

 

 

 

 

 

 

 

 

 

**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x240

 

0.0754

0.10

0.289

0.270

505

560

 

34

30

 

 

 

 

 

 

 

 

 

 

 

**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x300

 

0.0601

0.08

0.281

0.294

570

630

 

43

30

 

 

 

 

 

 

 

 

 

 

 

**

 

 

 

 

 

 

 

 

 

 

3x400

 

0.047

 

0.273

0.326

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

299

Technical parameters of cables - XLPE - 24kV - 3 phase

Cross

 

Core resistance

Self

Capacitan

Rated

Rated

Nominal

Test

section

 

induction

ce

current

current

short

 

voltage

 

 

 

 

 

area

o

DC

t

aAC

coefficient

cable

in earth

in air at

circuit

 

(kV/5

cable

 

20oC

 

90oC

(mH/km)

 

at 20oC

30oC (A)

current

 

 

(µF/km)

minutes)

 

 

(/km)

 

(/km)

 

(A)

 

at

1

(mm2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1x35

 

0.524

 

 

0.377

0.136

185

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

 

 

 

 

 

140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1x50

 

0.387

 

 

0.362

0.140

220

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.641

 

 

 

 

170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1x70

 

0.268

 

 

0.344

0.169

265

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.443

 

 

 

 

205

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1x95

 

0.193

 

 

0.328

0.190

320

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.320

 

 

 

 

240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1x120

 

0.153

 

 

0.318

0.206

360

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.253

 

 

 

 

275

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1x150

 

0.124

 

 

0.310

0.220

405

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.206

 

 

 

 

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1x185

 

0.0991

 

 

0.300

0.243

460

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.164

 

 

 

 

340

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1x240

 

0.0754

 

 

0.289

0.270

535

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.125

 

 

 

 

385

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1x300

 

0.0601

 

 

0.281

0.294

605

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.01

 

 

 

 

430

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1x400

 

0.047

 

 

0.273

0.326

690

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.0778

 

 

 

 

475

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300

Technical parameters of cables - XLPE - 24kV - 3 phase

Cross

 

Core resistance

Self

Capacitan

Rated

Rated

Nominal

Test

section

 

induction

ce

current

current

short

voltage

 

 

 

 

 

 

 

area

o

 

 

coefficient

cable

in earth

in air at

circuit

 

DC

AC

(kV/5

cable

 

20

o

C

90

o

C

(mH/km)

(µF/km)

at 20oC

30oC (A)

current

minutes)

 

 

 

 

 

(A)

 

at

1

(mm2)

 

(/km)

(/km)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

1x35

 

0.524

0.655

0.49

0.16

179

197

 

5.18

30

 

 

 

 

 

 

 

 

 

 

 

1x50

 

0.387

0.483

0.466

0.17

212

235

 

7.36

30

 

 

 

 

 

 

 

 

 

 

 

**

 

0.641

0.805

 

 

164

182

 

4.89

 

 

 

 

 

 

 

 

 

 

 

1x70

 

0.268

0.334

0.447

0.2

259

293

10.26

30

 

 

 

 

 

 

 

 

 

 

 

**

 

0.443

0.558

 

 

201

227

 

6.81

 

 

 

 

 

 

 

 

 

 

 

1x95

 

0.193

0.241

0.424

0.22

309

354

13.88

30

 

 

 

 

 

 

 

 

 

 

 

**

 

0.320

0.401

 

 

239

275

 

9.19

 

 

 

 

 

 

 

 

 

 

 

1x120

 

0.153

0.191

0.407

0.24

349

408

17.49

30

 

 

 

 

 

 

 

 

 

 

**

 

0.253

0.318

 

 

273

317

11.58

 

 

 

 

 

 

 

 

 

 

 

1x150

 

0.124

0.156

0.399

0.25

390

461

21.81

30

 

 

 

 

 

 

 

 

 

 

**

 

0.206

0.259

 

 

304

359

14.43

 

 

 

 

 

 

 

 

 

 

 

1x185

 

0.0991

0.124

0.387

0.28

440

527

26.86

30

 

 

 

 

 

 

 

 

 

 

**

 

0.164

0.206

 

 

344

411

17.76

 

 

 

 

 

 

 

 

 

 

 

3x240

 

0.0754

0.0981

0.373

0.31

508

621

34.78

30

 

 

 

 

 

 

 

 

 

 

**

 

0.125

0.156

 

 

400

488

22.98

 

 

 

 

 

 

 

 

 

 

 

1x300

 

0.0601

0.075

0.359

0.33

571

708

43.41

30

 

 

 

 

 

 

 

 

 

 

**

 

0.100

0.125

 

 

450

557

28.67

 

 

 

 

 

 

 

 

 

 

 

1x400

 

0.047

0.059

0.353

0.37

602

811

57.79

30

 

 

 

 

 

 

 

 

 

 

**

 

0.0778

0.098

 

 

486

645

38.14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

301

Technical parameters of cables - XLPE - 24kV - 3 phase

Cross

 

Core resistance

Self

Capacita

Rated

Rated

Nominal

Test

section

 

induction

nce

current

current

short

voltage

 

 

 

 

 

 

 

area

o

DC

AC

coefficient

cable

in

earth

in air at

circuit

(kV/5

cable

 

20

o

C

90

o

C

(mH/km)

 

at

o

30

o

C (A)

current

 

 

 

(µF/km)

20C

 

minutes)

 

 

(/km)

(/km)

 

(A)

 

 

 

at

1

(mm2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x35

 

0.524

 

 

 

0.377

0.136

 

171

 

173

 

5.18

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x50

 

0.387

 

 

 

0.362

0.149

 

202

 

206

 

7.36

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.641

 

 

 

 

 

 

154

 

161

 

4.49

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x70

 

0.268

 

 

 

0.344

0.169

 

246

 

257

10.26

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.443

 

 

 

 

 

 

191

 

199

 

6.81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x95

 

0.193

 

 

 

0.328

0.190

 

295

 

313

13.88

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.320

 

 

 

 

 

 

228

 

242

 

9.19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x120

 

0.153

 

 

 

0.318

0.206

 

335

 

360

17.49

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.253

 

 

 

 

 

 

260

 

280

11.58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x150

 

0.124

 

 

 

0.310

0.220

 

376

 

410

21.81

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.206

 

 

 

 

 

 

292

 

318

14.43

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x185

 

0.0991

 

 

 

0.300

0.243

 

425

 

459

26.86

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.164

 

 

 

 

 

 

331

 

365

17.76

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x240

 

0.0754

 

 

 

0.289

0.270

 

492

 

553

34.78

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.125

 

 

 

 

 

 

385

 

425

22.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x300

 

0.0601

 

 

 

0.281

0.294

 

554

 

629

43.41

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.01

 

 

 

 

 

 

437

 

481

28.67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3x400

 

0.047

 

 

 

0.273

0.326

 

625

 

554

57.79

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

 

0.0778

 

 

 

 

 

 

495

 

437

38.14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

302

Underground cables - XLPE - 14kV - 3 phase

Cross

 

Core resistance

Self

Capacitan

Rated

Rated

Nominal

Test

section

 

induction

ce

current

current

short

voltage

 

 

 

area

o

DC

AC

coefficient

cable

in earth

in air at

circuit

(kV/5

cable

 

20oC

90oC

(mH/km)

 

at 20oC

30oC (A)

current

 

(µF/km)

minutes)

 

 

(/km)

(/km)

 

(A)

 

at

1

(mm2)

 

 

 

 

 

 

 

 

 

 

 

 

 

(kA)

 

 

 

 

 

 

 

 

 

 

 

 

3x35

 

0.524

0.668

 

0.157

 

 

 

5.0

 

 

 

 

 

 

 

 

 

 

 

 

3x50

 

0.387

0.494

 

0.172

 

 

 

7.2

 

 

 

 

 

 

 

 

 

 

 

 

3x70

 

0.268

0.342

 

0.195

 

 

 

10.0

 

 

 

 

 

 

 

 

 

 

 

 

3x95

 

0.193

0.247

 

0.216

 

 

 

13.6

 

 

 

 

 

 

 

 

 

 

 

 

3x120

 

0.153

0.196

 

0.236

 

 

 

17.2

 

 

 

 

 

 

 

 

 

 

 

 

3x150

 

0.124

0.159

 

0.255

 

 

 

21.5

 

 

 

 

 

 

 

 

 

 

 

 

3x185

 

0.099

0.127

 

0.276

 

 

 

26.5

 

 

 

 

 

 

 

 

 

 

 

 

3x240

 

0.075

0.098

 

0.308

 

 

 

34.3

 

 

 

 

 

 

 

 

 

 

 

 

3x300

 

0.060

0.079

 

0.342

 

 

 

42.9

 

 

 

 

 

 

 

 

 

 

 

 

3x400

 

0.047

0.063

 

0.38

 

 

 

57.2

 

 

 

 

 

 

 

 

 

 

 

 

B - Conversion coefficient of load current of XLPE cables 1. Cable directly buried in earth

Conversion coefficient of cable load carrying capacity according to earth temperature

Earth temperature (oC)

20

 

25

 

30

 

 

 

35

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conversion coefficient

1.08

 

1.04

 

1.00

 

0.96

 

0.91

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current conversion coefficient for cable by earth resistivity

 

 

 

 

Earth resistivity (oC cm/W)

70

 

 

 

100

 

150

 

 

 

250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conversion coefficient

1.12

 

 

 

1.0

 

 

0.87

 

 

 

0.7

 

 

 

 

 

 

 

 

 

 

 

Current conversion coefficient of cable by its buried depth

 

 

 

 

Depth of cable placement

50

 

70

100

 

120

 

160

 

200

 

 

 

 

 

 

 

 

 

 

 

Conversion coefficient

1.02

 

1.0

0.98

 

0.97

 

0.95

 

0.94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

303

Conversion coefficient for group of multi-core cables

 

Shape

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Group number

1

2

 

3

 

 

4

 

5

 

 

6

 

8

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conversion coefficient

1.0

0.86

 

0.76

 

 

0.71

 

0.67

 

0.64

 

0.60

 

0.57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conversion coefficient for group pf cables arranged on one plane

 

 

 

 

 

 

 

Shape

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Group number

 

 

1

 

 

2

 

3

 

 

4

 

5

 

6

 

 

8

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conversion coefficient

 

 

1.00

 

 

0.87

 

0.77

 

 

0.73

 

0.70

 

0.68

 

0.65

 

 

0.63

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conversion coefficient for group one-core cables arranged in triangle

 

 

 

 

Shape

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Group number

 

1

 

2

 

3

 

 

4

 

5

 

 

6

 

 

8

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conversion coefficient

 

1.00

 

0.89

 

0.82

 

 

0.78

 

0.75

 

0.73

 

0.70

 

 

0.68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. Cables placed in air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conversion coefficient by air temperature

 

 

 

 

 

 

 

 

 

 

 

Air temperature (oC)

 

20

 

25

 

30

 

 

 

35

 

40

 

45

 

50

 

 

Conversion coefficient

 

1.08

 

1.04

 

1.00

 

 

0.96

 

0.91

 

0.87

 

0.82

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

304

Conversion coefficients for one-phase cables arranged on one plane

Distance to wall 2cm

Number of circuits

Picture (trang 95)

Distance between cables is

1

2

3

 

equal to diameter d of cable

Conversions coefficient

 

Cables buried in earth

0.92

0.89

0.88

 

 

 

Number of racks

 

 

 

 

Cables

 

1

0.92

0.89

0.88

 

placed

o

2

0.87

0.84

0.83

Picture (trang 95)

racks

 

3

0.84

0.82

0.81

 

 

 

6

0.82

0.80

0.79

 

 

 

Number of racks

 

 

 

 

Cables

 

1

1.00

0.97

0.96

 

placed

o

2

0.97

0.94

0.93

Picture (trang 95)

racks

 

3

0.96

0.93

0.92

 

 

 

6

0.94

0.91

0.90

 

Arranged near to wall

0.94

0.91

0.89

Picture (trang 95)

 

 

 

 

 

 

 

Arranged near to wall

0.89

0.86

0.84

Picture (trang 95)

 

 

 

 

Current conversion coefficient for one phase cables in 3-phase power system and arranged in triangle

Distance to wall 2cm

Number of circuits

 

 

 

 

 

Distance between cables is

1

2

3

Picture (trang 96)

equal to 2d of cable

Conversion coefficient

 

 

 

 

 

 

 

Cables buried in earth

0.95

0.90

0.88

 

 

 

 

 

 

 

 

Number

 

 

 

 

 

racks

0.90

0.90

0.88

 

Cables

1

0.85

0.85

0.83

Picture

place

2

0.83

0.83

0.81

racks

 

 

3

0.81

0.81

0.79

 

 

6

 

 

 

 

 

 

 

 

 

 

 

Number

 

 

 

 

 

racks

1.00

0.98

0.96

 

Cables

1

1.00

0.95

0.93

Picture

place

2

1.00

0.94

0.92

racks

 

 

3

1.00

0.93

0.90

 

 

6

 

 

 

 

 

 

 

 

 

 

Arrangement without conversion of current

 

Picture

 

 

 

 

 

 

305

Conversion coefficient for single core cables placed on one plane

Distance to wall 2cm

 

Number of circuits

 

 

 

 

 

 

 

 

 

 

Distance

between

cables i

 

 

 

 

 

Picture trang 97

1

2

3

6

9

equal diameter d of cable

 

 

 

 

 

 

 

 

 

 

Conversion coefficient

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cables buried in earth

 

0.95

0.90

0.88

0.85

0.84

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

 

 

 

 

 

 

 

Cables

 

racks

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

placed

o

 

 

 

 

 

 

 

 

 

 

 

racks

 

 

 

 

 

 

0.95

0.90

0.88

0.85

0.84

Picture

 

 

 

 

1

 

(limited

air

 

 

 

 

0.90

0.85

0.83

0.81

0.80

 

 

 

 

 

 

 

ventilation)

 

 

 

2

 

 

 

 

 

 

0.88

0.83

0.81

0.79

0.78

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

0.86

0.81

0.79

0.77

0.76

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

 

 

 

 

 

 

 

 

 

racks

 

 

 

 

 

 

 

 

Cables

 

 

 

 

 

 

1.00

0.98

0.96

0.93

0.92

Picture

o

 

 

 

1

 

placed

 

 

 

 

1.00

0.95

0.93

0.90

0.89

 

racks

 

 

 

 

2

 

 

 

 

 

 

 

3

 

1.00

0.94

0.92

0.89

0.88

 

 

 

 

 

 

 

1.00

0.93

0.90

0.87

0.86

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cables

placed

near

to

1.00

0.93

0.90

0.87

0.86

Picture

wall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Arrangement

t

 

Distance

 

 

 

 

 

 

ensure

 

 

 

 

to

wal

Distance between cables > 2d

 

Picture

carrying

capacity

 

 

of cables

 

 

 

 

> 2 cm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

306

Conversion coefficient for one-core aluminum cables arranged on one plane

 

 

 

 

Number of circuits

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cables adjacent to wall

 

1

 

2

 

3

 

6

9

Picture trang 98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conversion coefficient

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cables placed in ground

 

0.90

0.84

 

0.80

 

0.75

 

0.73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

of

 

 

 

 

 

 

 

 

 

 

 

 

support

 

 

 

 

 

 

 

 

 

 

 

Cables

 

racks

 

 

 

 

 

 

 

 

 

 

 

placed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

0.95

0.84

 

0.80

 

0.75

 

0.73

Picture

racks

 

 

 

 

 

 

 

 

 

 

 

(limited

ai

2

 

0.95

0.80

 

0.76

 

0.71

 

0.69

 

ventilation)

 

 

 

 

 

 

 

 

3

 

0.95

0.78

 

0.74

 

0.70

 

0.68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

0.95

0.76

 

0.72

 

0.68

 

0.66

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

of

 

 

 

 

 

 

 

 

 

 

 

 

support

 

 

 

 

 

 

 

 

 

 

 

 

 

racks

 

 

 

 

 

 

 

 

 

 

 

Cables

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

0.95

0.84

 

0.80

 

0.75

 

0.73

Picture

placed

 

 

 

 

 

 

 

 

 

 

 

racks

 

2

 

0.95

0.80

 

0.76

 

0.71

 

0.69

 

 

 

 

 

 

 

 

 

 

 

3

 

0.95

0.78

 

0.74

 

0.70

 

0.68

 

 

 

 

 

 

 

 

 

 

 

6

 

0.95

0.76

 

0.72

 

0.68

 

0.66

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cables placed on structure

0.95

0.78

 

0.73

 

0.68

 

0.66

Picture

or near to wall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 