
reading / British practice / Vol D - 1990 (ocr) ELECTRICAL SYSTEM & EQUIPMENT
.pdf
Technical requirements
power stations, the electrical auxiliary system to which the motors are connected is subject to high fault levels, so the effects of an electrical fault must be taken into account in the design of the terminal arrangement and terminal box to prevent a possible explosion due to the rapid heating of gas in a confined space with risk of injury to personnel or damage to plant (see Schwarz 1962 [61).
|
|
|
The CEGB requirements are summarised as follows: |
||
|
|
• Minimum electrical clearance and creepage distances |
|||
|
|
|
are specified. |
|
|
|
|
• |
Terminal boxes must be suitable for the type and |
||
|
|
|
size of cable to be used. |
||
|
|
• |
Terminal boxes for 415 V motors up to 75 kW shall |
||
|
|
|
be totally enclosed (IP 54) but may be open to the |
||
|
|
|
interior of the motor. Above 75 kW, the terminal |
||
|
|
|
boxes must be constructed of steel, be totally enclos- |
||
|
|
|
ed (IP 57) and sealed from the motor interior. |
||
|
|
• |
For 3.3 kV motors, a standard terminal box has |
||
|
|
|
been developed in conjunction with manufacturers. |
||
|
|
|
This is totally-enclosed (EP 57), phase-insulated, |
||
|
|
|
and of the pressure-relief type, with fully-insulated |
||
|
|
|
terminals. Maximum fault capacity 250 MVA. Maxi- |
||
|
|
|
mum current rating 290 A. For use with three- |
||
|
|
|
core, plastic-insulated cables up to 300 mm 2 , solid |
||
|
|
|
aluminium or copper conductor. Figure 7.14 shovis |
||
|
|
|
details of this terminal box. |
||
|
|
• |
For 11 kV motors, a standard terminal box has |
||
|
|
|
been developed in conjunction with manufacturers. |
||
|
|
|
This is totally-enclosed (IP57), phase-segregated, |
||
|
|
|
and of the pressure-relief type, with fully-insulated |
||
|
|
|
terminals. Maximum fault capacity 750 MVA. Maxi- |
||
|
|
|
mum current rating 650 A. For use with three single- |
||
|
|
|
core, polymeric-insulated cables up to 500 mm 2 , |
||
|
Typical arrangement of an oil lubricated |
|
with moulded elbow-type connector. Figure 7.15 |
||
7 .13 |
|
shows details of this terminal box. |
|||
|
sleeve-type bearing |
|
|
|
|
|
|
• |
Terminal boxes for ?-3.3 kV to be type-tested to |
||
H We same type in order to ensure that incorrect |
|
withstand internal short-circuit and through-fault |
|||
|
current capability. |
|
|||
di , :ribution of bearing loads does not occur due to |
|
|
|||
|
|
|
|||
differences in shaft lift during run-up, or of different |
|
|
|
||
idtcs of bearing wear, |
4 Technical requirements |
||||
ProN.ision |
must be made for the prevention of |
||||
|
|
|
|||
idin3ge to bearings by any shaft currents which may |
Some of the principal requirements of CEGB power |
||||
kc produced by uneven fluxes in the magnetic circuit |
station motors are given below. EEC documents equi- |
||||
H the motor. This is achieved by insulating the |
valent to BS are also given. |
||||
!' ,:arintls, if shaft currents are likely to occur. |
|
|
|
||
fable 7.4 gives details of the CEGB practice for |
Relevant standards: BS5000, Part 40 |
||||
l'cahnL, applications. |
|||||
|
|
BS4999, Parts 10, 20, 21, 30, 32, |
|||
|
|
|
|
||
|
|
|
|
33, 41, 50, 51, 60 (IEC 34, Parts |
|
3.7 Terminal boxes |
|
|
1, 2 and 4 to 10). |
||
Particular attention has to be given to the design of the |
|
|
ESI Standards 44-3, 44-4, 44-5. |
||
|
|
|
|||
:Lirininal arrangements and of terminal boxes in order |
|
|
|
||
lo achieve a high degree of reliability and also to faci- |
Service conditions: Ambient air 40° C (max) |
||||
late installation of the power supply cables. Within |
(normal) |
Cooling water 30 ° C (max) |
637

0)
co
GLASS POLYESTER TERMINAL BASE
MOTOR
CONNECTING
FLEXIBLE CABLE
111
PRESSURE RELIEF DIAPHRAGM
PROTECTIVE |
A |
MESH GRID |
■
CABLE SPACING
BLOCK
Section Through Box
TERMINAL BOX
LID
EARTHED STEEL
FLASHPLATE
NEOPRENE
RUBBER CAP
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0 |
|
|
|
|
|
0 |
|
|
|
|
|
|
|
|
0 |
|
|
|
|
|
I |
0 |
|
|||
|
|
|
|
|
|
|
|
_1_1=1_1___ |
|
|
|
|
|
|
|
|
|
|
|
|||||||||
|
|
(0 |
|
|
|
|
|
0 |
|
|
|
|
0 |
|
|
|
I |
0 |
|
|||||||||
|
|
|
t |
|
I |
|
|
|
|
|
|
|
|
|
|
|
|
/ |
I |
|
|
|
||||||
|
|
|
I |
\ |
|
|
|
|
|
|
|
|
|
|
|
|
|
/ |
/ |
|
|
|
|
|||||
|
|
o |
\ |
\ |
|
|
|
|
I |
I |
|
|
|
|
|
/ |
|
/ |
|
|
o |
|
||||||
|
|
\ |
\ |
\ |
|
|
|
|
|
|
|
|
|
/ |
|
|
/ |
|
|
|
||||||||
|
|
|
\ |
|
|
|
|
|
|
j |
|
|
|
/ |
|
/ |
|
|
|
|
||||||||
|
|
|
|
|
|
\ |
|
\ |
\.\ |
|
|
|
|
/ |
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
// |
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
\ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
\ |
|
|
|
V |
|
|
|
/ |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 CORE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
I |
7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
POWER SUPPLY '- |
|
|
|
|
|
|
|
|
|
I I |
I |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
CABLE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
I |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1,) |
|
|
|
|
|
|
0 |
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
_ _11 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
View on Front with Lid Removed
Fla- 7.14 3.3 kV ( 1 . (■ 11/B1.AN1A l Jrfl IuI 1)1. ■■

JOINT ACCESS COVER |
|
|
|
CONNECTOR |
VOLTAGE TES i |
||
|
|
POINT cap |
|
MOTOR CONNECTING FLEXIBLE CABLE
BUSHING
/ JOINT INSULATION
PRESSURE
RELIEF
DIAPHRAGM
PROTECTIVE
MESH GRID
STRESS
RELIEF
ADAPTOR
EARTHED STEEL ARC BARRIER
Section through Terminal Box
TERMINAL BOX//
LID
VOLTAGE TEST POINT
SPADE TERMINAL
o |
|
|
|
_ |
|
|
|
0 |
|||||||
|
p |
||||||
|
|
|
n
0
|
|
|
|
|
|
o |
|
|
|
|
|
0 |
|||||
|
|
|
|||
|
A—
SINGLE CORE POWER SUPPLY CABLE
View on Front with
0
/,'0- a
0 )
0 (
)
n |
0 |
|
0
0 |
|
_,.. |
' .,.,• |
Y,1, e |
0 |
|
Lid Removed
Fiu. 7.15 11 kV CEGI1/131:AMA 14:Emilia] Iro.
sluat.ua.i!nbai leD)ukpai
Motors |
Chapter 7 |
|
|
Temperature rises: |
To BS4999, Part 32 (IEC 34 — |
|
1), except that temperature |
|
rise of Class F insulation to |
|
be to limits of Class B. |
Rating: |
Maximum continuous rating. |
Nlinicaurn |
SO'''n rated voltage |
daring star:ing |
|
period: |
|
Variation of |
94% to 106a voltage and 9607o |
voltage and |
to 102% Hz. |
frequency: |
Capable of continued operation |
|
at 75 0'ii voltage for 5 minutes |
|
without injurious heating. |
Transient recovery: To recover after a power supply system disturbance causing loss of voltage for 0.2 seconds, followed by sudden restoration to 60% voltage for 3 seconds,
|
followed by restoration to 80% |
|
voltage, and then ultimate re- |
|
covery to normal. |
Starting (locked- |
Selected from BS4999, Part 41 |
rotor) kVA for |
(see Table 7.1) |
cage induction |
|
motors: |
|
Locked-rotor |
Must be adequate to meet re- |
torque for cage |
quirements of driven load, but |
induction motors: |
in any event CEGB practice |
|
requires the values to be not |
|
less than those given in BS4999, |
|
Part 41. |
Starting (run-up) |
The accelerating torque at any |
torque of cage |
speed and 80 07o voltage must |
induction motors: |
be not less than 10% of motor |
|
rated load. The motor starting |
|
(run-up) torque at 100% volt- |
|
age must also be not less than |
|
1.7 times the torque obtained |
|
from a load torque which var- |
|
ies as the square of the speed |
|
and is equal to 100% torque |
|
at full speed. |
Maximum (pull-out) 200% full-load torque torque:
Noise levels: Uo BS4999, Part 51, except that in no case shall the mean sound pressure level exceed 87dB(A) at 1 metre from the surface of the machine.
Harmonics: |
Voltage distortion less than |
(AC converter |
with individual harmonic corn- |
drives) |
ponents to IEC 146-2. |
Nuclear |
Qualification of Class 1E safety- |
qualification: |
related motors to IEEE 334. |
5 Power station auxiliary drives
Details of some of the more i mportant motor auriliary drives required on a modern CEGB power station with 660 MW turbine-generator (TG) units are given belmk, and also in Table 7.4.
5.1 Boiler feed pumps
The normal arrangement adopted currently by CEGS is for I x 100 070 steam turbine-driven feed pump, with
2 x 50% starting and standby motor-driven sariable. speed feed pumps. Motor-driven suction stage pumps are also required for the feed pumps.
Since the motor-driven feed pumps are required for starting and standby duty only, the choice of motor is largely dictated by first cost. Variable-speed sliprinct motors with variable rotor resistance liquid type controllers have been used. Squirrel-cage induction motors
with speed control by hydraulic couplings |
have also |
been used, particularly for nuclear power |
stations, |
where starting is required infrequently.
The variable-speed slipring induction motors are typically 1480 r/min (maximum), 9 MW, 11 kV, starting current 100% full load, 50 Hz, with speed variation 100% to 70% by rotor-resistance control, with liquidtype speed controllers. The feed pump is driven through speed-increasing gears at 8000 r/min (maximum). Three x 50% duty suction stage pumps are provided, driven by 1000 kW, 1480 r/min cage induction motors. Figure 7.16 shows a typical slipring induction motor reed pump drive.
With the cage induction motor drive, the motors are typically 1480 r/min, 10 MW, 11 kV, 50 MVA at start, 50 Hz, driving through hydraulic couplings with speed variation 100-70%. These are mechanically coupled to the feed pumps via speed-increasing gearboxes at 8000 r/min (maximum) pump speed. The suction stage pump is rated at 1000 kW, 1480 r/min and is coupled to a shaft extension of the main drive motor.
5.2 Coaland oil-fired boiler units
5.2.1 Draught plant
The practice is to install two induced-draught and two forced-draught fans per boiler unit, each working at full-load when the boiler is at continuous maximum
rating (CMR). It is possible to run the boiler unit at reduced load in the event of failure of one of the fans.
although it is expected that this condition would nol be allowed to continue for any length of ti me. The
640

Power station auxiliary drives
|
|
|
|
|
|
|
STATOR 'WINDINGS |
|
|
|
||||
|
|
|
|
|
|
|
|
COOLING FAN |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
• |
|
|
|
|
AIR DUCTS |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SLiP RING COVER |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2_— |
- |
|
__ROTOR WINDINGS |
|
||||||
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
• |
|
|
|
|
|
|
Fo OR RHI ipE STAGE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
■,ICV AB L |
|
|
|
|
|
|
|
|
PECESTAL EARTHED |
|||||
|
|
|
|
|
|
, |
|
|
|
r |
||||
|
|
|
|
|
|
|
|
|
THROUGH REMOVABLE |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
C O P P E S T R P |
oT H E RW I S E FULLY INSULATED
DIRECTION OF
AIR FLOW
„
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L |
ING |
|
|
|
|
|
|
|
|
|
HEAT EXCHANGER |
|||||
|
|
L jri_ET |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TUBES |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
- - 3 CL c,LLY |
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
PPINGS |
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
HEAT EXCHANGER |
||||||
|
|
|
|
|
|
|
|
|
HEAT EXCHANGER |
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
COOLING WATER |
|
|
||
|
|
|
|
|
|
|
|
|
|
VENTILATORS |
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
COOLING WATER |
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
INLET |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OUTLET |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
BRUSHES |
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
INSPECTION WINDOWS |
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
FIG. 7.16 Typical slipring induction-motor feed pump drive |
|||||||||
• |
for the motors to be single-speed cage induction |
be installed in each reactor to circulate the primary |
•.although two-speed cage induction and variablecoolant CO2 through the reactor core and boilers.
iitator-fed AC commutator motors have been i[lie moments of inertia of the fans are high, being ciI ti mes those of their respective motors, which rein relatively long run-up times, typically 50 to 80 s.
5 2.2 |
Milling plant |
|
|||
|
IIlIlliIlg |
plant comprises the coal pulveriser mill, |
|||
, |
- |
|
air Ian (or exhauster fan), coal feeder and |
||
|
|
|
|
||
|
,ir ,Ar or. Standby capacity is provided. The pulveriser |
||||
|
|
Luallv |
need More |
maintenance than any other |
|
|
, |
|
ill |
the station: |
for this reason, the running |
|
|
|
|
|
|
|
iiiindby units are frequently interchanged. Coal |
||||
|
[ |
Cr wills require a |
high starting torque (typically |
||
|
i) and a relatively high number of starts per hour |
||||
|
CLaJIV |
six). The vibration level of the plant is also |
|||
|
ill |
C2]\ |
high and a robust motor is therefore required. |
||
|
- enclosed air cooled squirrel-cage motors are |
proi.ided.
5 .3 Nuclear reactors — AGR
5 3. 1 Gas circulators
pical arrangement is for eight gas circulators to
Two basic configurations are in common use in the CEGB, horizontal and vertical; this description concentrates on the vertical configuration, but many of the principles apply to both. Figure 7.17 shows the location of a vertically-opposed gas circulator in a nuclear reactor at Heysham I power station.
Each gas circulator is a single-stage centrifugal type, delivering 461 kg/s of CO2 at 41 bar and a temperature of 287 ° C. The inlet gas temperature to the circulator is 278 ° C and the pressure rise across the circulator is 2.83 bar.
The circulator is driven at 3000 r/min by an 11 kV motor mounted below the impeller on the circulator shaft (see Fig 7.18). A 415 V pony motor, mounted on the circulator shaft below the main motor, drives the circulator at barring speeds below 350 r/min. The motor unit for each circulator is encapsulated and comprises the composite assembly of main motor, pony motor, rotor shaft, bearings, impeller, inlet guide vanes and isolating dome operating mechanism. This assembly is contained completely within the reactor pressure boundary. The circulator unit can be withdrawn and replaced for maintenance with the reactor depressurised.
The impeller shaft passes through a barrier plate which is provided with a labyrinth seal to minimise
641

Mot ors |
Chapter 7 |
|
|
LOCATION OF GAS CIRCULATOR
Fu. 7.17 Posiiion of gas circulator unit within AGR reactor
hot gas flow between the motor compartment and the reactor. The impeller operates in reactor gas at nearly 300 ° C, whereas the motor is isolated thermally to operate at temperatures of about 60 ° C. Although normal operation is in CO2 at 41 bar, the circulator must be capable of operation in air at atmospheric pressure (or reduced CO2 pressure) for commissioning, maintenance or during fault conditions.
motor
The circulator main drive motor is an 11 kV, two-pole squirrel-cage induction machine contained completely within the reactor pressure boundary. The motor, mounted on the circulator rotor shaft with the 415 V pony motor, rotates at a nominal speed of 3000 r/min and maximum continuous rating of 5.59 MW.
The motor is designed to I3S2613 Class F insulation, but operates normally within Class B temperature li mits, The motor is capable of operating continuously, at rated torque, at any frequency between 48 and 51 Hz and at any voltage between ±5% of the nominal value.
The motors are designated for 'essential duty' and are capable of continuous operation at 75% nominal volts at 50 Hz for a period of 5 minutes without injurious heating. They are also capable of recovering normal operation in the event of a system disturbance
causing temporary loss of supply voltage for periods of up to three seconds, followed by a sudden restoration initially to 80% nominal voltage.
The motor stator windings and laminations are con. tam ed within the main motor outer frame which is a mild steel cylindrical ribbed fabrication with top and bottom flanges (see Fig 7.19). The top flange aligns with the lower face of the top bearing bath and the bottom flange aligns with the bottom bearing batch assembly and incorporates holes for the motor securing bolts. The stator and outer frame complete weicth s approximately 14.5 tonnes.
The rotor is fitted on the forged carbon steel shaft together with the impeller, drive-end bearing sleeve, motor cooling fan, pony motor rotor, non-reverse clutch, pulsing disc and non-drive end thrust collar (see Fig 7.20).
Intensive research, development and full-scale t!stin g were required to establish the design of these ors, which have to operate under arduous conditio . The motor has also to withstand specified radiatio•: levels and also operate with contamination from lubricating oil mist. All these presented problems; in particular, the design of bearings under high rates of change of pressure of the ambient gas, the insulation system, the electrical design and thermal design. These are discussed in more detail (see Schwarz 1973 l7j).
A very high reliability is required, particular' the units are inside the reactor pressure cm and even apart from safety aspects, any 1: outage can be very costly.
5.4 Nuclear reactors — PWR
5.4.1 Reactor coolant pumps
A typical arrangement is four reactor cook: per reactor which are located within the re:. tainment. The pump unit consists of a vert:.
stage centrifugal-type pump, with vertical dr. .tor mounted above the pump and directly coupled to it. The motor has a drip-proof enclosure, but the cooling air outlet is water cooled. A flywheel is located at the top of the motor to provide the required coastdown capability in the event of loss of electrical power supply to the motor. This limits the transient temperatures within the reactor under such conditions. The motor must withstand specified radiation levels within the containment.
Figure 7.21 is a cutaway view of a typical reactor coolant pump and motor unit.
5.4.2 Safety-related drives
There are a number of drives, classified as safety-related category Class 1E to IEEE Standard 334, which are essential for the safety of the reactor during normal periods of shutdown or emergency periods following loss-of-coolant accidents which could involve severe
642

Power station auxiliary drives
1
F
F LOW
STRAIGHTENER
CONE
I MPELLER
D.E. OIL BATH
AND COOLER
ROTOR
11kV MAIN MOTOR
415V PONY MOTOR
SPEED SENSING
HEAD
NON REVERSE
CLUTCH
N.D.E. OIL BATH
AND COOLER
I. G V. OPERATING
SHAFT
ENO ENCLOSURE
PLATE
I G.V. GEARBOX
FIG. 7.18 Sectional arrangement of a gas circulator
643

Motors |
Chapter 7 |
|
|
-I
-1
I |
• |
A |
4 |
|
'
|
|
|
|
|
TERMINALS |
LOCATION OF |
|
|
|
||
MAIN MOTOR |
|
|
STATOR WITHDRAWN
FROM FRAME
OUTER |
CLAMPS |
|
FRAME |
TERMINALS |
PERIM |
|
1111601111. |
Medealte, |
|
IgneaMONOM, 1020.N. |
AngarArg• |
|||
AgrArmismordoir ~roe• |
- |
411=1.111111111111111hk |
||
|
|
|||
4 |
|
|
44L |
|
V. |
|
|
11°tit- |
|
|
|
|
_ roc |
|
|
|
|
|
|
|
|
|
NON-DRISE |
|
DRIVE |
|
|
|
|
|
||||
|
END |
|
|
|
|
|
|
ENO |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
COILS |
|
STATOR |
LOCKING |
|||
|
|
|
|
FR,. 7.19 Gas circulator — main motor stator and outer frame |
PLATE |
|
|
||
|
|
|
|
|
|
|
644

Testing
|
|
|
|
|
|
|
|
|
|
|
|
PONY |
|
|
|
|
MOTOR ROTOR |
|||
|
|
|
|
|
|
|
BALANCE |
|
|
|
|
|
|
WEiGHT |
|
\\ |
|
1 |
|
|
|
|
|
|
|||
|
|
1 |
|
—
|
|
|
|
|
|||
|
|
FAN |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CLUTCH AND PULSFNG |
|
|
|
|
|
MAIN |
|
DrSC, ASSEMBLY |
|
:MPELLER |
|||||||
|
|
|
MOTOR ROTOR |
|
|
||
|
|
||||||
|
|
|
|
|
|
|
|
|
Fu.j. 7.20 Gas circulator — main motor rotor |
|
-Aliation, thermal and environmental stresses. The test -,quirements to be met in order to qualify or prove
Jc2S[oT1 and reliability of such motors are given a IEEE. 334. Examples are motors for centrifugal
Airing pumps, high head safety injection pumps and :t2st,lual heat-removal containment spray pumps.
5.5Circulating water pumps
ii c usual arrangement of the cooling water system is system, in which the cooling water is taken to a ,tommon chamber whence a number of pumps dis-
.ii.iree into a common bus-main supplying all the conrisers in the station. In view of the vital importance tit the cooling water to the station output and in preplant damage due to loss of cooling water, spare
capacity is installed.
i - }1,2 motors are usually of the cage induction type. some installations use vertically-mounted motors, ,, ii cre-as others are horizontal. Figure 7.22 shows a vertical-shaft circulating water pump motor. The
.:iips are usually of low speed (typically 500 down to r min). With pump speeds lower than about 500 - ruin, it is usual to provide a motor driving through a cd-reducing gearbox, this being the most economic
saratieement.
rite more usual arrangement is to provide a pumpsometimes with removable or sliding roof for tii. Mitenance purposes. Both drip-proof and totally-
.::,.iosed motors have been used. The tendency is the totally-enclosed type, which gives greater ittroteetion against contamination of the windings. At Power stations, the stator windings are some-
. mcs additionally of the sealed type to protect against saline conditions.
6 Testing
'2 ling can be categorised into two groups: develop-
LI1I
and works testing.
The development of new designs and techniques, new materials and component parts is a research and development activity. Verification of the properties, performance, etc., must be obtained and is usually achieved by a testing process. Simulation methods may have to be used in some cases where direct testing is not possible or practical, e.g., accelerated ageing tests on insulation systems, where, for example, a relationship between voltage, temperature and time to breakdown can be established and the tests made at elevated temperatures and voltages. Fatigue testing of bars of cage induction motors is another example, where such tests are made to establish the total number of starts that can safely be made during the life of the motor.
Works testing on the completed motor needs to be made to verify that the motor is electrically and mechanically sound and that the stated performance characteristics are achieved. Such tests are categorised into basic and routine tests. Basic tests are in general made on the first motor of each type and routine tests on all other motors. Table 7.5 lists the individual test requirements for induction motors.
|
TABLE |
7.5 |
|
|
Works tests on induction motors |
|
|||
|
|
|
|
|
|
Test |
|
Basic |
Routine |
|
|
|
|
|
Resistance of windings (cold) |
|
\ |
,.-- |
|
No load losses and current |
|
\ |
,- |
|
|
1 |
|||
Locked rotor — |
current |
|
...- |
|
|
1 |
|||
— |
torque |
|
|
|
|
|
|
||
Starting (run-up) torque characteristics |
|
|
||
for cage motors over 375 kW |
|
\ |
|
|
Direct-on start at full voltage |
|
|
,..-- (_?..3.3 kV) |
|
(cage motors) |
|
|
\ |
|
Rotor open-circuit induced |
|
|
,-- |
|
voltage (slipring) |
|
|
\ |
|
Temperature rise test |
|
|
|
|
Power factor and efficiency |
|
1 |
|
|
Speed control (variable-speed slipring) |
|
|||
\ |
|
|||
|
|
|
|
|
Maximum (pull-out) torque |
|
\ |
|
|
Vibration measurement |
|
\ |
|
|
Noise level |
|
|
\ |
|
|
|
|
|
|
645

Motors |
Chapter 7 |
|
cL,WHF.EL
RACIA L
"H.uST
NE 3 SEAL LEAK OFF
CASING
I 51PELLER
SUCTION NOZZLE
FIG. 7.21 Reactor coolant pump and motor unit
7 Future trends
Motors for power station auxiliary drives are likely to continue to grow, both in power requirement and complexity. More emphasis is likely to be placed on the achievement of high reliability, due to increasing costs of unplanned outages, and on safety to personnel. This implies extension of and/or improvements to existing testing techniques and could include tests to determine the permissible number of direct-on-line starts in the life of cage induction motors. With increasing attention being given to the conservation of energy, improvement in operating efficiencies will be
sought. Improved materials will continue to be developed. These could include lubricating grease with a higher withstand-temperature and improved capability of insulation systems.
The use of motors having brushes, sliprings and commutators is likely to continue to be avoided. An increasing use of AC variable-speed converter drives is forecast, particularly with improvements in tech-
niques and reduction in cost of converter equipment. Linear motors are likely to find an increasing number
of applications where linear motion is required, such as cranes and sliding doors.
646