Добавил:
Опубликованный материал нарушает ваши авторские права? Сообщите нам.
Вуз: Предмет: Файл:

reading / British practice / Vol D - 1990 (ocr) ELECTRICAL SYSTEM & EQUIPMENT

.pdf
Скачиваний:
9
Добавлен:
17.07.2023
Размер:
30.18 Mб
Скачать

Technical requirements

power stations, the electrical auxiliary system to which the motors are connected is subject to high fault levels, so the effects of an electrical fault must be taken into account in the design of the terminal arrangement and terminal box to prevent a possible explosion due to the rapid heating of gas in a confined space with risk of injury to personnel or damage to plant (see Schwarz 1962 [61).

 

 

 

The CEGB requirements are summarised as follows:

 

 

• Minimum electrical clearance and creepage distances

 

 

 

are specified.

 

 

 

Terminal boxes must be suitable for the type and

 

 

 

size of cable to be used.

 

 

Terminal boxes for 415 V motors up to 75 kW shall

 

 

 

be totally enclosed (IP 54) but may be open to the

 

 

 

interior of the motor. Above 75 kW, the terminal

 

 

 

boxes must be constructed of steel, be totally enclos-

 

 

 

ed (IP 57) and sealed from the motor interior.

 

 

For 3.3 kV motors, a standard terminal box has

 

 

 

been developed in conjunction with manufacturers.

 

 

 

This is totally-enclosed (EP 57), phase-insulated,

 

 

 

and of the pressure-relief type, with fully-insulated

 

 

 

terminals. Maximum fault capacity 250 MVA. Maxi-

 

 

 

mum current rating 290 A. For use with three-

 

 

 

core, plastic-insulated cables up to 300 mm 2 , solid

 

 

 

aluminium or copper conductor. Figure 7.14 shovis

 

 

 

details of this terminal box.

 

 

For 11 kV motors, a standard terminal box has

 

 

 

been developed in conjunction with manufacturers.

 

 

 

This is totally-enclosed (IP57), phase-segregated,

 

 

 

and of the pressure-relief type, with fully-insulated

 

 

 

terminals. Maximum fault capacity 750 MVA. Maxi-

 

 

 

mum current rating 650 A. For use with three single-

 

 

 

core, polymeric-insulated cables up to 500 mm 2 ,

 

Typical arrangement of an oil lubricated

 

with moulded elbow-type connector. Figure 7.15

7 .13

 

shows details of this terminal box.

 

sleeve-type bearing

 

 

 

 

 

Terminal boxes for ?-3.3 kV to be type-tested to

H We same type in order to ensure that incorrect

 

withstand internal short-circuit and through-fault

 

current capability.

 

di , :ribution of bearing loads does not occur due to

 

 

 

 

 

differences in shaft lift during run-up, or of different

 

 

 

idtcs of bearing wear,

4 Technical requirements

ProN.ision

must be made for the prevention of

 

 

 

idin3ge to bearings by any shaft currents which may

Some of the principal requirements of CEGB power

kc produced by uneven fluxes in the magnetic circuit

station motors are given below. EEC documents equi-

H the motor. This is achieved by insulating the

valent to BS are also given.

!' ,:arintls, if shaft currents are likely to occur.

 

 

 

fable 7.4 gives details of the CEGB practice for

Relevant standards: BS5000, Part 40

l'cahnL, applications.

 

 

BS4999, Parts 10, 20, 21, 30, 32,

 

 

 

 

 

 

 

 

33, 41, 50, 51, 60 (IEC 34, Parts

3.7 Terminal boxes

 

 

1, 2 and 4 to 10).

Particular attention has to be given to the design of the

 

 

ESI Standards 44-3, 44-4, 44-5.

 

 

 

:Lirininal arrangements and of terminal boxes in order

 

 

 

lo achieve a high degree of reliability and also to faci-

Service conditions: Ambient air 40° C (max)

late installation of the power supply cables. Within

(normal)

Cooling water 30 ° C (max)

637

0)

co

GLASS POLYESTER TERMINAL BASE

MOTOR

CONNECTING

FLEXIBLE CABLE

111

PRESSURE RELIEF DIAPHRAGM

PROTECTIVE

A

MESH GRID

CABLE SPACING

BLOCK

Section Through Box

TERMINAL BOX

LID

EARTHED STEEL

FLASHPLATE

NEOPRENE

RUBBER CAP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

0

 

 

 

 

 

 

 

 

0

 

 

 

 

 

I

0

 

 

 

 

 

 

 

 

 

_1_1=1_1___

 

 

 

 

 

 

 

 

 

 

 

 

 

(0

 

 

 

 

 

0

 

 

 

 

0

 

 

 

I

0

 

 

 

 

t

 

I

 

 

 

 

 

 

 

 

 

 

 

 

/

I

 

 

 

 

 

 

I

\

 

 

 

 

 

 

 

 

 

 

 

 

 

/

/

 

 

 

 

 

 

o

\

\

 

 

 

 

I

I

 

 

 

 

 

/

 

/

 

 

o

 

 

 

\

\

\

 

 

 

 

 

 

 

 

 

/

 

 

/

 

 

 

 

 

 

\

 

 

 

 

 

 

j

 

 

 

/

 

/

 

 

 

 

 

 

 

 

 

 

\

 

\

\.\

 

 

 

 

/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

//

 

 

 

 

 

 

 

 

 

 

 

 

 

\

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

\

 

 

 

V

 

 

 

/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 CORE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

7

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY '-

 

 

 

 

 

 

 

 

 

I I

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1,)

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

_ _11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

View on Front with Lid Removed

Fla- 7.14 3.3 kV ( 1 . (■ 11/B1.AN1A l Jrfl IuI 1)1. ■■

JOINT ACCESS COVER

 

 

 

CONNECTOR

VOLTAGE TES i

 

 

POINT cap

 

MOTOR CONNECTING FLEXIBLE CABLE

BUSHING

/ JOINT INSULATION

PRESSURE

RELIEF

DIAPHRAGM

PROTECTIVE

MESH GRID

STRESS

RELIEF

ADAPTOR

EARTHED STEEL ARC BARRIER

Section through Terminal Box

TERMINAL BOX//

LID

VOLTAGE TEST POINT

SPADE TERMINAL

o

 

 

 

_

 

 

0

 

p

 

 

 

n

0

 

 

 

 

 

o

 

 

 

 

0

 

 

 

 

A—

SINGLE CORE POWER SUPPLY CABLE

View on Front with

0

/,'0- a

0 )

0 (

)

n

0

 

0

0

 

_,..

' .,.,•

Y,1, e

0

 

Lid Removed

Fiu. 7.15 11 kV CEGI1/131:AMA 14:Emilia] Iro.

sluat.ua.i!nbai leD)ukpai

Motors

Chapter 7

 

 

Temperature rises:

To BS4999, Part 32 (IEC 34

 

1), except that temperature

 

rise of Class F insulation to

 

be to limits of Class B.

Rating:

Maximum continuous rating.

Nlinicaurn

SO'''n rated voltage

daring star:ing

 

period:

 

Variation of

94% to 106a voltage and 9607o

voltage and

to 102% Hz.

frequency:

Capable of continued operation

 

at 75 0'ii voltage for 5 minutes

 

without injurious heating.

Transient recovery: To recover after a power supply system disturbance causing loss of voltage for 0.2 seconds, followed by sudden restoration to 60% voltage for 3 seconds,

 

followed by restoration to 80%

 

voltage, and then ultimate re-

 

covery to normal.

Starting (locked-

Selected from BS4999, Part 41

rotor) kVA for

(see Table 7.1)

cage induction

 

motors:

 

Locked-rotor

Must be adequate to meet re-

torque for cage

quirements of driven load, but

induction motors:

in any event CEGB practice

 

requires the values to be not

 

less than those given in BS4999,

 

Part 41.

Starting (run-up)

The accelerating torque at any

torque of cage

speed and 80 07o voltage must

induction motors:

be not less than 10% of motor

 

rated load. The motor starting

 

(run-up) torque at 100% volt-

 

age must also be not less than

 

1.7 times the torque obtained

 

from a load torque which var-

 

ies as the square of the speed

 

and is equal to 100% torque

 

at full speed.

Maximum (pull-out) 200% full-load torque torque:

Noise levels: Uo BS4999, Part 51, except that in no case shall the mean sound pressure level exceed 87dB(A) at 1 metre from the surface of the machine.

Harmonics:

Voltage distortion less than

(AC converter

with individual harmonic corn-

drives)

ponents to IEC 146-2.

Nuclear

Qualification of Class 1E safety-

qualification:

related motors to IEEE 334.

5 Power station auxiliary drives

Details of some of the more i mportant motor auriliary drives required on a modern CEGB power station with 660 MW turbine-generator (TG) units are given belmk, and also in Table 7.4.

5.1 Boiler feed pumps

The normal arrangement adopted currently by CEGS is for I x 100 070 steam turbine-driven feed pump, with

2 x 50% starting and standby motor-driven sariable. speed feed pumps. Motor-driven suction stage pumps are also required for the feed pumps.

Since the motor-driven feed pumps are required for starting and standby duty only, the choice of motor is largely dictated by first cost. Variable-speed sliprinct motors with variable rotor resistance liquid type controllers have been used. Squirrel-cage induction motors

with speed control by hydraulic couplings

have also

been used, particularly for nuclear power

stations,

where starting is required infrequently.

The variable-speed slipring induction motors are typically 1480 r/min (maximum), 9 MW, 11 kV, starting current 100% full load, 50 Hz, with speed variation 100% to 70% by rotor-resistance control, with liquidtype speed controllers. The feed pump is driven through speed-increasing gears at 8000 r/min (maximum). Three x 50% duty suction stage pumps are provided, driven by 1000 kW, 1480 r/min cage induction motors. Figure 7.16 shows a typical slipring induction motor reed pump drive.

With the cage induction motor drive, the motors are typically 1480 r/min, 10 MW, 11 kV, 50 MVA at start, 50 Hz, driving through hydraulic couplings with speed variation 100-70%. These are mechanically coupled to the feed pumps via speed-increasing gearboxes at 8000 r/min (maximum) pump speed. The suction stage pump is rated at 1000 kW, 1480 r/min and is coupled to a shaft extension of the main drive motor.

5.2 Coaland oil-fired boiler units

5.2.1 Draught plant

The practice is to install two induced-draught and two forced-draught fans per boiler unit, each working at full-load when the boiler is at continuous maximum

rating (CMR). It is possible to run the boiler unit at reduced load in the event of failure of one of the fans.

although it is expected that this condition would nol be allowed to continue for any length of ti me. The

640

Power station auxiliary drives

 

 

 

 

 

 

 

STATOR 'WINDINGS

 

 

 

 

 

 

 

 

 

 

 

COOLING FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR DUCTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLiP RING COVER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2_—

-

 

__ROTOR WINDINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fo OR RHI ipE STAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

,ICV AB L

 

 

 

 

 

 

 

 

PECESTAL EARTHED

 

 

 

 

 

 

,

 

 

 

r

 

 

 

 

 

 

 

 

 

THROUGH REMOVABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

C O P P E S T R P

oT H E RW I S E FULLY INSULATED

DIRECTION OF

AIR FLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

ING

 

 

 

 

 

 

 

 

 

HEAT EXCHANGER

 

 

L jri_ET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TUBES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- - 3 CL c,LLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PPINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT EXCHANGER

 

 

 

 

 

 

 

 

 

HEAT EXCHANGER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING WATER

 

 

 

 

 

 

 

 

 

 

 

 

VENTILATORS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING WATER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BRUSHES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSPECTION WINDOWS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIG. 7.16 Typical slipring induction-motor feed pump drive

for the motors to be single-speed cage induction

be installed in each reactor to circulate the primary

•.although two-speed cage induction and variablecoolant CO2 through the reactor core and boilers.

iitator-fed AC commutator motors have been i[lie moments of inertia of the fans are high, being ciI ti mes those of their respective motors, which rein relatively long run-up times, typically 50 to 80 s.

5 2.2

Milling plant

 

 

IIlIlliIlg

plant comprises the coal pulveriser mill,

,

-

 

air Ian (or exhauster fan), coal feeder and

 

 

 

 

 

,ir ,Ar or. Standby capacity is provided. The pulveriser

 

 

Luallv

need More

maintenance than any other

 

,

 

ill

the station:

for this reason, the running

 

 

 

 

 

 

iiiindby units are frequently interchanged. Coal

 

[

Cr wills require a

high starting torque (typically

 

i) and a relatively high number of starts per hour

 

CLaJIV

six). The vibration level of the plant is also

 

ill

C2]\

high and a robust motor is therefore required.

 

- enclosed air cooled squirrel-cage motors are

proi.ided.

5 .3 Nuclear reactors — AGR

5 3. 1 Gas circulators

pical arrangement is for eight gas circulators to

Two basic configurations are in common use in the CEGB, horizontal and vertical; this description concentrates on the vertical configuration, but many of the principles apply to both. Figure 7.17 shows the location of a vertically-opposed gas circulator in a nuclear reactor at Heysham I power station.

Each gas circulator is a single-stage centrifugal type, delivering 461 kg/s of CO2 at 41 bar and a temperature of 287 ° C. The inlet gas temperature to the circulator is 278 ° C and the pressure rise across the circulator is 2.83 bar.

The circulator is driven at 3000 r/min by an 11 kV motor mounted below the impeller on the circulator shaft (see Fig 7.18). A 415 V pony motor, mounted on the circulator shaft below the main motor, drives the circulator at barring speeds below 350 r/min. The motor unit for each circulator is encapsulated and comprises the composite assembly of main motor, pony motor, rotor shaft, bearings, impeller, inlet guide vanes and isolating dome operating mechanism. This assembly is contained completely within the reactor pressure boundary. The circulator unit can be withdrawn and replaced for maintenance with the reactor depressurised.

The impeller shaft passes through a barrier plate which is provided with a labyrinth seal to minimise

641

. since 'ent led
•)n-
:.e•
t welve

Mot ors

Chapter 7

 

 

LOCATION OF GAS CIRCULATOR

Fu. 7.17 Posiiion of gas circulator unit within AGR reactor

hot gas flow between the motor compartment and the reactor. The impeller operates in reactor gas at nearly 300 ° C, whereas the motor is isolated thermally to operate at temperatures of about 60 ° C. Although normal operation is in CO2 at 41 bar, the circulator must be capable of operation in air at atmospheric pressure (or reduced CO2 pressure) for commissioning, maintenance or during fault conditions.

motor

The circulator main drive motor is an 11 kV, two-pole squirrel-cage induction machine contained completely within the reactor pressure boundary. The motor, mounted on the circulator rotor shaft with the 415 V pony motor, rotates at a nominal speed of 3000 r/min and maximum continuous rating of 5.59 MW.

The motor is designed to I3S2613 Class F insulation, but operates normally within Class B temperature li mits, The motor is capable of operating continuously, at rated torque, at any frequency between 48 and 51 Hz and at any voltage between ±5% of the nominal value.

The motors are designated for 'essential duty' and are capable of continuous operation at 75% nominal volts at 50 Hz for a period of 5 minutes without injurious heating. They are also capable of recovering normal operation in the event of a system disturbance

causing temporary loss of supply voltage for periods of up to three seconds, followed by a sudden restoration initially to 80% nominal voltage.

The motor stator windings and laminations are con. tam ed within the main motor outer frame which is a mild steel cylindrical ribbed fabrication with top and bottom flanges (see Fig 7.19). The top flange aligns with the lower face of the top bearing bath and the bottom flange aligns with the bottom bearing batch assembly and incorporates holes for the motor securing bolts. The stator and outer frame complete weicth s approximately 14.5 tonnes.

The rotor is fitted on the forged carbon steel shaft together with the impeller, drive-end bearing sleeve, motor cooling fan, pony motor rotor, non-reverse clutch, pulsing disc and non-drive end thrust collar (see Fig 7.20).

Intensive research, development and full-scale t!stin g were required to establish the design of these ors, which have to operate under arduous conditio . The motor has also to withstand specified radiatio•: levels and also operate with contamination from lubricating oil mist. All these presented problems; in particular, the design of bearings under high rates of change of pressure of the ambient gas, the insulation system, the electrical design and thermal design. These are discussed in more detail (see Schwarz 1973 l7j).

A very high reliability is required, particular' the units are inside the reactor pressure cm and even apart from safety aspects, any 1: outage can be very costly.

5.4 Nuclear reactors — PWR

5.4.1 Reactor coolant pumps

A typical arrangement is four reactor cook: per reactor which are located within the re:. tainment. The pump unit consists of a vert:.

stage centrifugal-type pump, with vertical dr. .tor mounted above the pump and directly coupled to it. The motor has a drip-proof enclosure, but the cooling air outlet is water cooled. A flywheel is located at the top of the motor to provide the required coastdown capability in the event of loss of electrical power supply to the motor. This limits the transient temperatures within the reactor under such conditions. The motor must withstand specified radiation levels within the containment.

Figure 7.21 is a cutaway view of a typical reactor coolant pump and motor unit.

5.4.2 Safety-related drives

There are a number of drives, classified as safety-related category Class 1E to IEEE Standard 334, which are essential for the safety of the reactor during normal periods of shutdown or emergency periods following loss-of-coolant accidents which could involve severe

642

Power station auxiliary drives

1

F

F LOW

STRAIGHTENER

CONE

I MPELLER

D.E. OIL BATH

AND COOLER

ROTOR

11kV MAIN MOTOR

415V PONY MOTOR

SPEED SENSING

HEAD

NON REVERSE

CLUTCH

N.D.E. OIL BATH

AND COOLER

I. G V. OPERATING

SHAFT

ENO ENCLOSURE

PLATE

I G.V. GEARBOX

FIG. 7.18 Sectional arrangement of a gas circulator

643

Motors

Chapter 7

 

 

-I

-1

I

A

4

 

'

 

 

 

 

 

TERMINALS

LOCATION OF

 

 

 

MAIN MOTOR

 

 

STATOR WITHDRAWN

FROM FRAME

OUTER

CLAMPS

 

FRAME

TERMINALS

PERIM

 

1111601111.

Medealte,

IgneaMONOM, 1020.N.

AngarArg•

AgrArmismordoir ~roe

-

411=1.111111111111111hk

 

 

4

 

 

44L

 

V.

 

 

11°tit-

 

 

 

_ roc

 

 

 

 

 

 

 

 

 

NON-DRISE

DRIVE

 

 

 

 

 

 

END

 

 

 

 

 

 

ENO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COILS

 

STATOR

LOCKING

 

 

 

 

FR,. 7.19 Gas circulator — main motor stator and outer frame

PLATE

 

 

 

 

 

 

 

 

 

644

Testing

 

 

 

 

 

 

 

 

 

 

 

 

PONY

 

 

 

MOTOR ROTOR

 

 

 

 

 

 

 

BALANCE

 

 

 

 

 

 

WEiGHT

 

\\

 

1

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CLUTCH AND PULSFNG

 

 

 

 

MAIN

 

DrSC, ASSEMBLY

:MPELLER

 

 

 

MOTOR ROTOR

 

 

 

 

 

 

 

 

 

 

 

 

Fu.j. 7.20 Gas circulator — main motor rotor

 

-Aliation, thermal and environmental stresses. The test -,quirements to be met in order to qualify or prove

Jc2S[oT1 and reliability of such motors are given a IEEE. 334. Examples are motors for centrifugal

Airing pumps, high head safety injection pumps and :t2st,lual heat-removal containment spray pumps.

5.5Circulating water pumps

ii c usual arrangement of the cooling water system is system, in which the cooling water is taken to a ,tommon chamber whence a number of pumps dis-

.ii.iree into a common bus-main supplying all the conrisers in the station. In view of the vital importance tit the cooling water to the station output and in preplant damage due to loss of cooling water, spare

capacity is installed.

i - }1,2 motors are usually of the cage induction type. some installations use vertically-mounted motors, ,, ii cre-as others are horizontal. Figure 7.22 shows a vertical-shaft circulating water pump motor. The

.:iips are usually of low speed (typically 500 down to r min). With pump speeds lower than about 500 - ruin, it is usual to provide a motor driving through a cd-reducing gearbox, this being the most economic

saratieement.

rite more usual arrangement is to provide a pumpsometimes with removable or sliding roof for tii. Mitenance purposes. Both drip-proof and totally-

.::,.iosed motors have been used. The tendency is the totally-enclosed type, which gives greater ittroteetion against contamination of the windings. At Power stations, the stator windings are some-

. mcs additionally of the sealed type to protect against saline conditions.

6 Testing

'2 ling can be categorised into two groups: develop-

LI1I

and works testing.

The development of new designs and techniques, new materials and component parts is a research and development activity. Verification of the properties, performance, etc., must be obtained and is usually achieved by a testing process. Simulation methods may have to be used in some cases where direct testing is not possible or practical, e.g., accelerated ageing tests on insulation systems, where, for example, a relationship between voltage, temperature and time to breakdown can be established and the tests made at elevated temperatures and voltages. Fatigue testing of bars of cage induction motors is another example, where such tests are made to establish the total number of starts that can safely be made during the life of the motor.

Works testing on the completed motor needs to be made to verify that the motor is electrically and mechanically sound and that the stated performance characteristics are achieved. Such tests are categorised into basic and routine tests. Basic tests are in general made on the first motor of each type and routine tests on all other motors. Table 7.5 lists the individual test requirements for induction motors.

 

TABLE

7.5

 

 

Works tests on induction motors

 

 

 

 

 

 

 

Test

 

Basic

Routine

 

 

 

 

Resistance of windings (cold)

 

\

,.--

No load losses and current

 

\

,-

 

1

Locked rotor —

current

 

...-

 

1

torque

 

 

 

 

 

Starting (run-up) torque characteristics

 

 

for cage motors over 375 kW

 

\

 

Direct-on start at full voltage

 

 

,..-- (_?..3.3 kV)

(cage motors)

 

 

\

Rotor open-circuit induced

 

 

,--

voltage (slipring)

 

 

\

Temperature rise test

 

 

 

Power factor and efficiency

 

1

 

Speed control (variable-speed slipring)

 

\

 

 

 

 

 

Maximum (pull-out) torque

 

\

 

Vibration measurement

 

\

 

Noise level

 

 

\

 

 

 

 

 

 

645

Motors

Chapter 7

 

cL,WHF.EL

RACIA L

"H.uST

NE 3 SEAL LEAK OFF

CASING

I 51PELLER

SUCTION NOZZLE

FIG. 7.21 Reactor coolant pump and motor unit

7 Future trends

Motors for power station auxiliary drives are likely to continue to grow, both in power requirement and complexity. More emphasis is likely to be placed on the achievement of high reliability, due to increasing costs of unplanned outages, and on safety to personnel. This implies extension of and/or improvements to existing testing techniques and could include tests to determine the permissible number of direct-on-line starts in the life of cage induction motors. With increasing attention being given to the conservation of energy, improvement in operating efficiencies will be

sought. Improved materials will continue to be developed. These could include lubricating grease with a higher withstand-temperature and improved capability of insulation systems.

The use of motors having brushes, sliprings and commutators is likely to continue to be avoided. An increasing use of AC variable-speed converter drives is forecast, particularly with improvements in tech-

niques and reduction in cost of converter equipment. Linear motors are likely to find an increasing number

of applications where linear motion is required, such as cranes and sliding doors.

646