
reading / British practice / Vol D - 1990 (ocr) ELECTRICAL SYSTEM & EQUIPMENT
.pdf
|
|
|
|
|
|
|
|
|
|
Fire barriers |
||
|
|
|
|
|
|
|||||||
|
|
|
This property is assessed by examination of the |
strating the performance of the plain barrier arrange- |
||||||||
|
|
harrier both during and immediately following the |
ment of configuration 1. The case is not so clear cut |
|||||||||
|
|
st. It is essentially a measure of the strength of the |
when configuration 3 is examined |
and a separate test |
||||||||
|
|
(e |
|
|
|
|
|
|
on such an arrangement would most likely have to be |
|||
|
|
harrier assembly under the extreme temperatures of |
||||||||||
|
|
the fire. |
|
|
|
carried out. |
|
|
||||
• |
|
|
In addition to remaining 'stable', no cracks |
From the above, it is clear that care must be taken |
||||||||
|
Tweg oly |
|
||||||||||
|
|
in assessing whether fire test performance data may |
||||||||||
|
o penings must develop |
in the barrier during |
||||||||||
|
|
or |
other |
|
be applied to a particular practical |
configuration. |
||||||
|
|
the test which could affect its ability to prevent |
As a closing note on full scale fire testing, it is |
|||||||||
|
|
t h e spread |
of fire from one side of the barrier to |
|||||||||
|
|
important to remember that a fire barrier which has |
||||||||||
|
|
,he other. in cable installations, this aspect is par- |
successfully maintained stability, integrity and insula- |
|||||||||
|
|
ticularly important since such openings could permit |
||||||||||
|
|
tion during a fire test has performed in that manner |
||||||||||
|
|
|
ssage of the gases and fumes from one side of the |
|||||||||
|
|
pa |
under test fire conditions only. Fire barriers passing |
|||||||||
|
|
barrier to the other. A test is passed, therefore, only |
such tests are often referred to as having |
a 1 - hour |
||||||||
|
|
if [here is virtually no leakage of hot gases or smoke |
||||||||||
|
|
(say) rating. It should be appreciated, however, that |
||||||||||
|
|
through |
the barrier; particular attention being paid |
|||||||||
|
|
the I-hour rating relates to the specific characteristics of |
||||||||||
|
|
[GI joints, penetration seals and doors. It is difficult, |
||||||||||
|
|
the test. Since all real fires have differing and unique |
||||||||||
|
|
however, |
to quantify exactly what constitutes 'ac- |
|||||||||
|
|
characteristics, the fire test cannot ever be an absolute |
||||||||||
|
ceptable' leakage in this context as it will depend very |
|||||||||||
|
guarantee of performance. On the positive side, it |
|||||||||||
|
|
much on the size and complexity of the barrier |
||||||||||
|
|
must be remembered that the test fire is immediately |
||||||||||
|
|
assembly being tested. The British Standard calls for |
||||||||||
|
|
adjacent to the fire barrier whereas in practice this is |
||||||||||
|
|
integrity to be measured by holding cotton wool |
||||||||||
|
|
unlikely to be the case. It should also be noted that |
||||||||||
|
|
pads immediately over any cracks or fissures, a test |
||||||||||
|
|
test fire conditions make no allowance for the fast- |
||||||||||
|
|
pass being recorded if the pads do not catch fire. |
||||||||||
|
|
acting fire fighting systems which the CEGB usually |
||||||||||
|
|
This is not considered to achieve adequate demon- |
||||||||||
|
|
employs to protect its cable installations for economic |
||||||||||
|
Ntration that smoke and fumes will not pass through |
|||||||||||
|
reasons. |
|
|
|||||||||
|
the openings; the performance of the barrier is |
|
|
|||||||||
|
As well as the main full-scale fire performance tests |
|||||||||||
|
therefore checked by a careful visual examination |
|||||||||||
|
described above, the CEGB's specification also calls |
|||||||||||
|
throughout the test. |
|
||||||||||
|
|
for non-combustibility and surface spread-of-flame |
||||||||||
• |
Insulation |
The insulation performance of a fire |
||||||||||
tests to be carried out on fire barrier materials. |
||||||||||||
|
barrier is determined by measurement of tempera- |
The non-combustibility test is carried out in ac- |
||||||||||
|
tures on the unexposed face during the fire test. |
cordance with BS476: Part 4 [251, which calls for |
||||||||||
\\ hen assessing the thermal resistance of the barrier, |
specimens of a predetermined size to be heated in a |
|||||||||||
small, closely temperature controlled, electrically-heated |
||||||||||||
ii |
|
it |
important to consider the nature of the cable |
oven. During the test period, the current in the heating |
||||||||
materials local to the barrier. Because PVC can start to |
coils is held at a fixed value which, after a period of |
|||||||||||
cmil |
combustible gases from upwards of 200 ° C, it is |
stabilisation, produces an approximately constant oven |
||||||||||
important to limit the temperatures on the unexposed |
temperature. The test specimen is then introduced into |
|||||||||||
Lice by barrier design. Temperatures at various points |
the oven and held there for 20 minutes during which |
|||||||||||
on the unexposed barrier face are therefore monitored |
ti me the oven temperature is closely monitored. Any |
|||||||||||
throughout |
the test using thermocouples. A test pass |
increase in the oven temperature |
(above |
a certain |
||||||||
|
recorded |
if the mean temperature of the-unexposed |
tolerance value) is then deemed to be attributable to |
|||||||||
race rises by no more than 140 ° C and if the temperature |
the combustion of the test specimen. A sample giving |
|||||||||||
at any critical hot spots (for example, bolt heads) rises |
such a temperature rise would therefore fail the test. |
|||||||||||
hy no more than 180 ° C. These temperatures allow for |
In addition to this temperature measurement, any |
|||||||||||
;lie fact that the cables will not actually be in contact |
sustained flaming of the specimen is also noted. If |
|||||||||||
|
Lt h |
the barrier surface but will be protected to some |
flaming occurs continuously for more than 10 seconds, |
|||||||||
degree by their penetration seals. |
|
this is also deemed to be a test failure. |
|
|||||||||
|
As illustrated by Fig 6.119, many different fire |
It is clear therefore, that the term 'non-combustible' |
||||||||||
Harrier configurations will be used in protecting a cable |
as determined by this test procedure, is not absolute. |
|||||||||||
InNtallation. It may therefore be necessary to conduct |
The British Standard defines non-combustible materials |
|||||||||||
separate |
fire tests on a number of different barrier |
as those which 'make little or no thermal contribu- |
||||||||||
, |
|
|
|
|
||||||||
.ontigurations |
in order to have complete confidence |
tion to the heat of the furnace and do not produce a |
||||||||||
.tn the barrier installation as a whole. Since this would |
flame', which is consistent with CEGB philosophy for |
|||||||||||
Ce "Pensive, care is taken to ensure that a full scale |
fire barrier material combustibility. |
|
|
|||||||||
l est |
assembly covers as many of the practical barrier |
The surface spread of flame test is carried out in |
||||||||||
Ar |
|
|||||||||||
|
rangements as possible. For example, a successful |
accordance with BS476: Part 7 [26]. |
|
|
||||||||
1- |
|
on an |
arrangement such as configuration 2 in |
This test provides a method for measuring the lateral |
||||||||
|
|
|
|
|
|
|
|
spread of flame along the surface of the fire barrier |
||||
ig 6.119 would normally be considered as demon- |
547
Cabling |
C hapt er 6 |
|
|
|
|
panels when vertically orientated, and a classification system based on the rate and extent of flame spread.
The test method has been designed to take account of the combined effect of factors such as ignition characteristics and the extent to which the surface of the test specimen spreads the flame. The influence on these factors of any underlying materials, in relation to their ability to influence the rate of fire growth, is also taken into account.
In this method, specimens of the fire barrier panels are subjected to a specified radiative heating regime v.ith a small gas ignition flame at one end. The horizontal spread of flame from this ignition source is measured at 1.5 minutes and 10 minutes into the test, and the progress of the flame-front determines the surface spread-of-flame classification given to the material.
The most onerous classification, which is that required by the CEGB for its fire barrier panels, is Class I. To meet Class I requirements, the flame front must not progress beyond 165 mm from the ignition source after the 10-minute test period.
10.4 Additional performance criteria
In addition to the basic fire test performance criteria, the CEGB also dictates that its fire barriers provide the following features:
•Design performance over a lifetime of 40 years in a power station environment without the need for maintenance.
•Suitability for use in damp and wet conditions.
•Freedom from asbestos in their construction.
•Freedom from materials which emit any corrosive or toxic fumes or smoke on the unexposed face of the barrier under fire conditions.
•Defined minimum mechanical strength.
•Capability of withstanding the pressure rise associated with fires in sealed cable tunnels.
•Capability of withstanding in-service levels of vibration without reduction in fire performance.
•Barriers must not fail in such a way as to damage other plant (including cables) during a seismic disturbance of a specified magnitude (requirement for nuclear power stations only).
A wide range of tests are carried out on barrier samples which are designed to demonstrate the above qualities. These tests include:
•A hose stream test to verify that the thermal and mechanical shock of a hose stream being suddenly played on a hot fire barrier does not cause catastrophic failure.
•The following mechanical strength tests:
548
(a)I mpact withstand.
(b)Modulus of elasticity and bending strength.
(c)Mechanical strength after wet cycling.
(d)Pressure rise due to combustion (simulated statically or by analysis).
•Water absorption.
•Seismic qualification, usually by analysis based upo n dynamic tests on representative fire barrier sampl es.
It is more difficult to demonstrate that the materials used will not age significantly over their 40-year de s ign life. The type of testing which is carried out very much depends upon the materials used, but a common feature
is the application of heat, either a continually -applied elevated temperature or some form of thermal cycling.
In some cases, the materials used to construct the fire barrier are standard building materials for which ageing data is already well established. In these cases further testing is not necessary.
10.5 Fire doors
It is not possible to specify requirements for fire barriers without giving careful consideration to the design of fire doors.
Fire doors may effectively be considered as personnel penetrations, and they bring with them their own problems in ensuring adequate fire performance. Obviously, the presence of the door must not detract from the fire performance of the barrier in which it is located. This means that special care must be taken at the jamb assembly to ensure that integrity and insulation requirements are met. It may be particularly difficult to achieve the required fire performance whilst still providing doors which provide satisfactory emergency egress for personnel.
Another problem which arises with doors is that for ventilation purposes they often need to be latched open during normal operation. This means that a fastacting fire detection system must be provided to trigger door release in the event of a fire. The closing mechanism must obviously ensure that the required seal is made on closing.
10.6 Penetrations
Penetration seals are required in order to seal around openings where cables (and other services such as pipework) pass through fire barriers. It is a fundamental requirement, therefore, that the presence of these penetration seals does not degrade the fire performance of the barrier in which they are located.
Configurations 2 and 3 in Fig 6.119 show typical examples of the application of these seals, specifically installed in pre-formed type fire barriers. They could, however, equally be installed
|
|
|
|
|
|
Fire barriers |
|
|
|
|
|||
floors roof soffits, etc., since all of these may be |
|
it is identified that a pressure rise due to combustion |
||||
|
, |
|
|
|
in a sealed area may exist. |
|
• |
° nsidered as fire barriers. |
|
|
|||
There are three basic types of penetration seal; rigid, |
• |
Flexible seals A variation of the silicone elastorner |
||||
' |
|
|
|
|
||
ic , i bie and pre-formed, each of which is described |
|
rigid seal described above is formed by the addition |
||||
1H-icfly as follows: |
|
of a foaming agent to one of the components in |
||||
• |
Ri,id seals |
These are usually modified plasters |
|
the mix. Once mixed, the two components begin to |
||
inert materials such as vermiculite or |
|
cross-link at room temperature but, whilst doing so, |
||||
|
made up of |
|
||||
|
pcar lite ,which are Inked at site to form a paste. |
|
hydrogen gas is generated which causes foaming to |
|||
|
Bc1 rw i,ater based, they are placed around the pene- |
|
occur. This foaming leads to expansion of the seal |
|||
|
trants by trowelling and then form a rigid seal by |
|
material which in turn provides a good mould to |
|||
|
caporation at room temperature. When set, they |
|
the contours of the penetrants. Again, ceramic fibre |
|||
|
effectively form an extension of the fire barrier in |
|
board damming is required at each penetration prior |
|||
|
hich they are located, containing the fire in much |
|
to sealing and this forms part of the completed |
|||
|
the same way as the barrier itself. They have the |
|
||||
|
|
penetration seal assembly. |
||||
|
additional advantage of acting as a heat sink which |
|
The main advantage with this type of seal is |
|||
|
retards the conduction of heat along the conductors |
|
||||
|
|
the relative ease with which additional cables may |
||||
|
of the cable during a fire. |
|
||||
|
|
be added at a later date. The fully cross-linked foam |
||||
|
|
This type of seal, whilst being inexpensive, suffers |
|
may easily be cut with a craft type knife, as can |
||
|
from two main problems. Firstly, it requires the time- |
|
the ceramic fibre board by means of a special tool. |
|||
|
,J)nsurning, labour intensive process of damming at |
|
If the hole in the foam is cut slightly undersize |
|||
|
e ach |
penetration prior to forming. This is usually |
|
to the penetrant, its natural springiness will ensure |
||
|
carried out using plywood or a similar material. |
|
a good smoke-seal without the need to re-apply |
|||
|
Secondly, once a seal has been formed, it is then |
|
sealant. |
|||
|
difficult to add further cables. It is undesirable to |
|
As with the rigid elastomer seal, expense may |
|||
|
leave the sealing of penetrations to the very end of |
|
restrict the use of these seals which require trained |
|||
|
cable installation as the construction period itself |
|
staff and special equipment to install. |
|||
|
is the time of greatest fire hazard due to high person- |
• |
Pre-formed These types of seal, sometimes known |
|||
|
nel presence. Despite these two disadvantages, these |
|||||
|
|
as 'cable transits', are in the form of 2-part, semi- |
||||
|
are the traditional type of seals which have been |
|
||||
|
|
flexible, pre-formed blocks which are placed around |
||||
|
used in a wide variety of industrial applications for |
|
||||
|
|
individual cables. These blocks, along with 'blanks' |
||||
|
many years. |
|
|
|||
|
|
|
where necessary, are slid into a special frame formed |
|||
|
There is, however, a new form of rigid penetration |
|
||||
|
|
around the inside of the penetration. Clamping screws |
||||
|
seal which is now generally available in the form |
|
||||
|
or a two-part silicone elastomer which, when mixed, |
|
are used to achieve a tight seal around the penetrant. |
|||
|
|
During a fire, the block material is consumed very |
||||
|
■;ill cross-link at room temperature to become rigid. |
|
||||
|
|
slowly, hence the thickness determines the level of |
||||
|
This mixing takes place at the head of special pump- |
|
||||
|
ing equipment which is used to install this type of |
|
fire performance. |
|||
|
|
The design intent of these cable transits was the |
||||
|
',cal. Because the seal material is a liquid when first |
|
||||
|
|
easy addition and removal of cables after formation. |
||||
|
applied, it is able to mould itself to the contours |
|
||||
|
or the |
penetrations. |
|
However, it is necessary to keep a complete range |
||
|
During a fire, the seal material burns to form a |
|
of block and blank sizes to cover for all cable sizes |
|||
|
|
and penetration configurations. Use of these transits |
||||
|
surface layer |
of char. It is this char layer which |
|
|||
|
prevents further combustion of the seal and hence |
|
means that cable support ladders must be stopped |
|||
|
restricts the fire. |
|
on either side of the fire barrier, hence giving rise |
|||
|
Again, prior to forming the seal, damming ma- |
|
to the need for additional cable steelwork supports. |
|||
|
|
Also, the fact that blocks are placed around in- |
||||
|
terials need to be installed at each penetration. In this |
|
||||
|
|
dividual cables makes this a very time-consuming |
||||
|
case, the damming is formed from ceramic fibre |
|
||||
|
|
and expensive sealing method and consequently they |
||||
|
hoard which is not removed after curing and forms |
|
||||
|
|
are rarely used by the CEGB. |
||||
|
part of the finished penetration seal assembly. This |
|
||||
|
|
|
||||
|
type of seal suffers from the same disadvantages |
|
|
|||
|
as the |
modified plasters described above and is also |
As mentioned, it is essential that penetration seals |
|||
|
more |
expensive. Furthermore, it is also necessary |
provide the same level of fire performance as the bar- |
|||
|
to use specialised installation equipment and requires |
riers in which they are located. It is therefore necessary |
||||
|
trained applications staff in order to ensure a con- |
to incorporate examples of typical sealing arrangements |
||||
|
sistent standard of seal. It is, however, much faster |
in the full scale fire test assembly. Particular attention |
||||
|
to install than the plaster type seals and it also has |
is paid to the unexposed face temperatures around the |
||||
|
a pressure withstand capacity, which the plaster type |
seals which are a potential weak point in the barrier |
||||
|
seals do not have. This can be an advantage where |
assembly. • |
549
Cabling |
Chapter 6 |
|
|
As with fire barriers, in addition to the basic fire test performance criteria, the CEGB also dictates that its penetration seals provide the following features:
•Design performance over a lifetime of 40 years in a power station environment,
•Suitability for use in damp and wet conditions.
•Freedom from asbestos in their construction.
•Capability of withstanding the pressure rise associated with combustion in sealed cable tunnels.
•Compatibility with cable sheathing materials.
•Capability of withstanding in-service vibration and cable movement due to short-circuit and thermal cycling without reduction in fire performance.
1013: 1965, Clause 215, it is a requirement that if two or more stations are adjacent on what may be considered to be one site, then the earthing systems are to be interconnected to form a single earthing system. This applies to a number of generating stations on one site, and also to power stations and transmis s i on substations on a common site.
When reading this section it should be borne i n mind that earthing is closely associated with light n i ng protection, power cable ratings and gland bonding, and therefore reference will also need to be made to th e sections covering these topics.
11.2 Differences in earth potential
•They must not damage cables during a seismic disturbance of specified magnitude (requirement for nuclear power stations only).
A further design criterion which must be considered when selecting penetration seal materials, is the effect which the seals may have on the current carrying capacity of power cables which pass through them. Here, two conflicting interests exist. In order to achieve good insulation properties to restrict unexposed face temperatures during a fire, it is desirable for the seal to be a good thermal insulant. This does, however, restrict the conduction away of heat generated in the power cables due to copper losses under normal operating conditions. Thus it may become necessary to derate the power cable to accommodate the seals. This in turn may lead to the use of larger cables sizes to supply particular loads. The rigid plaster type seals will be less of a problem in this respect than the other seal types, since they are more thermally conductive.
11 Earthing systems
11.1Introduction
The purpose of an earthing system is to provide an adequate path for earth fault currents to return to the system neutral. This has to be performed in a manner which ensures 'safety to personnel', i.e., without giving rise to dangerous touch, step or transferred potentials. In addition, to prevent damage to plant, the rise of earth potential under fault conditions must not result in breakdown of insulation. In all cases, the system design must be such that enough fault current will flow to operate the protection devices and disconnect the fault. To meet these needs, an earth system must include earth electrodes to allow current to flow into the ground to remote system neutrals, and also a network of conductors to allow fault current to flow between plant within the station site. In this context, in accordance with British Standard Code of Practice
11.2.1 Definitions
When earth fault currents flow to ground, a potential gradient is formed around the earth electrode due to the resistance of the ground. This potential gradient is greatest adjacent to the earth electrode and reduces to zero or true earth at some distance from the earth electrode. Three methods of contact with these pot. tials are considered and defined as step, touch and transferred potentials. These are shown diagramma.. tically in Fig 6.121 which is discussed as follows:
•Step potentials Person 'a' on Fig 6.121 illustrates
'step potential'. Here the potential difference V 1 seen by the body is limited to the value between two points on the ground separated by the distance of one pace. Since the potential gradient in the ground is greatest immediately adjacent to the electrode area, it follows that the maximum step potential under earth fault conditions will be experienced by a person who has one foot on the area of maximum rise and the other foot one step towards true earth.
•Touch potential Person 'b' on Fig 6.121 illustrates 'touch potential'. Here the potential difference 112 seen by the body is the result of hand-to-both-feet contact. Again the highest potential will occur if there were a metal structure on the edge of the high potential area, and the person stood one pace away and touched this metal. The risk from this type of contact is higher than for step potential because
the voltage is applied across the body and could affect the heart muscles.
•Transferred potential The distance between the high potential area at the electrode and that of true earth may be sufficient to form a physical separation rendering a person in the high potential area i mmune from the possibility of simultaneous contact with zero potential. However, a metal object having sufficient length, such as a fence, cable sheath or cable core may be located in a manner that would
bridge this physical separation. By such means, zero earth potential may be transferred into a high potentiaI area or vice-versa. Person 'c' in Fig 6.12 1
550

Earthing systems
STA" ON |
PO , NT |
I ALE
PILOT CABLE HAVING coNrrNuous TAR TN
METALLIC SHEATH INSULATED
THROUGHOUT BUT WITH BOTH ENDS
EAposE0 SHEATH BONDED TO MAIN
EARTH GRID AT SUBSTATION END ONLY
|
|
|
|
|
|
|
EOU.POTENTIAL LINES DURING |
|
|||||
|
|
|
|
|
|
|
FLOW OF EARTH FAULT CURRENT |
|
|||||
|
|
|
|
BURIED |
|
|
|
|
|
|
|
|
|
|
|
|
|
ELECTRODE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FIGURE |
CURRENT FLOW PATH |
POTENTIAL |
TYPE |
||||||||||
DIFFERENCE |
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
'eg leg |
|
|
|
|
|
|
STEP POT ENTIAL |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
arm•bady•iegs |
|
|
|
|
|
|
TOUCH POTENTIAL |
||
|
|
|
|
dun tt0Cly-arrn |
|
|
v i |
|
|
|
• TRANSFERRED POTENTIAL |
||
|
|
|
|
arrn•ocKly leg |
|
Ti |
TRANSFERRED POTENTIAL |
Fin. 6.121 Differences in earth potential
illuqrates the case of a high potential being trans- ferred into a zero potential area via the armour of a cable. Since the armour is bonded to the main earth
:Ind |
at the power station, the voltage V3 will be |
he |
full 'rise of earth potential of the power station'. |
In the illustrated case, the person is making simultaneous contact hand-to-hand with the cable sheath
and true earth. However, if the person is standing an [rue earth then the voltage V3 seen by the body ,: ould be the result of a hand-to-both-feet contact. Person 'd' in Fig 6.121 represents the case of zero [' o[ential being transferred to a high potential area \ id a cable core which is earthed at the remote point. In this case, the voltage V4 is lower than V3 o hich represents the station rise of earth potential, because person 'd' is located some distance from the main earth electrode and therefore is subject to the ground potential gradient. Quite clearly if person 'cl'
ii ad been on or touching the main electrode he would hl asre experienced the full rise of earth potential V3. Franslerred potentials are therefore considered to
..airy the greatest risk since the shock voltage may he .equal to the full rise of earth potential and not
a iraction of it, as is the case with step or touch pa [ entials.
11 2.2 Acceptance criteria
cceptance criteria are related to the rise of earth ;otential and its duration in the following manner:
(a)For high reliability systems, i.e., systems having high speed protection, the maximum permissible rise of earth potential without special precautions is 650 V. This requirement, given in Engineering Recommendation S5/I, is based on limits set by the International Telegraph and Telephone Consultative Committee for installing telephone equipment without special protection for personnel or equipment. A duration is not given for the clearance time associated with high reliability systems, but this is generally accepted as 0.2 seconds. Although this value of 650 V originates from requirements for telephone equipment, it is now also used as a criterion for safety generally. Therefore, providing this limit is not exceeded, experience has shown that no special measures are necessary in respect of potential rise, step, touch or transferred potentials.
(b)For systems protected by overcurrent protection, the maximum permissible rise of earth potential without special precautions is 430 V.
This requirement, also taken from Engineering Recommendation S5/1, is again based on CCITT recommendations for telephone equipment. Once again, no fault duration is given for this condition
but using the criterion given in (a) and extrapolating on an 1 2 t basis, for the 430 V limit a maximum duration of 0.46 seconds is obtained. As for (a), providing the criterion is not exceeded, no special
561

Cabling |
Chapter 6 |
|
measures are required in respect of step, touch or transferred potentials.
(c)British Standard code of practice CPI013: 1965 (Clause 213) requires that the potential difference between two normally earthed items to which personnel may have simultaneous contact should not
exceed 55 V. Bearing in mind the criterion given in (b), this limit of 55 V is applied to all rises of earth potential that exist for durations in excess of 0.46 seconds.
(c1) If the criterion given in (a), (b) and (c) cannot be complied with, then special precautions must be taken to protect personnel and plant. An example of precautions to protect against transferred potentials is the use of isolation transformers on incoming telephone lines. A further example is the provision of local bonding to give immunity by ensuring that all metalwork to which simultaneous contact can be made is at the same potential. Guard rings buried at increasing depths around an electrode can be used to modify the ground surface potential to protect against step potentials.
11.3 Earthing systems design
When considering the design of earthing systems it is useful to bear in mind that earth fault currents have to return to their own system neutrals. This means that whilst a common earth system for all equipment is employed, it can be analysed in two parts depending on whether the neutral of the system feeding the fault is within the power station or is remote. The following Section 11.3.1 deals with 400 kV, 275 kV and 132 kV systems where a significant proportion of the earth fault current will flow via the earth electrode to a remote supply source. Section 11.3.2 deals with system voltages up to and including generator voltage, where the system neutral is within the power station and therefore the vast majority of earth fault current will flow in the metallic bonding system.
11.3.1 Systems having remote neutrals
400 kV, 275 kV and 132 kV systems have neutrals that are outside the confines of the power station and therefore the earth fault current flows back to the source via the ground and any EHV cable sheaths or aerial earth conductors. The proportion of fault current returning down each path will be dependent on the path impedance. Under such fault conditions the whole power station earth network will be raised in potential with respect to remote earth. The rise of earth potential will be the product of the current returning through the ground and resistance of the station earth. Since these EHV systems are classed as high reliability, the maximum allowable rise of earth potential under fault conditions without additional precautions is 650 V as discussed in Section 11.2.2 (a) of this chapter.
Since the earth fault current that flows into the ground is associated with the EHV systems, the mai n earth electrodes should be adjacent to plant connected to the EHV system (e.g., generator and station transformers). This is to enable earth currents to flo w to ground close to the fault location, thus restricting th e fault current flowing through the station earth system interconnections and minimising the potential gradients across the station. In addition to these main ea rt h electrodes, it is normal practice to install a number of secondary electrodes to reduce the overall station resistance and limit potential gradients across the site A typical station earth system arrangement is show n in Fig 6.122.
The earth electrode system is designed by calculating in sequence the following parameters:
•Maximum earth fault current that has to return to remote sources.
•Minimum size of electrode required to transfer fault current into the ground.
•Resistance of these minimum size individual electrodes.
•Consequent overall station earth resistance.
•Proportion of current that returns to source via the ground.
•Resultant rise of earth potential.
•If the rise of earth potential is unacceptable, the size of individual earth electrodes is increased and the calculations repeated.
•If the rise of earth potential cannot economically be reduced to an acceptable level, other measures to protect personnel and plant must be considered.
This process is explained in greater detail in the remainder of this section and a worked example is given in Section 11.4 of this chapter.
For earth electrode sizing it is only that proportion of EHV system earth fault current that has to return to remote neutrals that is of interest. Therefore, due account should be taken of on site' contributions to fault currents. For example, where generator transformers are connected to the 400 kV system, any contribution to the 400 kV earth fault level from on site' generation can be ignored when sizing the earth electrodes since the current will flow through metallic connections and not into the ground.
Before electrode sizing can be started, the soil resistivity at each proposed location must be established using the Wenner four-electrode test described in Section 11.6.1 of this chapter. The first step in sizing an electrode is to calculate the minimum surface area that is required to dissipate the current into the ground without undue heating and drying out of the soil local to the electrode. For these calculations it is considered prudent to ignore all EHV cable sheaths and overhead
552

ESSEI.NM
5 7 47.0N
. a.INFORMER
Earthing systems
To - A STATION |
1, |
TO A STATION |
EARTH PITT |
||
|
|
EARTH PIT |
ESOB , NE;
TURBINE |
HALL |
5508 ■NWr
••■•
r1:■:17:1=r 3
- 13
REACTOR 7 |
|
REACTOR |
REACTOR |
SERVICES |
BU I LDING |
ROAD
n„,
ESSE1(SW) |
ESSO tSE) |
STATION |
|
|
TRANSFORMER |
AETP |
E508 |
(SE) |
11,
Fic. 6.122 Typical station earth system
553
Cabling |
Chapter 6 |
|
|
|
|
line earth conductors, and to assume that all earth fault current returns to the remote neutrals via the electrode adjacent to the faulted plant. Whilst this may appear conservative, in reality the electrode size is normally dictated by its resistance (since this governs the rise of earth potential) and not by its current carrying capability. At this stage the cross-sectional area of the electrode itself should be checked to ensure that it is capable of carrying the anticipated fault current. Such calculations should take into account the estimated loss of metal due to corrosion during the station life.
Having established the minimum size of electrode required to carry the fault current, the next step is to calculate the resistance of the station earth system and assess whether the rise of earth potential is acceptable. The first step in this process is to calculate the resistance of each individual electrode as shown in Section 11.4 of this chapter. The overall station resistance is then calculated for all electrodes in parallel ignoring the impedance of interconnecting cables. This greatly si mplifies the calculations and experience has shown that this also compensates for ignoring fortuitous earth paths such as pipes and base slab concrete which cannot be readily identified or calculated.
This rise of earth potential will be the product of the station earth electrode resistance and the current flowing through it. As already stated, the earth fault current will return to remote neutrals via the ground and any overhead line aerial earths or cable sheaths that may exist. The current division will be dependent on the relative impedances of each route. Since the electrode design is dictated by the allowable rise of earth potential, it would be grossly uneconomic to base these calculations on the assumption that all current flows in the ground. Therefore, the division of current between the various paths must be assessed. The amplitude of the earth current returning to neutrals via overhead line earth wires and towers can be 30 - 70% depending on the number of lines and their length [27]. Therefore, quite clearly, the value of current flowing into the ground will be dependent on the physical location of EHV substations relative to the power station.
Where the power station and EHV substation share a common site, at least one metallic connection per generating unit will be provided between the two earthing systems. Earth fault currents can therefore flow via these connections to the earth wires and towers associated with the EHV substation. The magnitude of these currents will depend on the number of overhead lines or cables entering the substation and their lengths. Since power station earth electrodes normally consist of steel piles they have, of necessity, to be designed and installed at an early stage of power station construction. This frequently means that accurate predictions of current division cannot be made at the design stage. It is therefore normal practice to calculate the rise of earth potential assuming the worst case of 70%
of the fault current returning through the ground. The combined resistance of the power station and EHV substation earth systems is used for this calculation.
Another arrangement that may be encountered is a power station located a few miles from its associated EHV substation. En such cases it can be assumed that for an earth fault at the power station only 10Wo of th e current would flow in the ground. The rise of earth potential would therefore be the product of this pro.. portion of current and the power station earth syste m resistance.
If the calculated rise of earth potential exceeds th e 650 V limit, the size of the electrodes should be increased and their resistances and the potential rises recalculated.
In some cases it may not be economically or technically possible to provide an electrode system that will li mit earth potential to 650 V. En such cases the po- tential rise should be reduced to an economic minimum and additional precautions taken to safeguard against transferred, step and touch potentials. Such measures against transferred potentials would include isolation transformers on incoming telephone and pilot cables, and possibly isolated sections in pipelines or railway tracks entering the site. In addition, step and touch potentials would have to be assessed using the type of techniques given in IEEE Standard 80 [28]. If step or touch potentials are found to be excessive then additional provisions such as guard rings will be necessary. Guard rings consist of a number of ground conductors, connected to the main electrode, and buried at increasing depths around it so that the ground surface potential is modified. A typical arrangement is shown in Fig 6.123.
11.3.2 Faults on internal systems
For system voltages up to and including generator voltage, the system neutrals are earthed within the boundary of the power station and therefore the vast majority of the earth fault current will flow via metallic bonds and not into the ground itself. Equipment operating at generator voltage is considered a special case since it is all bonded to a special earth bar run with the main connections. Consequently, any earth fault current will preferentially flow in this special earth bar rather than in the station earth network. Details of generator main connections are given in Chapter 4.
Earth fault currents associated with 11 kV, 3.3 kV and 415 V systems will however return to their neutrals via the station earth network. The station earth net- work is a mesh of metallic bonds interconnecting the earth electrodes and forming a ring around plant areas.
We must now consider the magnitude of earth fault currents associated with these systems. If the zero phase sequence impedance of the system were the same as the positive phase sequence impedence, then the earth fault current would have the same magnitude as that for a three-phase symmetrical fault. In practice for
554

Earthing systems
Ve
POTENTiAu AT GROUND SURFACE |
|
|
|
V, |
||
WITH RESPECT TO REMOTE EARTH |
|
|
|
|||
|
|
|
|
|||
STEP EOTENUAL |
|
|
|
|
||
WITHOUT GUARD R , NG |
|
|
|
|
|
|
|
|
|
|
|
||
|
........ . . • |
|
|
|
|
|
|
|
|
|
|
||
|
|
|
EARTH |
|||
|
|
|
ELECTRODE |
GUARD RINGS RONDE0
TO EARTH ELECTRODE
WITHOUT GUARD RING |
|
WITH GUARD PING |
GUARD RINGS BURIED
AT INCREASING DEPTHS
TO CONTROL GROUND
POTENTIAL GRADIENT
FIG. 6.123 Typical guard ring arrangement
Thipsformers it is not possible to obtain identical -dues for positive and negative phase sequence im-
..1:11ices. Transformers are therefore specified to have ,mo phase sequence reactance as close as possible 10.0' of the positive phase sequence reactance, with
.Ellowable minimum of 90 07o. With this minimum he earth fault current could be 3.510 higher than :hrce-phase symmetrical fault current. Since every made to keep the negative phase sequence :;•:..Llarice as near as possible to the positive value,
.::.d since in practice earth fault currents rarely achieve
. or full prospective value, it is normal within power - .;:ion design to assume that the unrestricted earth Huh ..urrent is the same as the three-phase symmetrical
The fault levels associated with internal systems u .L follows:
• |
Ii v |
750 MVA (break) 39.4 kA |
|
|
|
||
• |
3.11 kV |
250 MVA |
= 43.7 kA |
|
|
||
• |
415 v — 31 MVA |
= 43.1 kA |
|
\..1.:rdl earthing resistors |
(NER) are provided on the |
I kV and 3.3 kV systems which limit the fault current
. d pproximately 1000 A per infeed. However, the
N±,stem is solidly bonded to earth to make avail- -lc he
full prospective fault current to allow proper
clearance of fuses. The maximum current returning to an internal system neutral under a single earth fault condition is therefore that associated with the 415 V system, and this fixes the size of the station earth network for internal faults. There is a very low probability of the NER flashing over, allowing unrestricted earth fault current to flow for 11 kV and 3.3 kV system faults. If this were to occur on the 3.3 kV system, the fault current flowing through the station earth network would be greater than the design value associated with the 415 V system. The increase in fault current would however be so marginal that the integrity of the station earth system would not be threatened. For outbuildings which do not directly form part of the main station earth network, the size of its earth ring will be dependent on the system voltage and fault levels for equipment within that building.
For faults on internal systems, the allowable rise of earth potential should be that appropriate to overcurrent protection as defined in Section 11.2.2 of this chapter. This means that the rise of earth potential should be limited to 430 V for faults cleared in less than 0.46 seconds and 55 V for longer clearance times. Where these limits cannot he economically achieved, special measures (such as local bonding to give immunity from transferred potentials) can be used as discussed later in this section. For these internal faults,
555
Cabling |
Chapter 6 |
|
|
|
|
the rise of earth potential at the faulted equipment is taken to be the product of the impedance of the metallic bonding system path and the total earth fault current.
To keep the potential gradient across the station to a minimum, the impedance of the fault current return path must also be kept to a minimum. Furthermore, to reduce the risk of electrical interference in control and instrumentation circuits, it is desirable to keep the fault current supply and return paths as close as possible. For rnulticore power cables these aims are achieved by using the armour as the main earth return path. For single-core cables which have their armours single - point bonded, these requirements can best be achieved by running an earth cable in close proximity with the power cables.
In the case of large transformer feeds and interconnectors, the single-core cable circuits will be short or will follow a major cable route where an earth cable forming part of the station earth network will already exist in close proximity. However, for motors fed by single-core cables, there is not likely to be an existing earth cable in close proximity to the power cables for the entire length of the route and, in these cases, it is necessary to provide an earth cable between the supply switchgear and the motor terminal. This earth cable is run in close proximity to its associated motor single-core cables.
For 11 kV and 3.3 kV plant, the 430 V and 55 V rise of earth potential criteria may not both be met. The possibility of transferred zero earth potential, via structural steelwork or adjacent electrical plant with its own earth return connection, cannot be ignored. Therefore, where paths exist for such 'transferred potentials, immunity must be given. This immunity is provided in these specific cases by installing local bonding between all adjacent plant and between plant and steelwork to which personnel may make simultaneous contact. Alternatively if there is a station earth bar connection point locally, the plant may be bonded to this.
For 415 V fuse-protected circuits the rise of earth potential under earth fault conditions will be in excess of 55 V and therefore local bonding may be necessary dependent on the protection clearance time. As shown in Section 4 of this chapter for motor circuits, the fuse size is selected for starting conditions rather than full-load current and is therefore relatively large. This means that to keep the conductor/armour loop resistance to a sufficiently low value to clear an earth fault in less than 0.46 seconds, the cable route length would have to be severely restricted or the cable size would have to be substantially increased. In this situation the economic solution is to provide local bonding on 415 V motors in a manner similar to that for I I kV and 3.3 kV circuits, to give immunity from transferred potentials. However, for feeder circuits other than those for motors, the fuse size will be more closely matched to the cable and therefore it is considered more economic to ensure that the pro-
tection operates in less than 0.46 seconds than t o provide local bonding. In making this judgement, account has been taken of the cost and difficulty of providing local bonding on all small plant such a s switches and light fittings. To ensure that the protectio n operates within the required time limit, the
armour loop resistance is controlled as
Section 4 of this chapter.
For remote outbuildings which are well outside th e area covered by the main earth electrode system, such as might be the case for a CW pumphouse, there i s some advantage in installing local earth electrodes.
Normally a pair of electrodes should be provided t o enable one to be disconnected for testing with the station operational. These electrodes will assist in reducing the rise of earth potential and hence transferred, touch and step potentials.
11.3.3 Lightning protection
As discussed in Section 12 of this chapter, it is necessary to connect the lightning protection system to the station earth network. The details of the required connections are also given in Section 12.
11.3.4 Additional considerations
The requirements of British Standard code of practice CP1013: 1965 should be complied with by earthing each of the following:
• The neutral points of each separate voltage ,istem.
• Apparatus frameworks and other non-cur |
car- |
rying metalwork associated with each syst , |
e.g., |
transformer tanks and the armours of pow. Ales.
•Extraneous metalwork not associated with power systems, e.g., boundary and transformer fences.
11.4Earth electrodes
The purpose of this section is to give a worked example for sizing an earth electrode system using the principles already given in Section 11.3.1 of this chapter. During this process, alternative types of electrodes are assessed for their suitability for power station applications. The types of electrode investigated are as follows:
•Sheet steel piles.
•Cylindrical steel piles.
•Vertical earth rods.
•Buried horizontal strip.
The calculations show that a considerable length of buried strip or a large number of earth rods would be required to dissipate the fault currents associated with
556