Добавил:
Опубликованный материал нарушает ваши авторские права? Сообщите нам.
Вуз: Предмет: Файл:

reading / British practice / Vol D - 1990 (ocr) ELECTRICAL SYSTEM & EQUIPMENT

.pdf
Скачиваний:
9
Добавлен:
17.07.2023
Размер:
30.18 Mб
Скачать

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cable performance under fire conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r this oxygen index test is very reproducible

niques, the temperature index test is time consuming

 

 

 

 

 

 

e

n excellent method for quality control of

and is less reproducible than an 01 test because of

 

 

 

 

 

 

 

0,1 forms aused in reduced propagation cable systems.

sample deformation at higher temperatures. It is not

 

 

 

 

 

 

nds

 

 

 

 

 

 

 

ia

rou-

 

 

 

 

 

 

 

 

therefore considered practical as a routine test. It is

 

 

 

 

d previously, a high 01 does not necessari-

-

 

[

ate

 

 

 

 

 

 

 

 

however considered by many manufacturers to be a

 

 

.d

a 1,etter flame propagation performance and,

\ ',:,

 

 

for routine OA tests, it is necessary to con-

useful aid to material assessment.

 

 

bot h the minimum and maximum 01 levels. This

 

 

 

 

L, c

a,:hio.ed by measuring the 01 of materials of

8.4 Smoke tests

 

 

 

 

 

,albjected to reduced propagation type tests de-

,:, L

b ed in the previous section. A positive and negative

 

 

 

rLince (in the order of ± 1.5%) is then agreed with

8.4.1 Test methods

•,,,, manufacturer for routine tests. It should be noted

There are two common methods of quantifying smoke

 

 

r o

 

apply this principle the absolute OI must be

 

 

 

emissions:

 

 

ireci. Therefore, when using Appendix A of BS4066

.re

 

 

 

 

routine testing of power station cables, it is im-

Measurement of light obscuration through smoke.

o r

 

,,,,riant :hat the complete test in Section A8 is specified

Weighing of smoke particles after trapping them in

 

 

 

 

than the abbreviated test in Section A10 which

111% checks for a minimum. In summary, 01 tests are

 

a filter.

 

 

 

 

to check whether a material has changed rather

 

 

'Lin to see if it meets a minimum 01 requirement.

Considering these methods, the weighing of smoke

 

 

 

ariation of this type of test which is gaining

particles ignores the effect that particle size has on

pu11r1ty is to measure the temperature index of the

visibility, i.e., a lot of small particles will reduce visi-

:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

•„i:crial. The apparatus used for this test is similar to

bility more than a fewer number of large particles for

ijl

 

ti,e(1 for oxygen index with the addition of heaters

the same total weight. Measurement of light obscura-

.rou rul the glass chimney. Both the oxygen/nitrogen

tion is therefore considered more meaningful where

 

 

and test temperatures are varied to enable a plot

it is desired to obtain a degree of correlation between

of the

 

 

type shown in Fig 6.103 to be prepared. The

tests and the visibility of, say, exit signs in a real fire

, ,mperature index of the materials is taken to be the

situation.

.,. amcrature at which the sample just supports corn-

 

Early investigations into smoke emission were carried

jon with an oxygen concentration in nitrogen of

out using small samples of cable materials in bench

:110 Whilst this type of test arguably gives greater

top equipment such as the USA National Bureau of

',formation on the material than a plain oxygen index

Standards (NBS) or the Arapahoe smoke chambers.

 

 

a must be remembered that it is still only a test

The NBS is an optical method in which a sample is

ci materials. Like the OI test it cannot be considered

burnt (either in a flaming or non-flaming mode) in a

,albstitute for full scale propagation tests, since it is

chamber having a volume of approximately 0.5 m 3 .

ciilccn

 

 

that both the quantity of cable and the cable

Light transmission is measured using a photometric

•. , ari pration affect flame spread. With present tech-

system with a vertical path. The Arapahoe is a gravi-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

metric system in which a sample is burnt using a small

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

propane-gas burner and the smoke particles are trapped

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in a filter and weighed. More recent work has shown

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

that smoke emission is highly dependent on the number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of cables involved and their configuration, i.e., spaced

 

 

35

 

 

 

 

 

 

 

 

 

 

 

or touching formation. The situation is similar to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

testing for reduced propagation characteristics where

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tests on materials or single cables are inadequate as

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

type tests. These bench-top tests are now therefore only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• ;EN

 

 

 

 

 

 

 

 

 

 

recommended for routine tests such as quality control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and for the preliminary evaluation of materials.

 

 

25

 

 

 

 

 

 

 

 

 

 

 

 

For type tests it is considered essential to carry

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

out large scale tests on a typical cable arrangement.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

One such large scale test method which was developed

 

 

!'

 

 

 

 

 

 

 

 

 

 

 

by the London Transport Executive (LTE) in the early

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1970s is the 3-metre cube and this has now gained

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

international popularity. The test equipment which is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

shown in Fig 6.104 consists of a cube of 3-metre

 

 

 

 

 

 

 

100

204

250

300

side and normally constructed from metal sheet. A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

door containing an inspection window is provided in

 

 

 

FIG. 6.103 Graph showing temperature index

 

 

one side for access purposes. Small windows are pro-

 

 

 

 

 

vided in opposite sides of the cube to enable a light

527

Cabling

Chapter 6

 

 

 

LADDER FOR

MOON TWO

CABLE SAMPLES

 

 

I

/

 

 

 

 

 

 

 

 

/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SOT RCS

 

3AS BURNER

 

DETECTOR

 

 

 

_ORAL:Or-if

 

 

 

 

 

 

 

 

SCREEN

 

 

 

 

 

WINDOW

 

 

 

 

 

 

 

 

 

 

,NINDOW

 

 

Jr,

 

 

 

 

 

 

 

 

 

 

 

 

FAN

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TiEiGHT OF ENCLOSURE = 3,,

ACCESS DOOR ,VITH

OBSERVATION WINDOW

FIG. 6.104 3-metre smoke cube

source and photoelectric cell assembly to be mounted externally, so that the attenuation of light with increasing smoke density can be measured. The photocell is designed to have a response close to that of the human eye. A fan is provided to mix the smoke and give reproducible results. Since a large number of manufacturers and test authorities have constructed this test equipment, there is clearly a need to ensure they all have similar characteristics. This can be achieved by burning known ratios of toluene/alcohol in the cube and checking the light attenuation against reference values. The 3-metre cube is now a well established test equipment that is relatively simple and very practical.

Having established suitable test equipment to measure smoke from a representative section of cable installation, we must now consider the fire model. The fire model used by LTE consists of burning a number of cables by placing them in horizontal formation over a fire source consisting of a tray containing I litre of alcohol. The number of cable samples is selected such that the test configuration contains 2-3 kg/m of combustible material which is considered typical of an underground railway installation. However, within a power station, higher densities of cables are involved and a number of routes are vertical; the LTE fire model is therefore not suitable for power stations. Considering power station applications, quite clearly for smoke tests it is desirable to use a vertical array of cable samples known to be the more onerous case. This follows the same principle as for reduced propagation tests. Taking this one step further to be consistent, the same type of fire model should be used for both the reduced propagation and smoke tests (i.e., a vertical ladder with a propane-gas burner fire source). In practice it is not possible to use the identical arrangement for smoke

tests because of limitations of the 3-metre cube te st equipment, e.g., the cable quantity subjected to the test has to be limited to avoid smoke saturation i n the cube. Although it is not possible to carry out smoke tests in the 3-metre cube on the largest array of cabli ng used in a power station, it is possible to use a representative sample which is adequate to correlate smoke emission with the effects of propagation.

The fire model selected for type tests is shown in Fig 6.105 and consists of cable samples 2 metres long, wired to a vertical ladder. The number of cable sampl es is selected to give a loading of 5 kg/m of non-met allic material and the cables are mounted in the same formation as detailed for reduced propagation in Section 8.2 of this chapter, i.e., power cables spaced and control cables bunched. It is important to note that cable formation is a dominant factor in smoke production and that variations in cable spacing can significantly affect results. The fire source itself consists of the same propane-gas ribbon burner and flow rates as used for the propagation test. The test regime consists of apply. ing the fire source for a period of 25 minutes, after which it is extinguished and the samples are left burn or smoulder until maximum smoke productioi: has been achieved. By this method both flaming and non-flaming modes can be assessed.

CABLE SAMPLES 2m LONG

LAODER

GAS BURNER

II

FIG. 6.105 Cable sample arrangement for smoke test

During the test, the intensity of the light received by the photocell is monitored on a chart recorder as

a measure of transmittance. The recorded light trans- mittance can be converted to absorbance using the

formula:

528

' h ere

Cable performance under fire conditions

A, = login 1 0/ 1- t

initial luminous intensity

kl here IC)

-- intensity of light beam through smoke

t

where D = visibility distance

K = parameter dependent on light level and type of exit sign

From Equations (6.8) and (6.9):

ormal to present the results as standard absor- ;,,i ,1, n A„ by the formula

A,) -= A, x

D =

KY

(6,10)

 

A0 n

-.s. volume of test chamber, m 3 t' = optical path length, m

,is hen defined as the absorbance produced across he faces of 'a 1-metre cube when the test installation

!, burnt under the given conditions.

The calculation for A o ignores the effect of any ‘riloke deposited on the windows of the optical system.

flis is because experience has shown that the absorb-

.111,:e associated with this deposition on the windows ,, ;mall compared to the absorbance associated with he smoke in the cube, and negligible error is caused i2noring this factor. Where it is wished to take :MN factor into account, the absorbance associated with Jcposition on the windows can be measured after clearmoke from the cube and the appropriate correc-

!i ons made.

Clearly A 0 can be calculated at any time during ;he test but the most significant measurements are „on,idered to be at the end of the test flame appli- -aion period, A, (ON), and the maximum after the :lame is extinguished, A 0 (OFF). Quite clearly the inft,t critical factor is the total smoke generation drid since this is achieved during the A o (OFF) period,

,hould be used for the acceptance criteria. A typical !e,i requirement would be that A, (OFF) should not ,A,eed 10.

84.2 Use of test information

I la ,,ing defined a test method we can now try to re-

.i e

information gained to what

would happen

Ii power station locations under fire

conditions. One

. 1mhod of achieving this is as follows:

The 'expected absorbance' in a particular location

• ,q1N.en by:

 

A, = A o n/V

(6.8)

A0 --: absorbance across the faces of a 1 m cube found from test

V

dispersal volume, M 3

nfactor depending on quantity of cable involved

A, = —

(6.9)

D

 

Now the factor 'n' must relate the quantity of cable material tested to that contained in the power station installation. It is suggested that the smoke test be carried out on an array containing 5 kg/m of non-metallic combustible material. Therefore, assuming a linear relationship:

n=

installed mass

 

installed mass

 

 

 

test mass

5

 

Typical values for the parameter K are given in Table 6.23. These parameters are based on experiments carried out in a 3-metre cube, using a random sample of observers to assess the visability of typical signs over a range of distances through a known density of smoke.

TABLE 6.23

Typical values for the parameter K

Lighting

Value of K

 

 

Self-illuminated signs

3.0 — 3.5

Reflecting signs in well lit areas

1.5

Reflecting signs in poorly lit areas

1,0

 

 

As an example, consider a cable flat 2 m wide by 2 m high and 50 m long. Using a test acceptance criterion of A 0 (OFF) = 10 and assuming one cable tray carrying a non-metallic combustible cable mass of 10 kg/m, for self-illuminated signs the visibility would be:

D =

kV

3 x 2 x 2 x 50

30 m

 

Aon

10 x 10/5

The results obtained by this process should only be used for guidance since the process assumes an even dispersion of smoke particles and ignores any irritant affect that smoke may have on the eyes.

8.5 Corrosive gas emissions

At present, bench-top tests on samples of materials taken from cables are considered the most practical method of assessing corrosive gas emissions.

The most commonly used of these bench-top tests is that specified in IEC 754. This test method requires

529

Cabling

Chapter 6

 

 

 

that approximately one gram of material is pyrolysed in a combustion tube using an electric furnace. Ramp heating is used with a maximum temperature of 800 ° C and the resultant gases are analysed by titration methods. Hydrogen chloride and hydrogen bromide are assessed as hydrogen chloride and the limit of sensitivity of this method is 0.5%. The difficulty with this test method is that it only assesses two of the halogen gases and, whilst hydrogen chloride may be potentially the most aggressive, other corrosive gases cannot be ignored. Another drawback with this method is that the limit of detection is 0.5% and may not be adequate for recent developments in low fire risk cables.

The CEGB has therefore developed a test method which monitors pH and conductivity which can detect all acid species. A diagrammatic arrangement of the test apparatus is given in Fig 6.106. The combustion arrangement is similar to EEC 754 in that the sample is pyrolysed in a combustion tube using an electric furnace and ramp heating up to 800 ° C. A sample size of one gram is used and the combustion products are drawn through distilled water of which the pH and conductivity is measured. Since hydrogen chloride is

of particular concern, a sensitive chloride ion electrode is included which can monitor to a level of 0.05%.

Experimental work has been carried out for the CEGR to assess the corrosive effects of the more commo n acid gas species on items such as printed circuit boards and relay contacts. From this work it is possible to judg e the maximum concentration of gas in parts per milli on (PPM) that is tolerable from a corrosion aspect. Using this information, together with a knowledge of th e quantity of cable material likely to be consumed in a fire and the station volume in which it may be released, it is possible to predict pH acceptance levels for the test method discussed.

8.6 Toxic gas emissions

At present, bench-top tests on samples of material taken from cables are considered to be the most practical way of assessing toxic gas emissions. There are several such tests available but the most established in this country is that defined in the Ministry of Defence specification NES 713. This test procedure has therefore been used as a basis for CEGB assessment of toxic gas emissions.

OR!ED

THEnmo-

COUPLES

COMBUSTION

TUBE

_17

pH

 

 

 

 

 

 

VHION

 

 

11

 

 

 

 

 

 

 

 

METER

 

 

 

 

 

 

 

 

 

 

 

 

 

CELL WITH CP TO

FIVE PROBES

OE-IONISED

H 2 0

MAGNETIC

STIRRER

Fm. 6.106 Corrosive gas emission test equipment

530

test method consists of . burning a four

,1::: e, aCaEl pGmetre. The chamber is constructed from a

1(typically polypropylene or polycar- iiilai [ei rni,a a tranyarent access door in wohnieside.irin a sealed chamber having a volume of

:„Iritille is burnt using a gas burner in

ch the

1‘..

, , ',remixed vith air. A fan is used to ensure rapid

:1

 

f products of combustion with the air in the

 

o

 

 

:bcr. Samples of the combustion products are drawn

 

o t- [he tes: enclosure through gas detection tubes.

[

as detection tubes consist of a glass tube filled

,tals which change colour when they react with

 

 

..:Iccied gas type. A selection of gas detection tubes

 

to assess the toxic gas emissions that are likely

obtained from cable insulating materials. ()\icity index can be calculated from the measured

ncentrations using IDLH values. The immediate

j.til2er to life and health (IDLH) value, as defined r, the NIOSH/OSHA 'Guide to chemical hazards',

a maximum level from which one could ,.„re %satin 30 minutes without any escape-impairing

:liriorns or any irreversible effects on health.

Cable accessories

 

PLASTIC WASHER

 

EARTH BOLT

 

 

 

 

 

 

ARMOUR CLAMP

 

METAL

 

 

 

 

 

 

 

 

 

EXTENSION TUBE

 

 

 

 

 

 

 

 

 

CABLE ARMOUR

 

 

 

 

 

OUTER

 

 

 

 

 

NE;SPR ENE SEAL

 

0 KNU

 

 

 

ASSOCiATEO ENCLOSURE

PLASTIC

OU 7 E. SEAL Vu

NSULATECI

 

 

OR GLANO PLATE

\ BUSH

 

 

 

 

NEOPRENE

 

 

 

 

FACE SEAL

 

iNSULATED SECT:ON

9 Cable accessories

9.1Cable glands

g1.1 Background to gland design

elands are used to terminate the outer finishes ables (i.e., inner sheath, armour and outer sheath) to take the insulated conductors through into the

•.j uiptucnt. The gland therefore locates the cable at the

.,;inpment and is required to form a moisture seal to

..,,t11 the cable and the equipment. Glands also provide iieans of making connections to the armour for rig when required. Where connections to earth are

.,itlircd, it is important that the gland is fitted with an

!cgal earth lug so that a bond can be installed to

•.kc the fault current direct to the earth bar. Without provision the fault current would have to flow to

1,ia the less secure route of gland threads, gland H.:!c securing bolts and equipment casing.

Hie requirements for cable glands are specified (ii)CD Standard 190: 'Insulated mechanical cable

:.trids'. These have been developed as replacements

, r the

traditional all-metal gland designs which are

, pc,:itied

in BS6I21: 'Specification for mechanical

...111J5 Part I — metallic glands'. Insulated glands the cable armour to be isolated from the gland ;'.ate and hence earth. Typical arrangements of insu-

•kd glands are shown in Fig 6.107. Insulated glands with GDCD Standard 190 must incorporate following features and offer certain advantages

cr metallic glands to BS6121, Part 1:

Insulated glands allow single-point bonding of sin- gle-eore cables to prevent armour circulating currents

and hence permit current rating to be maximised.

FIG. 6.107 Typical arrangements of insulated cable glands

Insulated glands allow single-point bonding of control cables to prevent circulating or fault currents flowing in the armour and hence reduce the risk of interference in control and instrumentation circuits.

Insulated glands allow cable armour to be isolated from earth to enable cable outer sheath integrity to be tested.

An integral earth lug is specified to provide an adequately tested means of connecting the cable armour to earth.

GDCD Standard 190 requires that all glands for use on power cables are subjected to short-circuit tests.

A screen terminator can be provided, as shown in Fig 6.108, to allow the copper tape screen of 11 kV cables to be electrically connected to the cable armour.

GDCD Standard 190 requires glands to accept a wider range of cable sizes.

9.1.2 Gland construction

GDCD Standard 190 covers a range of glands which are identified by 'Class Number according to armour type and gland configuration, i.e., whether bonding connectors or screen terminators are required. The armour

531

:nust be
greater
Iizes and
of 'aye
.Iled kA
,ble
indeed

PIP

Cabling

 

 

Chapter 6

 

 

 

'NSuLA'ED PUSH

PLAS7PC SASHEA

 

OUTEP 'SEAL

mETAL EX TENSiON r eE

 

ASSE . ,! BLY

NITH .ICOSAL SCREE4

 

 

 

 

TERki NATCR

 

 

A R MOUR L O CK

 

LOCK N uT

JUBILEE CLIP

CABLE COPPER NEOPRENE FACE SEAL

 

TAPE SCREEN

 

 

Fici, 6.108 Insulated gland with copper tape screen terminator for use on 11 kV cables

types covered are aluminium wire, aluminium strip, steel wire and double steel tape. To avoid corrosion problems, for aluminium armour the gland body is constructed from aluminium and for steel armour the gland body is made from brass. The glands include an outer seal, to seal between the gland and the cable outer sheath. A gland plate seal is also provided to seal between the gland and the gland plate. Inner seals, to seal between the cable inner sheath and the gland to prevent moisture entering the cable armour area are not considered necessary, as cable boxes are normally kept in a dry condition. In addition it is essential that compression-type inner seals are not used on cables insulated with materials such as low-density polythene, since this is likely to flow from under the seal during load cycling and reduce the dielectric strength of the cable.

Multipair cables, as described in Section 3.6 of this chapter, have a drain wire provided to enable connections to be made to the screen. Whilst insulated terminators can be provided on the gland for this drain wire to be terminated, it is normally more convenient to provide an insulated block of terminals in the equipment to terminate the drain wires for connection to each other, or to earth, as appropriate.

The nisulated portion of the gland is designed and tested to withstand 2 kV for I minute. The figure of 2 kV matches the design criteria for rise of potential on single-point bonded cable armours under fault conditions, this figure also being the minimum voltage withstand for cable sheaths. Quite clearly, if gland bodies can rise to voltages of up to 2 kV at the 'floating end' then insulated shrouds must be fitted for personnel safety. Where control cable glands are not bonded to earth these must also be shrouded to protect personnel

from transferred potentials. There is no requirement to shroud glands that are bonded to earth and

this would he physically difficult because of tj-k: ing connections.

With respect to short-circuit tests, it is jud_ . all power cables that could be fitted into gla of 40 mm and smaller would be fuse prote , therefore these sizes of glands are tested at 13.1 kA for 0.1 s. Gland sizes of 50 mm an may accept cables that are circuit-breaker and these are tested at a short-circuit level

for up to 1 s depending on the capability of armour.

Insulated glands for use with wire braid, -dell as on flexible cables, are not required since such cables are normally short and there is no risk of circulating currents. Standard CX glands to B56121 are therefore used for braided cables.

9.1.3 Gland sizing

When sizing cable glands the following factors must be taken into account:

The dimension over the cable inner sheath (under armour) must be smaller than the gland ! - ore.

• The dimension over the cable outer she smaller than the fully-opened outer seal

than the test mandrel size to ensure an ad _late seal.

The gland must be selected for the armour Mgt material and size.

There is not a large overlap in cable accommodation between gland sizes and therefore gland sizing should be carried out on the cable manufacturers' dimensional

532

 

 

 

 

 

Cable accessories

 

 

 

 

information rather than that obtained from cable stand-

 

be bolted to equipment. Alternatively, some manufac-

3rds. For this reason it is normally the responsibility

turers prefer to produce lugs by forging solid bars.

o f

.the cable installation contractor to ensure that the

A compression-lug fined to a single-core cable can be

 

manufacturer is supplied with all relevant cable

seen in Fig 6.116.

idndprior to manufacture of glands.

 

The lug is applied to the conductor using dies to

Jii

 

 

compress the fitting down onto the conductor. The

 

 

 

 

g 1.4

 

Installation

large mechanical forces required to complete this op-

 

eration are provided by a hydraulic tool into which

p 1,

normal practice to have equipment supplied with

the dies are fitted. Although these large mechanical

 

3c h a bie gland plates that are undrilled. This is

forces tend to break up the tenacious high electrical

['. c othe at the time of ordering equipment, the cable

resistance aluminium oxide film on the conductor and

 

and hence gland size are unknown. It is normally

fittings, to produce a good connection it is still im-

 

responsibility of the cable contractor to drill the

perative that surfaces are adequately prepared. It is

,21 and plate and fit the gland to the cable and equipment.

therefore required that fittings are factory cleaned by

Ciiand plates should be non-ferrous for cable circuit

shot blasting with aluminium oxide grit and are then

,,itirvis of 400 A or greater.

i mmediately dipped in petroleum jelly, or an equi-

 

Cables should be set as far as practicable in their

valent covering, to prevent further oxidation. Cable

ri aI position before glanding commences. This is to

conductors are cleaned with a stainless steel wire brush

,pioid

differential movement, e.g., between armour and

and immediately coated with petroleum jelly prior to

oiner

sheath, which could result in an ineffective seal

compression. Lugs are available for use on circular

should the cable be moved excessively after glanding.

stranded, circular solid and shaped solid aluminium

Ii is tiood practice to cleat all cables at a distance of

conductors.

[l o t more than 1 m below the gland to relieve glands

 

Properly designed compression fittings provide good

dud dand plates of the cable weight and of the stresses

reproducible results without the skill necessary to pro-

 

up by thermal cycling of the cables. Even after

duce a soldered connection. To assist in quality control

01 ,: s e precautions, it is not considered good practice

the following facilities are expected:

!0

use top-entry glands on equipment located out of

• Fittings to be marked with manufacturer's name,

doors.

 

 

 

identification number and appropriate conductor

Finally after installation of the glands has been

 

,ompleted all nuts should be checked for tightness. It

 

size.

should also be checked that a gap exists between the

• The fitting to be marked to show the position at

land body and armour clamp as this gives assurance

 

which the compression die is to be applied unless

:hat the armour wires are locked in the clamp.

 

controlled by other means as the tool is applied.

 

 

 

 

 

9.2 Power cable conductor terminations

A crimping code is to be marked during the for-

 

mation of the crimp so that the crimping die used

This section details methods that are used to terminate

 

can be identified.

 

 

;he conductors of power cables and connect them to

• The compression operation must not be interrupted

„Iiiipment. The conductor connection clearly must be

 

until complete and the tool must be designed to pre-

,dpable of carrying the cable full - load current without

 

vent this happening other than by deliberate action

o■ ,:rheating and must be mechanically robust to with-

 

by the operator.

 

 

any short-circuit forces.

Hydraulic tools are to be fitted with a pressure relief

The traditional method of using soldered lugs to ter-

 

valve that will operate at the end of the compression

minate conductors has now been completely replaced in

 

poker stations by compression or mechanical fittings.

 

operation to show that this is complete.

One reason for this is that it is a highly skilled job to

 

 

tKe soldered lugs, particularly on aluminium conduc-

The test requirements for aluminium compression fit-

;ors, and if full penetration of solder between strands

tings are given in Engineering Recommendation C79

1, not achieved overheating in use can occur. Secondly,

(1972) — 'Type approval tests for connectors and

, oldered lugs are not recommended for use on poly-

terminations for aluminium conductors of insulated

Merle

cables having a designed limiting short-circuit

power cables'. A British Standard, BS4579: Part 3: 1979

.omiductor temperature of 250 ° C since solder softens

— 'Mechanical and compression joints in aluminium

am this

temperature.

conductors', is based on Engineering Recommendation

 

 

 

 

C79 and gives similar requirements. The test regime

9.21 Fittings for aluminium conductors

consists of preparing 6 samples and subjecting them

to:

(o rnpressjonlugs typically consist of an aluminium

 

Ube

of a suitable size to fit over the conductor, which

Initial resistance measurements.

Has

been

squashed at one end to form a palm that can

Short-circuit tests (optional).

 

 

 

533

Cabling

Chapter 6

 

 

 

Electrical load cycling test — 2000 cycles with resistances and temperatures measured every 100 cycles.

Tensile test.

The test results are analysed to check whether the compression fittings have remained stable throughout the test.

Engineering Recommendation C79 was published before the large scale introduction of elastomeric cables; hence the load cycle test temperature of 80°C above ambient and the short-circuit test temperature of 160 ° C are appropriate to the cables commonly in use at that time, i.e., paper or PVC insulation. When dealing with fittings for elastomeric cables (e.g., XLPE or EPR), it is considered appropriate to increase the load cycle test temperature to 90 ° C above ambient and the short-circuit test temperature to 250 ° C.

As already stated, the short-circuit tests are optional and the choice depends on whether the fittings are going to be used on circuits protected by HBC fuses. As discussed in Section 4.2.1 of this chapter, multicore power cables are always fuse protected and there is no requirement to carry out short-circuit tests on fittings for shaped aluminium conductors. Single-core cables with stranded aluminium conductors are normally associated with circuit-breaker controlled circuits. Fittings for these must therefore be short-circuit tested. Fittings for circular solid aluminium conductors are associated with earth cables. Earth cables of 150 mm 2 and larger are used to bond plant that is associated with circuitbreakers, so the conductor fittings must be short-circuit tested. Earth cables smaller than 150 mm 2 are used to bond plant protected by HBC fuses and there is no requirement to have short-circuit tests carried out on these sizes of conductor fitting.

At the time of writing there is no published British or IEC Standard to control dimensions of conductor fittings. It is therefore left to the user to specify dimensional constraints, which is essential to ensure that clearances and creepage distances are maintained within standard terminal arrangements. British Standard BS5372: 1976 gives requirements for cable terminations for electrical equipment.

9.2.2 Fittings for copper conductors

The construction method for compression fittings for copper conductors is similar to that for aluminium which was discussed in the previous section. Although not mandatory it is normal practice to tin copper fittings. The requirements for tools and dies, and for marking (given in Section 9.2.1 for aluminium fittings) are considered to be equally relevant to copper fittings.

Test requirements for copper fittings are given in BS4579: Part 1: 1980 — 'Performance specification for compression joints in electric cable and wire connectors'. This specification requires six specimens to be prepared and subjected to:

Initial resistance measurement.

500 load cycles with resistance measurements every

50 cycles.

Final resistance measurement.

Tensile test.

It should be noted that, unlike aluminium, the test regime for copper fittings does not include an optio n of short-circuit tests. Experience from short-circuit tests on equipment in which conductor fittings have necessarily been included have demonstrated a need to design fittings to meet these conditions adequately. For fittings to be used on circuit-breaker controlled circuits, it is therefore recommended that short-circuit tests are carried out in a similar manner to that already prescribed for aluminium conductor fittings. A further point to bear in mind is that BS4579: Part 1 limits the fittings to use on conductors having a maximum conductor temperature of 85 ° C. Therefore, where fittings are required for use on elastomeric cables (e.g., XLPE or EPR) which operate at a continuous conductor temperature of 90 ° C, a more onerous test regime is required. In these cases it is recommended that the load cycling be carried out at 90 ° C above ambient as previously proposed for aluminium fittings in Section 9.2;1 of this chapter.

In practice, the vast majority of copper power cables used in power stations are small multicore types insulated with PVC and protected by fuses for which the test requirements given in BS4579: Part 1 for conductor fittings are more than adequate.

The comments given in the previous Section 9.2.1 regarding conductor lug dimensions and termination accommodation are equally applicable to copper fittings.

9.2.3 Formed terminations

Formed terminations are a means of terminating solid aluminium conductors by squashing the conductor flat and punching a hole through it for the terminal equipment fixing bolt. The operation is carried out using a hydraulic tool and special dies. An arrangement of formed terminations is shown in Fig 6.109.

This idea was proposed in the early 1960s (Burki and Sabine, 1963 [221), but it did not gain any immediate popularity possibly because of concerns about the mechanical and electrical integrity of the flattened palm. Formed terminations were reassessed by the Central Electricity Research Laboratories during the early 19705 and considerable effort was devoted to obtaining optimum palm dimensions for mechanical and electrical performance. The advantages of this system are:

The sensitive interface between conductor and compression fitting is eliminated.

The termination length is considerably reduced, relieving space problems in terminal boxes.

534

Cable accessories

the different forms of terminations for use on fuse protected cables and for earth cables of 150 mm 2 and

 

 

 

 

 

 

larger. Figure 6.110 shows the type of hydraulic tool

 

 

 

 

 

 

head and dies used to produce formed terminations.

 

 

 

 

 

 

Formed terminations for use on fuse-protected cir-

 

 

 

 

 

 

cuits have been tested to BS4579: Part 3, the require-

 

 

 

 

 

 

ments of which were discussed in Section 9.2.1 of this

 

 

 

 

 

 

chapter. These tests were carried out with the formed

 

 

 

 

 

 

terminations bolted to both aluminium and plain cop-

 

 

 

 

 

 

per connection bars. Although there is no requirement

 

 

 

 

 

 

to carry out short-circuit tests on terminations protected

 

 

 

 

 

 

by HBC fuses, such tests were carried out (to a final

 

 

 

 

 

 

conductor temperature of 160 ° C) to give confidence

 

 

 

 

 

 

in the system. A large number of the samples that

 

 

 

 

ALTERNATIVE CONDUCTOR

 

 

 

 

POSJTIONS GrtihNG

 

 

 

 

 

 

underwent the 2000 load cycles were simultaneously

 

 

 

 

REVERSE ANGLE TO PALM

 

 

 

 

 

 

 

 

 

 

 

 

 

subjected to 100 Hz vibration of approximately 0.5 mm

 

 

 

 

 

 

amplitude without ill effect.

 

 

 

 

 

 

Earth cable formed terminations which are designed

 

 

 

 

 

 

to have good short-circuit performance have been tested

 

 

 

 

 

 

successfully to demonstrate their performance at short-

 

 

 

Flo. 6.109 Formed terminations

circuit conductor temperatures in excess of 325 ° C.

 

 

 

 

 

The cost of purchasing and stocking the fittings is

9.2.4 Bolting terminations to equipment

 

Care is required in the selection and preparation of

 

 

eli minated.

 

The work content and hence the time required to

joint surfaces, particularly when dealing with alumi-

 

nium. With aluminium, an oxide immediately forms

 

 

terminate cables is reduced.

 

 

on its surface and this is both tenacious and insulating

One set of dies can cope with different-shaped

by nature, thus requiring special measures to be taken.

 

 

conductors.

After suitable preparation, an aluminium surface can

 

 

 

 

 

 

be bolted direct to another aluminium surface or to a

 

irtned terminations are currently suitable for circular

plain copper surface. Aluminium can also be bolted

or

shaped solid aluminium conductors from 35 mm 2

direct to hot-dipped tinned copper but not to copper

 

 

; 300 mm 2 . It is not possible to use this tech-

that has been electroplated with tin or silver. This re-

:Nue on conductor sizes smaller than 35 mm 2 , because

striction is attributed to the inability of soft platings

:here is insufficient conductor material to form a

to crack the aluminium oxide. Since it is difficult on-

 

 

of adequate mechanical integrity.

site to ascertain what type of plating has been used,

 

 

Vultieore cables having shaped solid aluminium

it is recommended that a brass transition washer of

5. nthictors are normally only used for fuse-protected

appropriate diameter is always used between aluminium

 

 

 

Therefore, since there is not an onerous short-

and plated copper. The grade of brass used should have

 

r‘iiit requirement, the palm area and bolt sizes are

a temperature expansion coefficient that is approxi-

 

 

 

to give optimum performance at the highest

mately midway between those of copper and alumi-

... , iitinuous conductor operating temperature. Since

nium. This helps to reduce differential movement at

 

 

cables having circular solid aluminium of less

the interfaces and hence the shearing of contact points.

. :ian 150 inm 2 are associated with the bonding of fuse-

The brass washer surfaces must of course be suitably

;,

7oiected equipment, the same palm configuration and

prepared on site, or prepared and protected at the

oicnce) dies can be used.

manufacturer's works. To avoid this complication, it

 

 

Furth cables having circular solid aluminium con-

is recommended that aluminium or plain copper ter-

Jueiors of 150 mm 2 and larger may be used to bond

mination interfaces are provided in equipment.

squipment controlled by circuit-breakers and therefore

The preparation of aluminium bar or formed ter-

Yiese are required to have an adequate short-circuit

mination palm contact areas, should consist of abrading

;-

ertormance. Since earth cables do not have to carry

the surface with a stainless steel wire brush until all

•'" appreciable continuous current, the palm area of

visible traces of oxide are removed and the surface

 

e formed termination may be reduced in favour of a

presents a matt finish. The surface must then be coated

:nore robust (thicker) palm to meet short-circuit re-

immediately with petroleum jelly to protect it and pro-

:iiiirernents. The radius between the palm and the un-

duce a low resistance joint. Aluminium compression

,irmed

conductor is also larger on earth cable formed

fittings are normally supplied factory cleaned and these

.;:r

 

 

 

ntinations, at the expense of palm length, to give

only need to be lightly smeared with petroleum jelly on

-rtimum short-circuit performance. Figure 6.109 shows

the mating surface.

535

Cabling

Chapter 6

 

FRONT LOCATOR

PUNCH .OLDER

CA9LF.

cAeLe

CONDUCTOR

RAM

 

 

 

 

OIL

 

 

 

 

 

 

 

 

PocKElmr, R

TO COLLECT

TERMNAL HOLE

SLUGS

FIG. 6.110 Formed termination tool

Plain copper or brass should also be cleaned with a stainless steel wire brush and immediately coated with petroleum jelly. Tinned surfaces need only be cleaned with a degreasing agent before a light coat of petroleum jelly is applied. Copper compression fittings should be supplied and packaged in a clean condition and only need a light coat of petroleum jelly on the mating palm surface.

It is important that the wire brush is made from stainless steel and that a separate brush is kept for each type of metal. If a joint is slackened for any reason it is essential that it is completely undone and remade using the appropriate surface preparations.

If aluminium is not involved, after suitable surface preparation the joint can be completed using normal diameter washers (to BS4320) between the joint materials and the fastener. With copper joints, the thin copper oxide film on the joint surfaces ruptures relatively easily to give metal-to-metal contact, therefore, the clamping pressure and hence the fastener torque is not critical.

Where aluminium is involved, because of the tenacious nature of the surface oxide, it is essential that the clamping pressure is sufficient to rupture the oxide fil m at contact spots so that metal-to-metal contact is formed. These contact points are actually crests or peaks that are formed on the contact surface by the preparation using a stainless steel wire brush. This contact pressure is clearly dependent on the surface area under the clamping washer and on the torque applied to the fastener. Because aluminium creeps under applied pressure and the dimensional change causes a relaxation in clamping load, it is important that the load is applied over as large an area as practicable. For this purpose, large diameter washers having an area complying with BS4320, Table 2, form C are used. These large-diameter washers are of sufficient area to restrict the aluminium creep whilst being small enough to generate sufficient clamping pressure to rupture su 1. face oxides using acceptable fastener torques. Washers complying with BS4320 have insufficient thickness to avoid deformation and this results in a reduction 01

536