114 • DeviceNet

Process data and Diagnostic Status

5.4.2 I/O Messaging Connections

The transfer or exchange of process data between the scanner and the I/O device is made via a „Polled I/O Connection“, „Change of State/Cyclic“ or „Bit Strobe“.

Polled I/O Connection

Slaves are cyclically polled by the master.

Strobe Function

All slaves are polled by the master by means of

 

a command.

Change of State

Messages are transmitted either cyclically by

 

the master or the slave, or in the event of a state

 

change.

5.5 Process data and Diagnostic Status

The data is transmitted between master and slave in the form of objects, a differentiation being made between input and output objects. The object architecture is defined by assembly objects which serve to group attributes of differing application objects. I/O data of different objects can, for this reason, be grouped to form a data block and transmitted by a message connection.

5.5.1 Process Image

The process image is differentiated according to input and output process images. The assembly object makes a statically configured process image available in the instances 1 ... 9.

The desired process image can be selected by setting the Produced Connection Path and the Consumed Connection Path of the individual I/O connections (Poll, Bit Strobe, Change of State or Change of Value).

The architecture of the individual instances of the assembly object is described in the following.

WAGO-I/O-SYSTEM 750

DeviceNet

DeviceNet • 115

Process data and Diagnostic Status

5.5.1.1 Assembly Instances

Permanently pre-programmed (static) assemblies in the device permit an easy and rapid transmission of input and output images from the fieldbus Coupler/Controller to the master. For this purpose, various assembly instances are provided in the fieldbus Coupler/Controller:

Output 1 (I/O Assembly Instance 1):

The entire output data image is transmitted from the master to the Controller via the corresponding I/O message connection. In this case, the data length corresponds to the number of output data in bytes. Analog output data come before digital output data.

Output 2 (I/O Assembly Instance 2):

The digital output data image is transmitted from the master to the Controller via the corresponding I/O message connection. The data length is equivalent to the number of digital output data and is rounded up to full bytes.

Output 3 (I/O Assembly Instance 3):

The analog output data image is transmitted from the master to the Controller via the corresponding I/O message connection. The data length is equivalent to the number of analog output data in bytes.

Input 1 (I/O Assembly Instance 4):

The entire input data image and one status byte are transmitted to the master via the corresponding I/O message connection. The data length is equivalent to the number of input data in bytes and one status byte.

Input 2 (I/O Assembly Instance 5):

The digital input data image and one status byte are transmitted to the master via the corresponding I/O message connection. The data length is equivalent to the number of digital input data and rounded up to full bytes. In addition, a status byte is inserted.

Input 3 (I/O Assembly Instance 6):

The analog input data image and one status byte are transmitted to the master via the corresponding I/O message connection. The data length is equivalent to the number of analog input data in bytes and one status byte.

Input 1 (I/O Assembly Instance 7):

The entire input data image is transmitted to the master via the corresponding I/O message connection. The data length is equivalent to the number of input data in byte.

WAGO-I/O-SYSTEM 750

DeviceNet