Feldbus-Koppler/-Controller • 99

Fieldbus Controller 750-806

3.2.10LED Display

The Controller possesses several LEDs for on site display of the Controller operating status or the complete node.

DeviceNet

01

02

 

 

OVERFL

A

C

C

 

MS

B

A

 

RUN

 

 

 

D

 

 

 

 

 

BUS OFF

24V

0V

 

 

NS

 

 

 

 

CONNECT

 

 

 

 

I/O

 

 

 

 

USR

 

 

 

 

Fig. 3-34: Display elements 750-806

g080602x

The module status (MS) and the network status (NS) can be displayed by the top 4 LED’s. They react as described in the following tables.

Module status (MS)

OVERFL

RUN

State of device

Meaning

(red)

(green)

 

 

 

 

 

 

off

off

no power

No power supply to the device.

off

on

device operational

The device operates correctly.

off

blinking

device in standby

The device needs to be configured or has been partly

 

 

 

configured.

blinking

off

minor fault

A minor fault has occurred. It exists a diagnostics.

on

off

unrecoverable fault

The device is defective, needs to be serviced or

 

 

 

replaced.

blinking

blinking

device self testing

The device performs a built-in check.

Table 3-3: Fault and status displays: MS

 

 

 

 

Network status (NS)

 

 

BUSOFF

CONNECT

State of device

Meaning

(red)

(green)

 

 

off

off

not powered, not online

No power supply to the device / fieldbus supply /

 

 

 

DeviceNet cable not connected and „Duplicate MAC

 

 

 

ID detection“ is not yet completed.

off

blinking

online, not connected

The device operates correctly at the fieldbus. How-

 

 

 

ever, it has not yet been integrated by the scanner.

off

on

link ok online, connec-

The device operates correctly at the fieldbus. At

 

 

ted

least one connection to another device has been

 

 

 

established.

blinking

off

connection time out

A minor fault has occurred (e.g. EPR is unequal 0

 

 

 

during a polling connection, slave is not polled any

 

 

 

longer).

on

off

critical link failure

The device has detected a fault (duplicated MAC ID

 

 

 

check error). It is unable to perform any more func-

 

 

 

tions in the network.

Table 3-4: Fault and status displays: NS

WAGO-I/O-SYSTEM 750

DeviceNet

100 • Feldbus Coupler/Controller

Fieldbus Controller 750-806

3.2.10.1.1Node Status

LED

Color

Meaning

IO

red /green

The 'I/O' LED indicates the node operation and signals faults occur-

 

/ orange

ring.

 

 

 

The Controller starts after switching on the supply voltage. The "I/O" LED flashes red. Following an error free start up the "I/O" LED changes to green steady light.

In the case of a fault the "I/O" LED continues blinking red. The fault is cyclically displayed with the blink code.

Versorgungsspannung

einschalten

Koppler-Hochlauf

“I/O”-LED blinkt

Fehler

Ja

 

Nein

 

“I/O”-LED

1. Blinksequenz

(leitet opt. Anzeige eines Fehlers ein)

1. Pause

“I/O”-LED

2. Blinksequenz

Fehlercode (Anzahl Blinkimpulse)

2. Pause

“I/O”-LED

“I/O”-LED an 3. Blinksequenz

Fehlerargument (Anz. Blinkimp.)

Feldbusstart

 

Fig. 3-35: Signalling the LED's node status

g012111d

After overcoming a fault, restart the Controller by cycling the power.

I/O

Meaning

green

Data cycle on the internal bus

 

 

off

No data cycle on the internal bus

 

 

red

Coupler hardware defective

 

 

red

When starting: internal bus is initialized

blinks

During operation: general internal bus fault

 

 

red

Fault message during internal bus reset and internal fault:

blinks cyclically

 

 

 

orange

MAC-ID is changed via SW and is different to the DIP switch setting

 

 