Fieldbus Coupler/Controller • 49

Fieldbus Coupler 750-306

3.1.5.3 Addressing

3.1.5.3.1 Fieldbus Specific

Once the supply voltage is applied, the Assembly Object maps data from the process image. As soon as a connection is established, a DeviceNet-Master (Scanner) can address and access the data by "Class", "Instance" and "Attribute".

Data mapping depends on the selected Assembly Instance of the static Assembly.

Further information

The Assembly Instances of the static Assembly are described in chapter 5.5.1.1 "Assembly Instance".

fieldbus master

Fieldbus coupler

memory area for input data

word 0

1

I/O modules

Connection

Assembly

Application

input

 

modules

 

Object

Object

Object

 

 

 

Producer

Input-

 

 

 

 

 

 

 

 

Assemly

 

 

 

 

 

 

word 255

 

 

 

 

memory area

 

Consumer

Output-

 

for output data

 

 

 

word 0

 

 

Assemly

 

2

 

 

 

 

 

 

output

 

 

 

 

modules

 

I O

word 255

Fig. 3-1: Fieldbus specific data exchange for a DeviceNet fieldbus Coupler

g012531e

Note

For the number of input and output bits or bytes of the individual I/O modules, please refer to the corresponding I/O module description.

Note

A process image restructuring may result if a node is changed or extended. In this case the process data addresses also change in comparison with earlier ones. In the event of adding a module, take the process data of all previous modules into account.

WAGO-I/O-SYSTEM 750

DeviceNet

50 • Fieldbus Coupler/Controller

Fieldbus Coupler 750-306

Example for static assembly (default assembly):

The default assembly is:

 

Output1

(I/O Assembly Instance 1)

Input1

(I/O Assembly Instance 4)

In this example, the fieldbus node arrangement looks like this:

1)1 fieldbus coupler DeviceNet (750-306),

2)1 digital 4-channel input module (i. e. 750-402),

3)1 digital 4- channel output module (i. e. 750-504),

4)1 analog 2- channel output module with 2 bytes per channel (i. e. 750-552),

5)1 analog 2- channel input module with 2 bytes per channel (i. e. 750-456),

6)1 End module (750-600).

Input process image:

Default process data, input image (Assembly Class, Instance 4)

Byte

.7

.6

.5

.4

.3

.2

.1

.0

0

 

 

 

low byte channel 1

 

 

 

1

 

 

 

high byte channel 1

 

 

 

2

 

 

 

low byte channel 2

 

 

 

3

 

 

 

high byte channel 2

 

 

 

4

 

not used

 

DI041)

DI031)

DI021)

DI011)

5

DS08 2)

DS07 2)

DS06 2)

DS05 2)

DS04 2)

DS03 2)

DS02 2)

DS01 2)

1)DI = Digital Input

2)DS = Diagnostic Status

Output process image:

Default process data, output image (Assembly Class, Instance 1)

Byte

.7

.6

 

.5

.4

.3

.2

.1

.0

0

 

 

 

 

low byte channel 1

 

 

 

1

 

 

 

 

high byte channel 1

 

 

 

2

 

 

 

 

low byte channel 2

 

 

 

3

 

 

 

 

high byte channel 2

 

 

 

4

 

 

not used

 

DO041)

DO031)

DO021)

DO011)

1) DO = Digital Output

WAGO-I/O-SYSTEM 750

DeviceNet