Добавил:
Опубликованный материал нарушает ваши авторские права? Сообщите нам.
Вуз: Предмет: Файл:
Скачиваний:
26
Добавлен:
11.10.2020
Размер:
3 Mб
Скачать

250 Application in Explosive Environments

Identification

6.5 Identification

6.5.1 For Europe

According to CENELEC and IEC

Explosion protection group

Unit category

Community symbol for explosion protected electrical components

II 3 G

 

KEMA 01ATEX1024 X

 

EEX nA II T4

Temperature class

Approval body and/or number of the examination certificate

Explosion protection group

E = conforming with European standards Ex = explosion protected component

n = Type of ignition

Extended identification

ITEM-NO.:750-400

24V DC AWG 28-14 55°C max ambient

CL I DIV 2 Grp. A B C D op temp code T4A

LISTED 22ZA AND 22XM

-02----03

4246

1-

2

090

 

Hansastr. 27

2DI 24V DC 3.0ms

 

D-32423 Minden

0.08-2.5mm2

0V 24V DI1

Di2

PATENTS PENDING

II 3 G

KEMA 01ATEX1024 X EEx nA II T4

Fig. 6-1: Example for lateral labeling of bus modules

 

(750-400, 2 channel digital input module 24 V DC)

g01xx03e

Modular I/O System

LONWORKS®

Application in Explosive Environments • 251

Identification

6.5.2 For America

According to NEC 500

Explosion protection group

Area of application (zone)

(condition of use category)

 

Explosion group

CL I DIV 2

 

Grp. ABCD

 

(gas group)

 

optemp code T4A

Temperature class

 

24V DC AWG 28-14 55°C max ambient

CL I DIV 2 Grp. A B C D op temp code T4A

LISTED 22ZA AND 22XM

-02----03

4246

0-

2

410

 

 

ITEM-NO.:750-400

Hansastr. 27

2DI 24V DC 3.0ms

 

D-32423 Minden

0.08-2.5mm2

0V 24V DI1

Di2

PATENTS PENDING

II 3 G

KEMA 01ATEX1024 X EEx nA II T4

Fig. 6-2: Example for lateral labeling of bus modules

 

(750-400, 2 channel digital input module 24 V DC)

g01xx04e

Modular I/O System

LONWORKS®

Соседние файлы в папке 750-819