30 • Fieldbus coupler/controller Fieldbus coupler 750-319

3.1.9 Technical Data

System data

 

No. of nodes

64 without repeater, 127 with repeater

 

 

Transmission medium

Twisted Pair - FTT

 

 

Max. length of fieldbus segment

free topology 500 m,bus topology 2700 m

 

 

Topology

in accordance with LON specification

 

 

Baud rate

78 kbps

 

 

Buscoupler connection

2-pole male connector, series 231 (MCS)

 

female connector (231-302) is included

Standards and approvals

 

UL

E175199, UL 508 (applied for)

 

 

Conformity marking

CE

 

 

Technical data

 

Max. number of I/O modules

62 per node

 

 

digital signals

max. 248 (Inputs and Outputs)

 

 

analog signals

max. 124 (Inputs and Outputs)

 

 

Config. possibility

via PC with LON interface

 

 

Voltage supply

DC 24 V (-15 % / + 20 %)

 

 

Input current max

500 mA at 24 V

Efficiency of the power supply

87 %

 

 

Internal current consumption

300 mA at 5 V

 

 

Total current for I/O modules

1700 mA at 5 V

 

 

Isolation

500 V system/supply

 

 

Voltage via power jumper con-

DC 24 V (-15 % / + 20 %)

tacts

 

 

 

Current via power jumper con-

DC 10 A

tactmax

 

Transceiver

FTT 10 A

 

 

Dimensions (mm) W x H x L

51 x 65* x 100 (*from top edge of mounting rail)

 

 

Weight

ca. 180 g

 

 

EMC Immunity to interference

acc. EN 50082-2 (95)

 

 

EMC Emission of interference

acc. EN 50081-2 (94)

 

 