Fieldbus coupler/controller

• 25

Fieldbus coupler 750-319

 

 

 

3.1.7 LED display

The coupler possesses several LEDs for on site display of the coupler operating status or the complete node.

LonWorks

01

02

 

 

 

A

 

C

 

 

 

C

 

 

 

A

 

SERVICE

B

D

 

 

 

 

 

STATUS

24V

0V

 

 

ICOM

 

 

 

 

I/O

+

+

 

 

 

 

 

Fig. 3-6:

Display elements 750-319

g031902x

A differentiation between two LED groups is made.

The first group = fieldbus contains the solid color LEDs having the designation SERVICE (green), STATUS (red) und ICOM (green) indicating the operating status of the communication via LON.

The second group = internal bus consists of the three-color I/O LED (red/green/orange). This LED is used to display the status of the internal bus and software exception handling, i. e. the status of the fieldbus node.

LEDs located on the right-hand side in the coupler power supply section show the status of the supply voltage.

3.1.7.1 Blink code

Detailed fault messages are displayed with the aid of a blink code. A fault is cyclically displayed with up to 3 blink sequences.

The first blink sequence (approx. 10 Hz) starts the fault display.

The second blink sequence (approx. 1 Hz) following a pause. The number of blink pulses indicates the fault code.

The third blink sequence (approx. 1 Hz) follows after a further pause. The number of blink pulses indicates the fault argument.

Modular I/O System

LONWORKS®

26 • Fieldbus coupler/controller Fieldbus coupler 750-319

3.1.7.2 Fieldbus status

The operating status of the communication via LON is signalled via the top LED group (SERVICE, STATUS and ICOM).

The SERVICE LED is directly connected to the Service Pin of the Neuron Chip and indicates the state of the Neuron-C application.

SERVICE-

Meaning

Trouble shooting

LED

 

 

green

Configuration successfully completed.

 

(lights up for

Adress assigned and Neuron-C application is

 

half a second

active.

 

and then

 

 

remains off)

 

 

green blinks

No configuration,

Press the Service-Pin of the coupler and check

(1 second on,

no addressing of the Network Management

the Neuron-C application.

1 second off)

Tool (domain, subnet, node), Neuron-C

 

 

application is not activated yet.

 

green blinks

No Neuron-C application loaded on the

Load the Neuron-C application from your net-

(1 second on,

node.

work management tool software into the node.

2 seconds off

 

 

then remains

 

 

on)

 

 

green blinks

Watchdog Timer,

Check the Neuron-C application, if necessary

cyclically

Neuron-C application error

restart the application.

The STATUS LED indicates that a coupler is activated. This is the case when a wink task is sent and when the communication of both network manager and DPRAM interface fails.

STATUS-

Meaning

Trouble shouting

LED

 

 

red blinks

5 times within the WINK task

 

(0,5 Hz)

(fault messages basically have a greater priority

 

 

than the WINK task.

 

red blinks

DPRAM interface communication fault (has

Reset fieldbus coupler hardware by switching off

(2 Hz)

priority)

the supply voltage of the coupler for about 3

 

 

seconds.

 

 

Change the fieldbus coupler if necessary.

The ICOM-LED indicates a communication and data exchange between Neuron® Chip and µC165.

ICOM-LED

Meaning

Trouble shooting

green

Data exchange

 

off

No data exchange

Check bus system integrity

Modular I/O System

LONWORKS®

 

 

 

Fieldbus coupler/controller • 27

 

 

 

Fieldbus coupler 750-319

 

 

 

 

3.1.7.3 Node status

 

 

 

 

 

 

 

LED

Color

Meaning

 

IO

red /green

The 'I/O' LED indicates the node operation and signals faults occur-

 

 

/ orange

ring.

 

 

 

 

The coupler starts after switching on the supply voltage. The "I/O" LED flashes red. Following an error free start up the "I/O" LED changes to green steady light.

In the case of a fault the "I/O" LED continues blinking red. The fault is cyclically displayed with the blink code.

Fig. 3-7: Signalling the LED's node status

g012111e

After overcoming a fault, restart the coupler by cycling the power.

I/O-LED

Meaning

Trouble shooting

 

green

Data cycle on the internal bus

 

 

off

No data cycle on the internal bus

 

 

red

Coupler hardware defective

Change the coupler

 

red

a) When starting: internal bus is initialized

Evaluate the fault signal

(fault code

blinks

b) During operation: general internal bus fault

and fault argument)

 

red

Fault message during internal bus reset and

Evaluate the fault signal

(fault code

blinks cyclically

internal fault.

and fault argument)

 

Modular I/O System

LONWORKS®

28 • Fieldbus coupler/controller Fieldbus coupler 750-319

3.1.7.4 Fault message via the blink code of the I/O LED

Fault argument

Fault description

 

Trouble shooting

Fault code 1: Hardware and configuration fault

 

 

 

0

EEPROM check sum fault / check sum

 

Change the fieldbus coupler

 

fault in parameter area of the flash

 

 

 

 

memory

 

 

 

1

Overflow of the internal buffer memory

 

Change the fieldbus coupler

 

for the inline code

 

 

 

2

Unknown data type

 

Change the fieldbus coupler

3

Module type of the flash program

 

Change the fieldbus coupler

 

memory could not be determined / is

 

 

 

 

incorrect

 

 

 

4

Fault during writing in the flash mem-

 

Change the fieldbus coupler

 

ory

 

 

 

5

Fault when deleting the FLASH mem-

 

Change the fieldbus coupler

 

ory

 

 

 

6

Changed I/O module configuration

 

Change the fieldbus coupler

 

found after AUTORESET

 

 

 

Fault code 2: Fault in programmed configuration

 

 

 

n* (n<0, n>65)

Incorrect table entry

 

Change the entry in the configuration for

 

 

 

I/O module n.

Fault code 3: Internal bus command fault

 

 

 

0

I/O module(s) has (have) identified

 

Determine where the module bus has been

 

internal bus command as incorrect.

 

interrupted by removing the fieldbus cable.

 

 

 

Plug the end module in the middle of the

 

 

 

node. Switch the coupler off and on again.

 

 

 

If the I/O LED keeps blinking, displace the

 

 

 

end module anew. If there is only one

 

 

 

module left which is connected to the

 

 

 

coupler and if the I/O LED lights up, either

 

 

 

the module or the coupler is defective.

 

 

 

Change the defective component.

Fault code 4: Internal bus data fault

 

 

 

n* (n<0, n>65)

Interruption after the nth module

 

Replace the nth module within the node

Fault code 5: Register communication fault

 

 

 

n* (n<0, n>65)

Module bus fault during register com-

 

Replace the nth module within the node

 

munication

 

 

 

Fault code 6: Fieldbus specific fault

 

 

 

0

Fault code 6 is not implemented

 

 

 

Fault code 7: I/O module not supported

 

 

 

n*

I/O module not supported at position n

 

 

 

Fault code 8: unused

 

 

 

 

0

Fault code 8 is not used.

 

 

 

Fault code 9: CPU TRAP error

 

 

 

1

Illegal Opcode

 

 

 

2

Stack overflow

 

 

 

3

Stack underflow

 

 

 

4NMI

* The number of blink pulses (n) indicates the position of the I/O module. I/O modules without data are not counted (i.e. supply module without diagnosis)

Example: the 13th I/O module is removed.

1.The "I/O" LED generates a fault display with the first blink sequence (approx. 10 Hz).

2.The first pause is followed by the second blink sequence (approx. 1 Hz). The "I/O" LED blinks four times and thus signals the fault code 4 (internal bus data fault).

3.The third blink sequence follows the second pause. The "I/O" LED blinks twelve times. The fault argument 12 means that the internal bus is interrupted after the 12th I/O module.

Modular I/O System

LONWORKS®