6 CALCULATION AND ANALYSIS OF NETWORK MODE

6.1 Preparation of input data. Calculation of modes

Perform the calculation of the maximum and minimum load. The results of the calculations will determine the loss of power and electricity to the grid. This will develop measures for their reduction and to evaluate the effectiveness of such measures.Calculate carry out sustainable mode using DigSILENT Power Factory. In Fig. 6.1 shows the design diagram network.To assess the adequacy of the control range of transformers is performed calculations desired voltage level on the tires according to the method of counter-consumer regulation. Calculation is made as follows.

Results of the calculation given in table 6.1.

Table 6.1 - Results of the calculation of the desired voltage at the bus-bars consumers

Name of substation

Pmax

МВт

Pmin

МВт

%

Uном мер

кВ

Uбаж max

кВ

Uбаж min

кВ

Gorniak-110 (T1)

Т1

6,48

1,68

-0,29

6,00

10,05

5,98

Stazhkovo-35 (T1)

Т1

1,98

1,44

3,05

6,00

8,90

6,18

Т2

1,20

0,72

2,14

6,00

4,41

6,13

Davydovka-35 (T1)

Т1

2,64

1,39

1,62

6,00

8,47

6,10

Т2

2,70

1,08

0,71

6,00

6,53

6,04

Drowing 6.1 – Calculation scheme in the DigSILENT Power Factory for the site of an electric network which is considered

Input data to the graph for mode calculation the presented in a table 6.2 – 6.5.

Table 6.2 - Input data for the calculation scheme

Name of substation

Uном

кВ

Type switchgear

Gorniak-110 (T1)

35

Two of the bus bar system

Stazhkovo-35 (T1)

35

Two of the bus bar system

6

Two of the bus barsystem

Davydovka-35 (T1)

35

Two of the bus bar system

6

Two of the bus bar system

Table 6.3 - Data of lines of electricity transmissions

Section

Brand wire

R0 Ом/км

X0 Ом/км

B0·10-6 См/км

l

км

nкіл

Uном

Postnikovo-Stazh.

АС-185/34

0,428

0,432

0

4,88

1

35

Stazhkovo –Dav.

АС-150/27

0,198

0,406

0

0,025

1

35

АС-150/27

0,198

0,406

0

0,612

1

35

СА-70

0,428

0,432

0

5,64

1

35

Dav. - Gorniak

АС-95/16

0,306

0,421

0

6,88

1

35

Gorniak- – Davydovka Severn

АС-120/19

0,249

0,414

0

3,42

1

35

Table 6.4 – Data of transformers of a network of 35 kV according to 2013

тр

Name of substation

Type of transformer

Scheme and group of connection of windings

SНОМ

МВА

UВН

кВ

UНН

кВ

1

2

3

4

5

6

7

1

Gorniak-110 (T1)

ТДН-25000/35

Y\D-11

25

36,75

6,6

2

Stazhkovo-35 (T1)

ТД-10000/35

Y\D-11

10

36,75

6,3

3

Stazhkovo-35 (T2)

ТД-10000/35

Y\D-11

10

36,75

6,3

4

Davydovka-35 (T1)

ТД-15000/35

Yo\D-11

15

36,75

6,6

5

Davydovka-35 (T2)

ТД-15000/35

Yo\D-11

15

38

6,3

table 6.4 continuation

тр

Name of substation

DPК

кВт

DPХ

кВт

UК

%

Iх

%

Обм.

рег.

№ ст.

% ст.

1

2

8

9

10

11

12

13

14

1

Gorniak-110 (T1)

145

25,8

14,72

0,65

1

±4

2,5

2

Stazhkovo-35 (T1)

66

48,8

7,89

0,75

1

±2

2,5

3

Stazhkovo-35 (T2)

90

21,3

9,3

0,75

1

±2

2,5

4

Davydovka-35 (T1)

124

32

8,9

0,72

1

±2

2,5

5

Davydovka-35 (T2)

137

26

9,8

0,72

1

±2

2,5

Table 6.5 – Date of the load node of network 35 kV

Name of substation

Maximum power mode

Minimum power mode

РМ

МВт

QМ

Мвар

QКУ

Мвар

Рм

МВт

Qм

Мвар

QКУ

Мвар

Gorniak-110 (T1)

6,48

2,16

-

1,68

1,44

-

Stazhkovo-35 (T1)

1,98

0,36

-

1,44

1,08

-

Stazhkovo-35 (T2)

1,20

0,84

-

0,72

0,52

-

Davydovka-35 (T1)

2,64

1,44

-

1,39

0,98

-

Davydovka-35 (T2)

2,70

0,90

-

1,08

1,08

-

For an assessment of indicators of functioning of a projected network we will execute calculation of modes of the maximum and minimum loadings. Results of calculation of modes are presented in Addition B.